Further information for Schneider Electric A9N18393 circuit breaker 4-pole 125A
Additional features
Network frequency
50/60 Hz
[Ue] Operational rated voltage
380 - 415 V AC 50/60 Hz;
Magnetic trip threshold
10 - 14 x In
[Ics] Rated operational breaking capacity
7500 A 75 % corresponds to EN/IEC 60898-1 - 400 V AC 50/60 Hz; 4.5 kA 75 % corresponds to EN/IEC 60947-2 - 440 V AC 50/60 Hz; 7.5 kA 75 % corresponds to EN/IEC 60947-2 - 380 - 415 V AC 50/60 Hz; 15 kA 75 % corresponds to EN/IEC 60947-2 - 220 - 240 V AC 50/60 Hz; 10 kA 100 % corresponds to EN/IEC 60947-2 -
Limiting class
3 corresponds to EN/IEC 60947-2
[Ui] Rated insulation voltage
500 V AC 50/60 Hz corresponds to EN/IEC 60947-2
[Uimp] Rated impulse voltage withstand
6 kV corresponds to EN/IEC 60947-2
Control type
Toggle switch
Local signalling
ON/OFF indicator
Mounting mode
Plug-in
Mounting bracket
35 mm symmetrical DIN rail
9-mm pitch
12
Height
81 mm
Depth
73 mm
Width
108 mm
Product weight
0,82 kg
Colour
White
Mechanical life
20000 cycles
Electrical lifetime
5000 cycles corresponds to IEC 60947-2
Description of locking options
Handle sealable with cable diameter 0.7mm in OFF or ON position
Compatibility of comb rails and distribution blocks
Contractual warranty
Warranty (in months)
18
Main features
Product series
Acti9
Product name
Acti9 C120
Product or component type
Miniature circuit breaker (MCB)
Device short name
C120N
Device application
Distribution
Pole description
4P
Number of protected poles
4
[In] Rated current
125 A at 30 °C
Type of network
AC; DC
Trigger technology
Thermal-magnetic
Cam disc
D
Breaking capacity
10000 A Icn at 400 V AC 50/60 Hz in accordance with EN/IEC 60898-1; 6 kA Icu at 440 V AC 50/60 Hz in accordance with EN/IEC 60947-2; 20 kA Icu at 220 - 240 V AC 50/60 Hz in accordance with EN/IEC 60947-2; 10 kA Icu at 380 - 415 V AC 50/60 Hz in accordance with EN/IEC 60947-2; 10 kA Icu at
Suitability for insulation
Yes, complies with IEC 60947-2
Standards
EN/IEC 60898-1; EN/IEC 60947-2
Product certifications
EAC
Mounting
Degree of protection (IP)
IP20 complies with IEC 60529
Pollution degree
3 corresponds to IEC 60947-2
Over voltage category
IV
Drip-proof
2 corresponds to IEC 60068-1
Relative humidity
95 % at 55 °C
Operating altitude
2.000 m
Operating ambient temperature
-25…70 °C
Ambient temperature during storage
-40…85 °C
Packaging units
VPE 1 type
PCE
Number of devices per package
1
VPE 1 height
7,300 cm
VPE 1 width
10,300 cm
VPE 1 length
8,100 cm
Packaging weight (Lbs)
776,000 g
VPE 2 type
BB1
VPE 2 quantity
3
VPE 2 height
8,500 cm
VPE 2 width
9,500 cm
VPE 2 length
33,100 cm
VPE 2 weight
2,400 kg
VPE 3 type
S03
VPE 3 quantity
18
VPE 3 height
30,000 cm
VPE 3 width
30,000 cm
VPE 3 length
40,000 cm
VPE 3 weight
14,888 kg
Circuit breaker Acti 9 iC60H, 10kA (IEC/EN 60898-1), 15kA (IEC/EN 60947-2). 2-pole, nominal current 6A, C characteristic, operating voltage (Ue) 380-415V AC, insulation voltage (Ui) 500V AC. Double connection terminal for cable and pin comb bar on the top and bottom of the device. Snap action for low-wear switching of the contacts. Insulation cover that moves with the device. Operation of the top hat rail fastening element on the front of the device for tool-free installation and easy access for the user. With mechanical front-side fault indication display (VisiTrip) to indicate tripping due to overload or short circuit. Safe contact display (VisiSafe) of the circuit breaker, with a green display to ensure that there is no voltage on the output side. Technology of the trip unit - thermomagnetic. Can be combined with the residual current circuit breakers of the Acti 9 iID series, as well as the Vigi iC60 residual current block. Additional auxiliary modules (optional) can be added - display of switch position, fault tripping, shunt release, undervoltage release, overvoltage release. Color RAL 9003. The iC60H circuit breaker meets the following standards - IEC/EN 60898-1 and IEC/EN 60947-2. This series is also VDE certified.