Further information for Schneider Electric A9S65363 Disconnect Switch 3P 63A
Complementary
[Ie] rated operational current
63 A at 415 V AC 50/60 Hz
[Ue] rated operational voltage
415 V AC 50/60 Hz
[Icm] rated short-circuit making capacity
5 kA switch-disconnector alone
[Icw] rated short-time withstand current
1260 A
[Ui] rated insulation voltage
500 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage
6 kV
Control type
Toggle
Local signalling
ON/OFF indication
Mounting mode
Fixed
Mounting support
DIN rail
Comb busbar and distribution block compatibility
Top or bottom: YES
9 mm pitches
6
Height
85 mm
Width
54 mm
Depth
73 mm
Colour
White
Mechanical durability
20000 cycles
Electrical durability
15000 cycles
Connections - terminals
Tunnel type terminals (top or bottom) -
Wire stripping length
14 mm
Tightening torque
3.5 N.m
Contact position indicator
Contractual warranty
Warranty (in months)
18
Environment
Standards
IEC 60947-3; EN 60947-3
IP degree of protection
IP20
Pollution degree
3
Tropicalisation
2
Relative humidity
95 % at 55 °C
Ambient air temperature for operation
-25…60 °C
Ambient air temperature for storage
-40…85 °C
Logistical informations
Country of origin
HU
Main
Range
Acti9
Product name
Acti9 iSW
Product or component type
Switch disconnector
Device short name
iSW
Device application
Isolation; Control
Poles description
3P
Utilisation category
AC-22A
Suitability for isolation
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
5.500 cm
Package 1 Width
7.500 cm
Package 1 Length
9.500 cm
Package 1 Weight
250.800 g
Unit Type of Package 2
BB1
Number of Units in Package 2
4
Package 2 Height
8.500 cm
Package 2 Width
10.000 cm
Package 2 Length
22.000 cm
Package 2 Weight
1.059 kg
Unit Type of Package 3
S03
Number of Units in Package 3
44
Package 3 Height
30.000 cm
Package 3 Width
30.000 cm
Package 3 Length
40.000 cm
Package 3 Weight
12.096 kg
The Acti9 iSW load disconnector from Schneider Electric, type A9S65363, is a 3-pole switch for isolating and controlling electrical circuits. It is designed for use in industrial and commercial installations where safe disconnection of circuits under load is required. The device belongs to the Acti9 series and features a rated operational current of 63 A at an operating voltage of 415 V AC (50/60 Hz). The rated insulation voltage is 500 V AC, enabling safe electrical isolation even at higher voltages. The rated short-circuit making capacity is 5 kA when operated alone, and the rated short-time withstand current is 1260 A. The rated impulse voltage withstand is specified at 6 kV, ensuring robustness against transient voltage surges.
Applications
This load disconnector is intended for applications in electrical distribution technology, particularly in enclosures and distribution boxes. It enables safe isolation of circuits to allow maintenance or repairs to be carried out under safe conditions. The usage category AC-22A specifies that the switch is suitable for operation with alternating current in installations with inductive loads. The suitability for isolation is explicitly confirmed, qualifying it for use in installations with high safety requirements.
Functions and Equipment in Detail
The switch features a toggle switch as the control type, enabling clear and unambiguous operation. Local signaling is provided via an ON/OFF indicator, with the switch position indicated by a green marking on the operating handle, ensuring visual control of the switch position even from a distance. The contact position indicator is also integrated, allowing the state of the contacts to be checked. Mounting is tool-free on the left side of the device, accelerating installation in enclosures. The device color is white, corresponding to RAL 9003.
Technology Explained Simply
The tunnel terminals allow flexible connection of conductors, with connections possible both top and bottom. The required wire stripping length is 14 mm, and the tightening torque for the terminals is specified as 3.5 Nm. The mechanical life is 20,000 cycles, and the electrical life is 15,000 cycles, indicating high operational reliability and longevity. Mounting is on DIN rail, ensuring standardization in electrical installations. Compatibility with comb busbars and distribution blocks is provided both top and bottom, increasing installation flexibility.
Compatibility and Accessories
Additional stackable auxiliary modules such as the iOF auxiliary switch enable status signaling of the switch, which is useful for remote monitoring systems or controls. Compatibility with various phase bar modules such as A9XPH309, A9XPH324, or A9XPH306 is provided, allowing integration into existing distribution systems. Additional compatible accessories include locking elements, rotary drives, terminal covers, and sockets, which can be added depending on the application scenario.
Mounting and Installation
Mounting is fixed on DIN rail, with device dimensions of 85 mm (height), 54 mm (width), and 73 mm (depth). The device conforms to the 9 mm grid and occupies 6 grid positions. The operating ambient temperature ranges from -25 °C to 60 °C, and storage temperature ranges from -40 °C to 85 °C. Relative humidity is up to 95 % at 55 °C. The protection rating IP20 protects against finger contact and vertical dripping water, making it suitable for indoor use. Pollution degree 3 and drip proof class 2 indicate use in environments with increased contamination risk.
Advantages in Operation
The load disconnector offers clear visual indication of switch position, high service life, and tool-free mounting, reducing installation time. Compatibility with various accessory modules extends functionality, and compliance with standards IEC 60947-3 and EN 60947-3 ensures conformity with international safety standards. The rated data are designed for industrial applications, ensuring reliable performance under load conditions.