Further information for Schneider Electric A9N61526 circuit breaker 2-pole C60H-DC 6A
Complementary
Network frequency
50/60 Hz
[Ue] rated operational voltage
500 V DC
[Ics] rated service breaking capacity
15 kA 75 % conforming to EN 60947-2 - 220 V DC; 15 kA 75 % conforming to IEC 60947-2 - 220 V DC; 15 kA 75 % conforming to EN 60947-2 - 250 V DC; 15 kA 75 % conforming to IEC 60947-2 - 250 V DC; 4.5 kA 75 % conforming to EN 60947-2 - 500 V DC; 4.5 kA 75 % conforming to IEC 60947-2 - 500 V DC; 7.5 kA 75 % conforming to EN 60947-2 - 440 V DC; 7.5 kA 75 % conforming to IEC 60947-2 - 440 V DC
[Ui] rated insulation voltage
500 V DC conforming to IEC 60947-2; 500 V DC conforming to EN 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to EN 60947-2; 6 kV conforming to IEC 60947-2
Control type
Toggle
Local signalling
ON/OFF indication
Mounting mode
Fixed
Mounting support
35 mm symmetrical DIN rail
Comb busbar and distribution block compatibility
Top or bottom: standard
9 mm pitches
4
Net weight
0.256 kg
Colour
White
Mechanical durability
20000 cycles
Electrical durability
3000 cycles L/R = 2 ms
Provision for padlocking
Padlockable
Locking options description
In position O
Tightening torque
Power circuit: 2.5 N.m top or bottom
Earth-leakage protection
Without
Contact position indicator
Contractual warranty
Warranty (in months)
18
Environment
Pollution degree
3 conforming to EN 60947-2; 3 conforming to IEC 60947-2
Overvoltage category
IV
Tropicalisation
2 conforming to IEC 60068-2
Operating altitude
2000 m
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-40…85 °C
Logistical informations
Country of origin
CN
Main
Range
Acti9
Product name
Acti9 C60H-DC
Product or component type
Miniature circuit-breaker
Device short name
C60H-DC
Device application
Distribution
Poles description
2P
Number of protected poles
2
[In] rated current
6 A at 25 °C
Network type
DC
Trip unit technology
Thermal-magnetic
Curve code
C
Breaking capacity
10 kA Icu at 440 V DC conforming to EN 60947-2; 10 kA Icu at 440 V DC conforming to IEC 60947-2; 6 kA Icu at 500 V DC conforming to EN 60947-2; 6 kA Icu at 500 V DC conforming to IEC 60947-2; 20 kA Icu at 220 V DC conforming to GB 14048.2; 20 kA Icu at 220 V DC conforming to IEC 60947-2; 20 kA Icu at 250 V DC conforming to GB 14048.2; 20 kA Icu at 250 V DC conforming to IEC 60947-2
Utilisation category
Category A conforming to EN 60947-2; Category A conforming to IEC 60947-2
Suitability for isolation
Yes conforming to IEC 60947-2; Yes conforming to EN 60947-2
Standards
EN 60947-2; IEC 60947-2
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
3.500 cm
Package 1 Width
7.200 cm
Package 1 Length
8.300 cm
Package 1 Weight
224.000 g
Unit Type of Package 2
BB1
Number of Units in Package 2
6
Package 2 Height
8.400 cm
Package 2 Width
9.200 cm
Package 2 Length
22.700 cm
Package 2 Weight
1.390 kg
Unit Type of Package 3
S03
Number of Units in Package 3
72
Package 3 Height
30.000 cm
Package 3 Width
30.000 cm
Package 3 Length
40.000 cm
Package 3 Weight
17.262 kg
The circuit breaker Acti9 C60H-DC from Schneider Electric is a two-pole (2P) switch for direct current (DC) applications with a rated current of 6 A at an ambient temperature of 25 °C. It belongs to the Acti9 series and is designed for use in distribution systems. The protection function is achieved through thermomagnetic tripping technology, which combines both thermal and magnetic tripping mechanisms to ensure safe disconnection in case of overload and short circuit. The C-characteristic of the trip curve ensures selective disconnection during transient load peaks, thereby increasing the reliability of the power supply.
Applications
The switch is designed for industrial and technical applications where safe and reliable power distribution at direct voltage is required. It is suitable for use in energy technology installations, solar systems, automation technology, or vehicle systems. The operating voltage is up to 500 V DC, with the device specified for various voltage levels and different breaking capacities: 20 kA Icu at 220 V DC and 250 V DC, 10 kA Icu at 440 V DC, and 6 kA Icu at 500 V DC. These values comply with standards EN 60947-2 and IEC 60947-2. The usage category is defined as Category A, enabling use in distribution systems with direct connection to the power supply.
Functions and Equipment in Detail
The device features a contact position indicator, which visually signals the current position (ON/OFF). Control is performed via a toggle switch, enabling simple and secure operation. Mounting is tool-free on a 35 mm symmetrical DIN rail, with fastening achieved via a clip lock. Connections are located on the top and bottom of the device and support connections with cables and pin rail terminals. The torque values for the current circuits are 2.5 Nm, with terminals connectable both on top and bottom. The device is lockable and can be secured in the "O" (off) position, which is useful for maintenance work or safety measures.
Technology Explained Simply
The thermomagnetic tripping technology combines two protection principles: during a prolonged overload, a bimetal strip heats up and triggers the switch after a certain time. In case of a sudden short circuit, a magnetic tripping mechanism reacts immediately to quickly interrupt the high current. The C-characteristic means that the switch does not trip at current values up to approximately 5 times the rated current (30 A at 6 A nominal current), making it suitable for systems with high inrush currents. The rated insulation voltage (Ui) is 500 V DC, ensuring electrical insulation for operation at this voltage. The rated impulse voltage withstand (Uimp) of 6 kV protects the device against transient voltage surges.
Compatibility and Accessories
The switch is compatible with various accessory modules that can be optionally mounted. These include auxiliary switches such as the A9N26904 (OF 1OC, 100 mA–6 A AC/DC, connection bottom), current release devices such as the A9N26946 (MX+OF, 220–415 V AC, 110–130 V DC), or undervoltage release devices such as the A9N26969 (MNX, 230 VAC). Additionally, phase rail modules such as the A9XPH206 (2P, 6 modules, 100 A) or A9XPH257 (2-pole, 57 TE, adjustable, 100 A) are available, enabling flexible integration into distribution systems. Mounting is possible on a 35 mm DIN rail, with the device occupying 4 modules (9-mm pitch).
Mounting and Installation
Mounting is tool-free on a 35 mm symmetrical DIN rail. Connections are located on the top and bottom of the device, allowing flexible integration into existing switchgear. The terminals are designed for cables and pin rail terminals. The mechanical life is 20,000 cycles, and the electrical life is 3,000 cycles at a load constant of L/R = 2 ms. The operating temperature range is from -25 °C to +70 °C, and the storage temperature range is from -40 °C to +85 °C. The operating altitude is limited to 2,000 m above sea level. The device is designed for pollution degree 3 and overvoltage category IV, enabling use in industrial environments with increased pollution risk and transient voltage surges.
Advantages in Operation
The switch offers high reliability through thermomagnetic tripping technology and the C-characteristic, which ensures selective disconnection. Tool-free mounting and the integrated contact position indicator simplify installation and maintenance. The lockable feature in the "O" position increases safety during maintenance work. Compatibility with various accessory modules allows flexible adaptation to specific requirements. The device is designed for a long service life, reducing maintenance costs and increasing operational safety. Compliance with standards EN 60947-2 and IEC 60947-2 ensures safe and standard-compliant use in industrial installations.