| Additional features |
| Device position in system | Outlet; group input |
| Network frequency | 50 Hz |
| [Ue] Operational rated voltage | 230 - 415 V AC 50 Hz |
| Earth fault trip technology | Voltage-independent |
| [Ui] Rated insulation voltage | 500 V AC 50/60 Hz conforms to IEC 60947-1 |
| [Uimp] Rated impulse voltage withstand | 6 kV corresponds to IEC 60947-2 |
| Mounting mode | Plug-in |
| Mounting bracket | 35 mm symmetrical DIN rail |
| Electrical connection for LS switch | With screws |
| 9-mm pitch | 7 |
| Height | 95 mm |
| Width | 117 mm |
| Depth | 73 mm |
| Product weight | 0,325 kg |
| Colour | White |
| Mechanical life | 20000 cycles |
| Connections - terminals | Tunnel terminals 1…35 mm² flexible; tunnel terminals 1…50 mm² solid |
| Wire stripping length | 15 mm |
| [M] tightening torque | 3,5 Nm |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | Acti9 |
| Product name | Acti9 Vigi C120 |
| Product or component type | Additional residual current protective devices |
| Device short name | Vigi C120 |
| Pole description | 2P |
| [In] Rated current | 125 A |
| Type of network | AC |
| Earth fault sensitivity | 300 mA |
| Earth fault protection time delay | Instantaneous |
| Earth fault protection class | Type A-SI (Superimmunized) |
| Standards | EN 61009; IEC/EN 61009-2-1 |
| Mounting |
| Degree of protection (IP) | IP20 |
| Pollution degree | 3 corresponds to IEC 60947-2 |
| Operating ambient temperature | -25…60 °C |
| Ambient temperature during storage | -40…60 °C |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 9,500 cm |
| VPE 1 width | 13,500 cm |
| VPE 1 length | 13,500 cm |
| Packaging weight (Lbs) | 389,000 g |
| VPE 2 type | S03 |
| VPE 2 quantity | 8 |
| VPE 2 height | 30,000 cm |
| VPE 2 width | 30,000 cm |
| VPE 2 length | 40,000 cm |
| VPE 2 weight | 3,599 kg |
Acti 9 Vigi C120 residual current block. 2-pole, nominal residual current 300mA, type A, SI, operating voltage (Ue) 230-415V AC, insulation voltage (Ui) 500V AC. Can be mounted on the right-hand side of the C120 series circuit breaker. Tripping due to residual current is indicated by a red, mechanical indicator on the knob. Terminals IP 20. Test button for regular function testing. Technology of the trip unit - thermomagnetic. Additional auxiliary modules that can be added in series (optional) - fault signaling switch, auxiliary switch, undervoltage release, overvoltage release, shunt release. The Vigi C120 residual current block complies with the following standards - IEC/EN 61009-1.