| Additional features |
| Device position in system | Outlet |
| Earth fault trip technology | Voltage-independent |
| [Ui] Rated insulation voltage | 500 V AC 50/60 Hz corresponds to IEC 60947-2 |
| [Uimp] Rated impulse voltage withstand | 6 kV corresponds to IEC 60947-2 |
| Compatible product family | Acti9 iC60 circuit breaker |
| Product compatibility | IC60H/N double terminal miniature circuit-breaker |
| Local signalling | trip indicator |
| Mounting mode | Plug-in |
| Mounting bracket | DIN rail |
| Electrical connection for LS switch | With screws |
| Height | 91 mm |
| Width | 72 mm |
| Depth | 74 mm |
| Product weight | 0,165 kg |
| Connections - terminals | Tunnel terminals bottom side 1…35 mm² solid; tunnel terminals bottom side 1…25 mm² stranded |
| Wire stripping length | 14 mm |
| [M] tightening torque | 3,5 Nm |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | Acti9 |
| Product name | Acti9 Vigi iC60 |
| Product or component type | Additional residual current protective devices |
| Device short name | Vigi iC60 |
| Pole description | 2P |
| [In] Rated current | 63 A |
| Earth fault sensitivity | 30 mA |
| Earth fault protection time delay | Instantaneous |
| Residual current protection type | Type A |
| Type of network | AC |
| Network frequency | 50/60 Hz |
| [Ue] Rated operational voltage | 230/400 V AC 50/60 Hz conforms to EN 61009-1; 230/240 V AC 50/60 Hz conforms to IEC 61009-1 |
| Standards | EN 61009-1; IEC 61009-1 |
| 9-mm pitch | 4 |
| Mounting |
| Degree of protection (IP) | IP20 corresponds to IEC 60529; IP40 (modular housing) corresponds to IEC 60529 |
| Pollution degree | 3 corresponds to IEC 60947-2 |
| Electromagnetic compatibility | 8/20 µs impulse resistance, 250 A corresponds to IEC 61009-1 |
| Operating ambient temperature | -25…60 °C |
| Ambient temperature during storage | -40…85 °C |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 8,2 cm |
| VPE 1 width | 7,8 cm |
| VPE 1 length | 11,3 cm |
| Packaging weight (Lbs) | 189,0 g |
| VPE 2 type | S03 |
| VPE 2 quantity | 27 |
| VPE 2 height | 30 cm |
| VPE 2 width | 30 cm |
| VPE 2 length | 40 cm |
| VPE 2 weight | 5,587 kg |
The product A9W21263 from Schneider Electric is a
residual current circuit breaker of the Acti9 series, specifically designed as a
Vigi iC60. It is a
2-pole RCD module intended to be mounted as an additional residual current protection device on circuit breakers of the iC60N/H series. The device is designed for use in electrical installations where high safety against dangerous fault currents is required, particularly in residential and commercial buildings as well as industrial installations with increased protection requirements.
Applications
This RCD module is designed for use in electrical distributions requiring a
residual current sensitivity of 30 mA. This sensitivity is typical for protection measures against electric shock, especially in areas with increased risk of contact, such as bathrooms, kitchens, or workshops. The
instantaneous tripping upon detection of a fault current ensures rapid disconnection to protect people from dangerous currents. The
operating voltage is 230/400 V AC at 50/60 Hz, enabling use in standard power networks in Europe and other regions with corresponding voltage levels.
Functions and Features in Detail
The device features a
trip indication, visible via a red mechanical marking on the handle, indicating whether tripping occurred due to a fault current. This facilitates maintenance and quick identification of faults. A
test button allows regular functional testing to ensure the reliability of the protective device. The
residual current tripping technology is voltage-independent, meaning the protection remains functional even during voltage dips or outages. The
residual current protection type is Type A, enabling detection of pulsating direct current components, such as those occurring in devices with electronic power supplies.
Technical Explanation
The tripping unit operates using
thermal-magnetic technology, allowing the device to respond to both overloads (thermally) and short circuits (magnetically). The
rated insulation voltage is 500 V AC, ensuring sufficient electrical insulation for use in distribution switchgear. The
rated impulse withstand voltage of 6 kV protects the device against transient voltage surges caused by lightning strikes or switching operations. The
protection rating IP20 for the terminals means the device is protected against contact with fingers and against solid foreign objects, but not against splashing water or dust. In the modular enclosure, a protection rating of IP40 is provided, offering protection against splashing water and larger foreign objects.
Compatibility and Accessories
The RCD module is specifically designed for mounting on
circuit breakers of the iC60N/H series and can be clipped on to the right side of these devices. Compatibility includes both iC60H and iC60N variants with dual terminal connections. Additionally,
auxiliary modules such as fault alarm switches, auxiliary switches, under-voltage release, over-voltage release, or load current release can be connected to extend the functionality of the switch. Mounting is done on a
DIN rail, enabling standardized and secure installation in enclosures.
Mounting and Installation
Mounting is performed by
clipping onto the corresponding circuit breaker. Electrical connections are made via
tunnel terminals on the underside, designed for solid cable up to 35 mm² and flexible cable up to 25 mm². The
wire stripping length is 14 mm, and the
torque for the terminals is 3.5 Nm. The dimensions of the device are 91 mm (height), 72 mm (width), and 74 mm (depth), mounted on a 9 mm grid. The
operating ambient temperature ranges from -25 °C to 60 °C, allowing use in a wide variety of environments.
Operational Advantages
The RCD module provides reliable protection against dangerous fault currents with high sensitivity of 30 mA. The mechanical trip indication and test button simplify maintenance and functional checks. Compatibility with the iC60 series and the ability to connect additional auxiliary modules increase flexibility and adaptability to specific requirements. Compliance with standards
IEC/EN 61009-1 and
VDE certification guarantee the safety and quality of the product. The operating voltage and insulation voltage are designed for typical distribution systems, enabling universal use in various applications.