Further information for Schneider Electric A9Z21425 RCD 4-pole 25A
Additional features
Network frequency
50/60 Hz
[Ue] Rated operational voltage
400 - 415 V AC 50/60 Hz
Earth fault trip technology
Voltage-independent
Rated breaking force and rated power
Idm 1500 A; IM 1500 A
Conditional rated short-circuit current
10 kA
[Ui] Rated insulation voltage
500 V AC 50/60 Hz
[Uimp] Rated impulse voltage withstand
6 kV
Control type
Toggle switch
Mounting mode
Plug-in
Mounting bracket
35 mm DIN rail
9-mm pitch
8
Height
91 mm
Width
72 mm
Depth
73 mm
Product weight
370 g
Colour
White (RAL 9003)
Mechanical life
20000 cycles
Electrical lifetime
15000 cycles
Description of locking options
Padlock
Connections - terminals
Double terminal front side 1…35 mm² solid; Double terminal front side 1…25 mm² fine-stranded; Double terminal front side 1…25 mm² fine-stranded with ferrule; Double terminal rear side 1…25 mm² solid; Double terminal rear side 1…16 mm² fine-stranded; Double terminal rear side 1…16 mm² fine-stranded with ferrule
Wire stripping length
14 mm for top or bottom connection
[M] tightening torque
3.5 Nm top or bottom
Contact position indicator
Contractual warranty
Warranty (in months)
18
Main features
Product series
Acti9
Product name
Acti9 iID
Product or component type
Residual current circuit breaker (RCCB)
Device short name
iID
Pole description
4P
Neutral position
Left
[In] Rated current
25 A
Type of network
AC
Earth fault sensitivity
30 mA
Earth fault protection time delay
Instantaneous
Earth fault protection class
Type A
Mounting
Standards
EN/IEC 61008-1; EN/IEC 61008-2-1
Degree of protection (IP)
IP20 corresponds to IEC 60529; IP40 (modular housing) corresponds to IEC 60529
Pollution degree
3
Electromagnetic compatibility
8/20 µs impulse resistance, 250 A according to EN/IEC 61008-1
Operating ambient temperature
-25…60 °C
Ambient temperature during storage
-40…85 °C
Packaging units
VPE 1 type
PCE
Number of devices per package
1
VPE 1 height
7,500 cm
VPE 1 width
8,000 cm
VPE 1 length
10,000 cm
Packaging weight (Lbs)
377,500 g
VPE 2 type
S03
VPE 2 quantity
27
VPE 2 height
30,000 cm
VPE 2 width
30,000 cm
VPE 2 length
40,000 cm
VPE 2 weight
10,493 kg
VPE 3 type
P12
VPE 3 quantity
216
VPE 3 height
45,000 cm
VPE 3 width
80,000 cm
VPE 3 length
120,000 cm
VPE 3 weight
97,252 kg
The Acti9 iID residual current circuit breaker from Schneider Electric, type A9Z21425, is a 4-pole RCD designed for use in electrical distributions. It protects circuits from dangerous earth fault currents and provides additional protection against direct contact with a sensitivity of 30 mA. The Type A protection class enables detection of pulsating fault currents, which is essential for applications involving electronic devices or non-sinusoidal loads. The device is rated for an operating voltage of 400 to 415 V AC and complies with standards EN/IEC 61008-1 and EN/IEC 61008-2-1. The rated current is 25 A, with a conditional rated short-circuit current of 10 kA. The tripping mechanism is voltage-independent, ensuring reliable operation even during voltage fluctuations.
Applications
This circuit breaker is suitable for use in industrial and commercial installations, as well as in residential and office buildings. It protects against both direct and indirect contact, with the 30 mA sensitivity ensuring protection during direct contact. In case of insulation faults or electrical system failures, immediate tripping interrupts dangerous fault currents. The protective function remains effective in construction power distributors with a sensitivity of 500 mA. Switching is performed via a toggle switch, enabling tool-free mounting on the left side of the device.
Functions and Features in Detail
The switch features a mechanical front-mounted fault indication (VisiTrip), which signals tripping due to overload or short circuit. The safe contact indication (VisiSafe) shows green when the output side is de-energized, which is important for maintenance or inspections. An integrated test button allows for regular functional testing. Dual connection terminals on the front and rear enable two-sided cable or phase bar connections. The wire stripping length is 14 mm, and the tightening torque for the terminals is specified at 3.5 Nm. Mounting is on a 35 mm DIN rail, with the device occupying an 8 mm pitch.
Technology Explained Simply
The snap-action switching ensures wear-free contact operation, increasing the service life. The mechanical life is 20,000 cycles, and the electrical life is 15,000 cycles. The rated insulation voltage is 500 V AC, and the rated impulse voltage withstand is 6 kV. The protection rating IP20 corresponds to IEC 60529, while the modular housing achieves IP40. The pollution degree is rated 3, indicating suitability for environments with increased contamination risk. The operating ambient temperature ranges from -25 °C to 60 °C, and the storage temperature ranges from -40 °C to 85 °C.
Compatibility and Accessories
Additional auxiliary modules can be mounted in series to extend functionality. These include undervoltage release (iMN), overvoltage release (iMSU), load current release (iMX), auxiliary switches for status indication (iOF), and fault indication switches (iSD). These modules can be adapted according to system requirements. Locking options include a padlock attachment, enabling secure locking of the switch.
Mounting and Installation
Mounting is on a 35 mm DIN rail, with the device occupying an 8 mm pitch. The front side is designed for mounting auxiliary modules. The device can be easily removed even with an installed phase bar, as the mounting element is accessible from the front. The device color is white (RAL 9003), enabling uniform visual design in distributions.
Operational Advantages
The circuit breaker offers high reliability due to its voltage-independent tripping mechanism and immediate response to fault currents. The integrated indicators (VisiTrip, VisiSafe) simplify maintenance and inspection. Tool-free mounting and two-sided dual terminals speed up installation. The long service life and compatibility with various auxiliary modules increase system flexibility and maintainability. Certification according to VDE and compliance with standards IEC/EN 61008-1 and IEC/EN 60947-2 ensure the quality and safety of the device.