Further information for Schneider Electric A9N61508 circuit breaker 1p C 10A
Complementary
Network frequency
50/60 Hz
[Ue] rated operational voltage
250 V DC
[Ics] rated service breaking capacity
15 kA 75 % conforming to EN 60947-2 - 110 V DC; 15 kA 75 % conforming to IEC 60947-2 - 110 V DC; 4.5 kA 75 % conforming to EN 60947-2 - 250 V DC; 4.5 kA 75 % conforming to IEC 60947-2 - 250 V DC; 7.5 kA 75 % conforming to EN 60947-2 - 220 V DC; 7.5 kA 75 % conforming to IEC 60947-2 - 220 V DC
[Ui] rated insulation voltage
500 V DC conforming to IEC 60947-2; 500 V DC conforming to EN 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to EN 60947-2; 6 kV conforming to IEC 60947-2
Control type
Toggle
Local signalling
ON/OFF indication
Mounting mode
Fixed
Mounting support
35 mm symmetrical DIN rail
Comb busbar and distribution block compatibility
Top or bottom: standard
9 mm pitches
2
Net weight
0.128 kg
Colour
White
Mechanical durability
20000 cycles
Electrical durability
3000 cycles L/R = 2 ms
Provision for padlocking
Padlockable
Locking options description
In position O
Tightening torque
Power circuit: 2.5 N.m top or bottom
Earth-leakage protection
Without
Contact position indicator
Contractual warranty
Warranty (in months)
18
Environment
Pollution degree
3 conforming to EN 60947-2; 3 conforming to IEC 60947-2
Overvoltage category
IV
Tropicalisation
2 conforming to IEC 60068-2
Operating altitude
2000 m
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-40…85 °C
Logistical informations
Country of origin
CN
Main
Range
Acti9
Product name
Acti9 C60H-DC
Product or component type
Miniature circuit-breaker
Device short name
C60H-DC
Device application
Distribution
Poles description
1P
Number of protected poles
1
[In] rated current
10 A at 25 °C
Network type
DC
Trip unit technology
Thermal-magnetic
Curve code
C
Breaking capacity
10 kA Icu at 220 V DC conforming to EN 60947-2; 10 kA Icu at 220 V DC conforming to IEC 60947-2; 6 kA Icu at 250 V DC conforming to EN 60947-2; 6 kA Icu at 250 V DC conforming to IEC 60947-2; 20 kA Icu at 110 V DC conforming to EN 60947-2; 20 kA Icu at 110 V DC conforming to IEC 60947-2
Utilisation category
Category A conforming to EN 60947-2; Category A conforming to IEC 60947-2
Suitability for isolation
Yes conforming to IEC 60947-2; Yes conforming to EN 60947-2
Standards
EN 60947-2; IEC 60947-2
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
1.700 cm
Package 1 Width
7.000 cm
Package 1 Length
8.400 cm
Package 1 Weight
110.000 g
Unit Type of Package 2
BB1
Number of Units in Package 2
12
Package 2 Height
8.300 cm
Package 2 Width
9.000 cm
Package 2 Length
22.500 cm
Package 2 Weight
1.380 kg
Unit Type of Package 3
S03
Number of Units in Package 3
144
Package 3 Height
30.000 cm
Package 3 Width
30.000 cm
Package 3 Length
40.000 cm
Package 3 Weight
17.035 kg
The circuit breaker Acti9 C60H-DC from Schneider Electric is a 1-pole protection switch for direct current applications. It is designed for distribution in electrical installations and provides a rated current of 10 A at an ambient temperature of 25 °C. The operating voltage is 250 V DC, with a rated insulation voltage of 500 V DC. The switch complies with standards EN 60947-2 and IEC 60947-2 and is designed for usage category A, making it suitable for applications with low load fluctuation and normal operating conditions.
Applications
The protection switch is intended for use in industrial and technical installations, particularly in systems with direct current supply. It is suitable for distribution circuits where safe disconnection is required in case of overload or short circuit. The operating temperature ranges from -25 °C to 70 °C, enabling use in various environments. The maximum operating altitude is 2,000 m above sea level, and the devices are designed for pollution degree 3 and overvoltage category IV.
Functions and Equipment in Detail
The switch features thermal-magnetic tripping technology, which responds to overloads (thermal) and short circuits (magnetic). The C curve defines the tripping characteristic, causing the switch to trip within seconds at approximately 5 to 10 times the rated current. The contact position indicator shows the current position (ON/OFF), facilitating status monitoring. Control is via a toggle switch, and installation is tool-free onto a 35 mm symmetrical DIN rail. The connection terminals are available at the top and bottom, enabling connection to cables or pin-type busbars.
Technology Explained Simply
The breaking capacity of the switch varies depending on voltage: 20 kA Icu at 110 V DC, 10 kA Icu at 220 V DC, and 6 kA Icu at 250 V DC. The rated operational breaking capacity is 15 kA at 110 V DC, 7.5 kA at 220 V DC, and 4.5 kA at 250 V DC. The rated impulse withstand voltage is 6 kV, ensuring safety during transient voltage surges. The mechanical life is 20,000 cycles, and the electrical life is 3,000 cycles at a load switching time constant of 2 ms. The tightening torques for the circuit terminals are 2.5 Nm.
Compatibility and Accessories
The switch is compatible with various accessory modules that can be optionally mounted. These include current trip units (MX, MX+OF), undervoltage trip units (MN, MNS, MNX), auxiliary switches (OF), and remote signaling switches (SD). These modules extend functionality, for example, by enabling remote reading of the switch status or automatic disconnection in case of undervoltage. Installation is on the left side of the device, with modules being stackable.
Mounting and Installation
Mounting is fixed onto a 35 mm DIN rail using a clip fastening. Connection terminals are available at the top and bottom, allowing flexible integration into existing control panels. The devices are white and fit into the Acti9 series. The locking option allows locking in position O (off), which is useful for maintenance work.
Advantages in Operation
The switch offers a long service life and is designed for demanding industrial environments. The snap-action switching ensures wear-free switching of contacts. Local signaling (ON/OFF indicator) simplifies status monitoring. The locking option and compatibility with additional modules enhance safety and functionality. Compliance with standards EN 60947-2 and IEC 60947-2 ensures reliable and standard-compliant performance.
The devices are available in individual packaging (1 piece per pack), with packaging units BB1 (12 pieces) and S03 (144 pieces) intended for larger orders. The warranty is 18 months.