| Complementary |
| Range compatibility | Acti9 iDPN; Acti9 C120; Acti9 C40; Acti9 C60H-DC; Acti9 C60NA-DC; Acti9 C60PV-DC; Acti9 DPN Vigi; Acti9 DT40; Acti9 DT60; Acti9 ID C40; Acti9 IDc; Acti9 ITG40; Acti9 ID; Acti9 DPN |
| Local signalling | Action indicator |
| Mounting mode | Fixed |
| Mounting support | 35 mm symmetrical DIN rail |
| Comb busbar and distribution block compatibility | Top: YES |
| Height | 82.5 mm |
| Width | 18 mm |
| Depth | 73.5 mm |
| Net weight | 66 g |
| Colour | White |
| Connections - terminals | Screw clamp terminal (bottom) - 2 cable(s) 1.5 mm² - flexible; Screw clamp terminal (bottom) - 2 cable(s) 1.5 mm² - flexible with ferrule; Screw clamp terminal (bottom) - 1 cable(s) 0.5…2.5 mm² - rigid |
| Wire stripping length | 9 mm for bottom connection |
| Tightening torque | 1 N.m bottom |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-2 |
| Product certifications | ASEFA; ASTA; LCIE; KEMA |
| Tropicalisation | 2 conforming to EN/IEC 60947-2 |
| Relative humidity | 95 % at 55 °C |
| Ambient air temperature for operation | -25…50 °C |
| Ambient air temperature for storage | -40…85 °C |
| Main |
| range of product | Acti9 |
| Product or component type | Undervoltage release |
| Device short name | MN |
| [Uc] control circuit voltage | 48 V AC 50/60 Hz; 48 V DC |
| Control type | Standard |
| 9 mm pitches | 2 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 2.700 cm |
| Package 1 Width | 7.700 cm |
| Package 1 Length | 9.500 cm |
| Package 1 Weight | 74.000 g |
| Unit Type of Package 2 | BB1 |
| Number of Units in Package 2 | 8 |
| Package 2 Height | 8.500 cm |
| Package 2 Width | 10.000 cm |
| Package 2 Length | 26.500 cm |
| Package 2 Weight | 646.000 g |
| Unit Type of Package 3 | S03 |
| Number of Units in Package 3 | 72 |
| Package 3 Height | 30 cm |
| Package 3 Width | 30 cm |
| Package 3 Length | 40 cm |
| Package 3 Weight | 6.253 kg |
Undervoltage release Acti 9 MN. Operating voltage (Ue) 48V AC / 48V DC. Causes the device with which it is combined to trip when the input voltage drops. Prevents the device from closing until the input voltage is restored. Emergency stop by opening button. The undervoltage release MN complies with the following standards - IEC/EN 60947-1 and EN 60947-2.