| Complementary |
| Range compatibility | Acti9 iDPN; Acti9 C120; Acti9 C40; Acti9 C60H-DC; Acti9 C60NA-DC; Acti9 C60PV-DC; Acti9 DPN Vigi; Acti9 DT40; Acti9 DT60; Acti9 ID C40; Acti9 IDc; Acti9 ITG40; Acti9 ID; Acti9 DPN |
| Local signalling | Action indicator |
| Mounting mode | Fixed |
| Mounting support | 35 mm symmetrical DIN rail |
| Comb busbar and distribution block compatibility | Top: YES |
| Height | 82.5 mm |
| Width | 18 mm |
| Depth | 73.5 mm |
| Net weight | 65 g |
| Colour | White |
| Connections - terminals | Screw clamp terminal (bottom) - 2 cable(s) 1.5 mm² - flexible; Screw clamp terminal (bottom) - 2 cable(s) 1.5 mm² - flexible with ferrule; Screw clamp terminal (bottom) - 1 cable(s) 0.5…2.5 mm² - rigid |
| Wire stripping length | 9 mm for bottom connection |
| Tightening torque | 1 N.m bottom |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-2 |
| Product certifications | ASTA; ASEFA; LCIE; KEMA |
| Tropicalisation | 2 conforming to EN/IEC 60947-2 |
| Relative humidity | 95 % at 55 °C |
| Ambient air temperature for operation | -25…50 °C |
| Ambient air temperature for storage | -40…85 °C |
| Logistical informations |
| Country of origin | BE |
| Main |
| range of product | Acti9 |
| Product or component type | Shunt trip release with OC contact |
| Device short name | MX + OF |
| Signal contacts composition | 1 C/O |
| [In] rated current | 3 A at 415 V, AC; 6 A at |
| [Uc] control circuit voltage | 110...415 V AC 50/60 Hz; 110...130 V DC |
| 9 mm pitches | 2 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 8.000 cm |
| Package 1 Width | 2.800 cm |
| Package 1 Length | 9.400 cm |
| Package 1 Weight | 70.000 g |
| Unit Type of Package 2 | BB1 |
| Number of Units in Package 2 | 8 |
| Package 2 Height | 8.500 cm |
| Package 2 Width | 10.000 cm |
| Package 2 Length | 26.500 cm |
| Package 2 Weight | 620.000 g |
| Unit Type of Package 3 | S03 |
| Number of Units in Package 3 | 72 |
| Package 3 Height | 30 cm |
| Package 3 Width | 30 cm |
| Package 3 Length | 40 cm |
| Package 3 Weight | 6.012 kg |
The product A9N26946 from Schneider Electric is an operating current tripping unit with an integrated auxiliary switch OF, specifically designed for use in the Acti9 product range. It is used for remote control and signaling of power switches and disconnectors, triggering the associated device upon activation and simultaneously indicating the switching status via an auxiliary switch. The component is rated for operating voltages of 220 to 415 V AC and 110 to 130 V DC, enabling integration into various control and protection systems. The auxiliary switch OF is designed as a changeover contact, allowing it to function as either a make or break contact — particularly suitable for emergency stop functions using a make contact.
Applications
The operating current tripping unit MX+OF is used in industrial and commercial electrical installations where remote disconnection or visual indication of the switching status is required. It is especially suitable for applications in automation technology, machine control, distribution boards, or integration into safety and emergency stop circuits. Compatibility with various Acti9 product families such as C120, C40, DT40, DT60, ID C40, IDc, ITG40, DPN Vigi, and DPN significantly expands its range of applications.
Functions and Equipment in Detail
The device features local signaling in the form of an action indicator, visually displaying the operating status. The auxiliary switch OF is configured as 1 changeover contact, enabling flexible use in control and signaling circuits. The control circuit voltage is 110 to 415 V AC (50/60 Hz) and 110 to 130 V DC, allowing connection to various supply voltages. The rated current is 3 A at 415 V AC and 6 A at an unspecified voltage, defining its load capacity for control and signaling applications.
Technology Explained Simply
The operating current tripping unit is activated by an external control voltage, triggering the associated power switch device. This is necessary, for example, in emergency shutdowns or automated processes. The integrated auxiliary switch OF handles the signaling of the switching status — it closes when the tripping unit is actuated, which can be used for emergency stop functions. Connections are made via screw terminals on the underside, allowing flexible cables up to 1.5 mm² and rigid cables from 0.5 to 2.5 mm² to be connected. The wire stripping length is 9 mm, and the tightening torque for the terminals is specified as 1 Nm.
Compatibility and Accessories
The operating current tripping unit is designed for mounting on a 35 mm symmetrical DIN rail and is compatible with a wide range of Acti9 product families, including C120, C40, DT40, DT60, ID C40, IDc, ITG40, DPN Vigi, and DPN. Additionally, it is compatible with comb rails and distribution blocks on the top. As accessories, various LS switches from the C120N series are available, offered in different pole counts and rated currents (e.g., 80 A, 100 A) and suitable for combination with the MX+OF.
Mounting and Installation
Mounting is done directly onto a 35 mm DIN rail. Dimensions are 82.5 mm height, 18 mm width, and 73.5 mm depth. The device is white and conforms to the 9 mm grid with 2 grid positions. Mounting requires no additional tools, as the screw terminals are directly accessible on the underside. The drip-proof rating corresponds to Class 2 according to EN/IEC 60947-2, enabling use in humid environments.
Advantages in Operation
The operating current tripping unit MX+OF provides reliable remote disconnection and signaling in industrial installations. The integrated action indicator allows for quick status checks, while the auxiliary switch OF can be used for additional control and safety functions. High compatibility with various Acti9 products and a robust design for operating temperatures from -25 to 50 °C and storage temperatures from -40 to 85 °C make the device suitable for diverse operating conditions. The relative humidity of up to 95 % at 55 °C demonstrates suitability for humid environments. Certifications from ASTA, ASEFA, LCIE, and KEMA confirm compliance with international safety and quality standards.
Standards and Certifications
The device complies with standards EN/IEC 60947-2 and is certified by ASTA, ASEFA, LCIE, and KEMA. The drip-proof rating Class 2 according to EN/IEC 60947-2 ensures suitability for use in humid and tropical environments. Operating temperature range of -25 to 50 °C and storage temperature range of -40 to 85 °C guarantee broad applicability under various climatic conditions. The warranty period is 18 months.