| Complementary |
| Device location in system | Outgoer; Group incomer |
| Network frequency | 50/60 Hz |
| [Ue] rated operational voltage | 400...415 V AC 50/60 Hz |
| Residual current tripping technology | Voltage independent |
| [Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to IEC 60947-1 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| Mounting mode | Clip-on |
| Mounting support | 35 mm symmetrical DIN rail |
| Electrical connection to mcb | By screws |
| 9 mm pitches | 10 |
| Height | 95 mm |
| Width | 198 mm |
| Depth | 73 mm |
| Net weight | 0.58 kg |
| Colour | White |
| Mechanical durability | 20000 cycles |
| Connections - terminals | Tunnel type terminals 1…35 mm² flexible; Tunnel type terminals 1…50 mm² rigid |
| Wire stripping length | 15 mm |
| Tightening torque | 3.5 N.m |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP20 |
| Pollution degree | 3 conforming to IEC 60947-2 |
| Ambient air temperature for operation | -25…60 °C |
| Ambient air temperature for storage | -40…60 °C |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | Acti9 |
| Product name | Acti9 Vigi C120 |
| Product or component type | Add-on residual current device |
| Device short name | Vigi C120 |
| Poles description | 4P |
| [In] rated current | 125 A |
| Network type | AC |
| Earth-leakage sensitivity | 30 mA |
| Earth-leakage protection time delay | Instantaneous |
| Earth-leakage protection class | Type A |
| Standards | EN 61009; IEC/EN 61009-2-1 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 9.100 cm |
| Package 1 Width | 13.300 cm |
| Package 1 Length | 25.000 cm |
| Package 1 Weight | 800.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 8 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 6.893 kg |
Acti 9 Vigi C120 residual current block. 4-pole, nominal residual current 30mA, type A, operating voltage (Ue) 230-415V AC, insulation voltage (Ui) 500V AC. Can be mounted on the right-hand side of the C120 series circuit breaker. Tripping due to residual current is indicated by a red, mechanical indicator on the knob. Terminals IP 20. Test button for regular function testing. Technology of the trip unit - thermomagnetic. Additional auxiliary modules that can be added in series (optional) - fault signaling switch, auxiliary switch, undervoltage release, overvoltage release, shunt release. The Vigi C120 residual current block complies with the following standards - IEC/EN 61009-1.