| Complementary |
| Device location in system | Outgoer |
| Residual current tripping technology | Voltage independent |
| [Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| Range compatibility | Acti9 iC60 miniature circuit-breaker; Acti9 Reflex iC60 integrated control circuit breaker |
| Product compatibility | IC60a/N/H/L/P single terminal miniature circuit-breaker |
| Local signalling | Trip indicator |
| Mounting mode | Clip-on |
| Mounting support | DIN rail |
| Electrical connection to mcb | By screws |
| Comb busbar and distribution block compatibility | Bottom: YES |
| Height | 91 mm |
| Width | 63 mm |
| Depth | 73.5 mm |
| Net weight | 0.165 kg |
| Connections - terminals | Tunnel type terminal downside for 1 cable(s) 1…25 mm² rigid without cable end; Tunnel type terminal downside for 1 cable(s) 1…16 mm² flexible without cable end; Tunnel type terminal downside for 1 cable(s) 1…16 mm² flexible with cable end |
| Wire stripping length | 14 mm for bottom connection |
| Tightening torque | 2 N.m bottom |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP20 conforming to IEC 60529; IP40 (modular enclosure) conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60947-2 |
| Electromagnetic compatibility | 8/20 µs impulse withstand, 250 A conforming to IEC 61009-1 |
| Ambient air temperature for operation | -25…60 °C |
| Ambient air temperature for storage | -40…85 °C |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | Acti9 |
| Product name | Acti9 Vigi iC60 |
| Product or component type | Add-on residual current device |
| Device short name | Vigi iC60 |
| Poles description | 2P |
| [In] rated current | 25 A |
| Earth-leakage sensitivity | 30 mA |
| Earth-leakage protection time delay | Instantaneous |
| Earth leakage protection type | Type A |
| Network type | AC |
| Network frequency | 50/60 Hz |
| [Ue] rated operational voltage | 230...240 V AC 50/60 Hz conforming to EN/IEC 61009-1; 230...240 V AC 50/60 Hz conforming to EN/IEC 61009-2-1 |
| Standards | EN/IEC 61009-1; EN/IEC 61009-2-1 |
| 9 mm pitches | 3 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 8.800 cm |
| Package 1 Width | 13.400 cm |
| Package 1 Length | 14.600 cm |
| Package 1 Weight | 145.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 27 |
| Package 2 Height | 30 cm |
| Package 2 Width | 30 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 4.439 kg |
The product is a residual current circuit breaker of the Acti9 series by Schneider Electric, type A9V51225, specifically designed as a Vigi iC60 FI module. It is an additional residual current protection device that is mounted directly onto circuit breakers of the iC60L series. The unit is intended for use in branch circuits and provides instantaneous protection at a residual current of 30 mA. The protection device is designed for operation in alternating current networks, with a rated operational voltage of 230 to 240 V AC at 50/60 Hz. The rated insulation voltage is 500 V AC, and the rated impulse withstand voltage is 6 kV, ensuring high electrical strength. The unit complies with standards EN/IEC 61009-1 and EN/IEC 61009-2-1 and is VDE-certified.
Applications
The FI module is designed for use in electrical installations where high protection against electric shock is required, particularly in residential and commercial buildings. It is suitable for applications requiring rapid disconnection at a residual current of 30 mA to protect people from dangerous touch currents. The unit is intended for indoor use, as the protection rating IP20 (terminals) and IP40 (modular housing) does not provide protection against water or dust. The operating ambient temperature ranges from -25 °C to 60 °C, allowing use under normal indoor conditions.
Functions and Equipment in Detail
The protection device is 2-pole and has a rated current of 25 A. The residual current tripping technology is voltage-independent, meaning tripping occurs even with fluctuating network voltage. Tripping is indicated by a red mechanical indicator on the handle, visually informing the operator of the tripping status. A test button allows regular functional testing to ensure the reliability of the protection device. The tripping unit operates on a thermomagnetic principle, combining thermal and magnetic tripping.
Technology Explained Simply
The FI module detects residual currents caused by leakage in the electrical system and disconnects the circuit within milliseconds. The sensitivity of 30 mA is typical for personal protection and meets common safety requirements. The instantaneous tripping ensures the circuit is immediately disconnected as soon as a residual current is detected. The voltage-independent technology ensures the protection device functions even during voltage fluctuations or voltage dips. The terminals are designed as tunnel terminals, enabling connections for solid and flexible conductors with cross-sections of 1 to 25 mm² (solid) and 1 to 16 mm² (flexible), with a wire stripping length of 14 mm. The tightening torque for the terminals is 2 Nm.
Compatibility and Accessories
The FI module is compatible with circuit breakers of the iC60L series as well as with the Acti9 Reflex iC60 built-in control power switch. Installation is done by mounting directly onto a DIN rail, with the unit being 3 modules (9 mm) wide. Optional auxiliary modules such as fault indicator switches, auxiliary switches, under-voltage release, over-voltage release, or load current release can be added to extend functionality. Suitable accessories include, for example, the LS switch iC60L 2p C 16A (item A9F94216) or the LS switch iC60L 2p C 10A (item A9F94210).
Installation and Mounting
Mounting is done on a DIN rail, with the unit attached to the right side of a compatible circuit breaker. Electrical connections are made via screw terminals at the bottom. The terminals are designed for connecting solid and flexible conductors, with specified maximum cross-sections and tightening torque. The unit is intended for indoor use, with protection rating IP20 (terminals) and IP40 (modular housing) providing no protection against water or dust. The ambient temperature during operation ranges from -25 °C to 60 °C.
Operational Advantages
The FI module provides reliable personal protection through rapid disconnection at a residual current of 30 mA. The visual tripping indicator and test button enable easy verification of functionality. Compatibility with the iC60L series and the option to add auxiliary modules expand application possibilities. The thermomagnetic tripping technology ensures precise and reliable disconnection. The unit is designed for indoor use and complies with applicable standards and certifications.