Further information for Schneider Electric A9N18470 circuit breaker 3-pole C125A
Complementary
Network frequency
50/60 Hz
Magnetic tripping limit
5...10 x In
[Ics] rated service breaking capacity
7500 A 50 % conforming to EN/IEC 60898-1 - 400 V AC 50/60 Hz; 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz; 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz; 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz; 15 kA 100 % conforming to EN/IEC 60947-2 -
Limitation class
3 conforming to EN/IEC 60947-2
[Ui] rated insulation voltage
500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-2
Control type
Toggle
Local signalling
ON/OFF indication
Mounting mode
Clip-on
Mounting support
35 mm symmetrical DIN rail
9 mm pitches
9
Height
81 mm
Depth
73 mm
Width
81 mm
Net weight
0.615 kg
Colour
White
Mechanical durability
20000 cycles
Electrical durability
5000 cycles conforming to IEC 60947-2
Locking options description
Handle sealable with cable diameter 0.7mm in OFF or ON position
Connections - terminals
Tunnel type terminals1…50 mm² rigid; Tunnel type terminals1.5…35 mm² flexible
Wire stripping length
15 mm
Tightening torque
3.5 N.m
Earth-leakage protection
Separate block
Contact position indicator
Comb busbar and distribution block compatibility
Contractual warranty
Warranty (in months)
18
Environment
IP degree of protection
IP20 conforming to IEC 60529
Pollution degree
3 conforming to IEC 60947-2
Overvoltage category
IV
Tropicalisation
2 conforming to IEC 60068-1
Relative humidity
95 % at 55 °C
Operating altitude
2000 m
Ambient air temperature for operation
-30…60 °C
Ambient air temperature for storage
-40…70 °C
Logistical informations
Country of origin
FR
Main
Range
Acti9
Product name
Acti9 C120
Product or component type
Miniature circuit-breaker
Device short name
C120H
Device application
Distribution
Poles description
3P
Number of protected poles
3
[In] rated current
125 A at 30 °C
Network type
AC; DC
Trip unit technology
Thermal-magnetic
Curve code
C
Breaking capacity
15000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1; 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2; 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA Icu at
Suitability for isolation
Yes conforming to IEC 60947-2
Standards
EN/IEC 60898-1; EN/IEC 60947-2
Product certifications
EAC
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
7.500 cm
Package 1 Width
8.000 cm
Package 1 Length
8.200 cm
Package 1 Weight
582.000 g
Unit Type of Package 2
BB1
Number of Units in Package 2
4
Package 2 Height
8.500 cm
Package 2 Width
9.500 cm
Package 2 Length
33.000 cm
Package 2 Weight
2.392 kg
Unit Type of Package 3
S03
Number of Units in Package 3
24
Package 3 Height
30.000 cm
Package 3 Width
30.000 cm
Package 3 Length
40.000 cm
Package 3 Weight
14.839 kg
The circuit breaker Acti9 C120 from Schneider Electric is a 3-pole switch from the Acti9 series, designed for distribution in electrical installations. It provides protection against overload and short circuit and is rated for a nominal current of 125 A at an ambient temperature of 30 °C. The tripping technology is based on a thermal-magnetic principle, where the thermal component responds to sustained overload and the magnetic component reacts to sudden short circuits. The C-characteristic of the tripping curve ensures selective disconnection during transient load peaks, thereby enhancing the reliability of power supply.
Applications include installation in enclosures and distribution systems, particularly in installations where the neutral conductor is switched. The compact design with height, width, and depth of 81 mm, 81 mm, and 73 mm respectively allows for high packing density, minimizing space requirements in enclosures. Mounting is done on a 35 mm symmetrical DIN rail, ensuring standardized and quick installation. The protection rating IP20 according to IEC 60529 makes the switch suitable for indoor use where no direct mechanical impacts or moisture occur.
Functions and equipment in detail include an ON/OFF indicator for visual control of the switching position and a contact position indicator. The mechanical life is 20,000 cycles, and the electrical life is 5,000 cycles according to IEC 60947-2. The terminals are designed as tunnel terminals and allow connection of solid conductors with a cross-section of 1 to 50 mm² and flexible conductors from 1.5 to 35 mm². The required wire stripping length is 15 mm, and the tightening torque for the terminals is 3.5 Nm. The rated insulation voltage is 500 V AC, and the rated impulse withstand voltage is 6 kV, ensuring suitability for installations with higher voltage stresses.
Technology explained simply shows that the switch is designed for networks with a frequency of 50/60 Hz and is suitable for both AC and DC applications. The breaking capacity is 15,000 A Icn at 400 V AC, indicating the ability to safely interrupt high short-circuit currents. The limiting class 3 according to EN/IEC 60947-2 ensures efficient energy limitation during tripping events. The magnetic tripping threshold is between 5 and 10 times the nominal current, enabling rapid response to sudden current surges. The rated operational breaking capacity varies depending on the voltage level, for example, reaching 15 kA (100 %) at 220–240 V AC.
Compatibility and accessories allow combination with various modules. Compatible accessories include RCD modules such as the Vigi C120 3p 30 mA Type A, providing additional earth fault protection. Other modules include under-voltage release units (e.g. MN 220–240 VAC), over-voltage release units (e.g. MSU 230 V AC), remote signaling switches (e.g. Acti9 SD 100 mA–6 A AC/DC), and auxiliary switches (e.g. Acti9 OF 1OC). These modules can be mounted in series on the switch to adapt functionality to specific requirements.
Mounting and installation is done on a 35 mm DIN rail, where the switch is plug-in type. Mounting is tool-free, as the DIN rail is standardized. The operating temperature range is from -30 °C to 60 °C, and the storage temperature range is from -40 °C to 70 °C. The maximum operating altitude is 2,000 m above sea level. The pollution degree class 3 according to IEC 60947-2 makes the switch suitable for environments with increased pollution risk. The overvoltage category IV indicates suitability for end devices in electrical distribution.
Operational advantages include high reliability, long service life, and modular expandability. The combinability with various add-on modules enables customized solutions for different applications. Clear indication of switching position and robust construction ensure safe and maintenance-friendly use. Compliance with standards EN/IEC 60898-1 and EN/IEC 60947-2 as well as certification according to EAC confirms conformity with international standards. The device color is white, corresponding to RAL 9003.
The switch is designed for use in electrical distribution systems where high safety, reliability, and flexibility are required. Technical specifications and modularity make it a suitable solution for industrial and commercial applications.