Further information for Schneider Electric A9N18358 circuit breaker 1p C120N 100A
Complementary
Network frequency
50/60 Hz
[Ue] rated operational voltage
380...415 V AC 50/60 Hz; 125 V DC;
Magnetic tripping limit
5...10 x In
[Ics] rated service breaking capacity
15 kA 75 % conforming to EN/IEC 60947-2 - 130 V AC 50/60 Hz; 15 kA 100 % conforming to EN/IEC 60947-2 - 125 V DC; 2.25 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz; 15 kA 100 % conforming to EN/IEC 60947-2 - 12 V DC; 10 kA 100 % conforming to EN/IEC 60947-2 -
Limitation class
3 conforming to EN/IEC 60947-2
[Ui] rated insulation voltage
500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-2
Control type
Toggle
Local signalling
ON/OFF indication
Mounting mode
Clip-on
Mounting support
35 mm symmetrical DIN rail
9 mm pitches
3
Height
81 mm
Depth
73 mm
Width
27 mm
Net weight
0.205 kg
Colour
White
Mechanical durability
20000 cycles
Electrical durability
5000 cycles conforming to IEC 60947-2
Locking options description
Handle sealable with cable diameter 0.7mm in OFF or ON position
Connections - terminals
Tunnel type terminals1…50 mm² rigid; Tunnel type terminals1.5…35 mm² flexible
Wire stripping length
15 mm
Tightening torque
3.5 N.m
Earth-leakage protection
Without
Contact position indicator
Comb busbar and distribution block compatibility
Contractual warranty
Warranty (in months)
18
Environment
IP degree of protection
IP20 conforming to IEC 60529
Pollution degree
3 conforming to IEC 60947-2
Overvoltage category
IV
Tropicalisation
2 conforming to IEC 60068-1
Relative humidity
95 % at 55 °C
Operating altitude
2000 m
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-40…85 °C
Logistical informations
Country of origin
FR
Main
Range
Acti9
Product name
Acti9 C120
Product or component type
Miniature circuit-breaker
Device short name
C120N
Device application
Distribution
Poles description
1P
Number of protected poles
1
[In] rated current
100 A at 30 °C
Network type
AC; DC
Trip unit technology
Thermal-magnetic
Curve code
C
Breaking capacity
3 kA Icu at 380...415 V AC 50/60 Hz IT conforming to EN/IEC 60947-2; 20 kA Icu at 130 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA Icu at 12 V DC conforming to EN/IEC 60947-2; 15 kA Icu at 125 V DC conforming to EN/IEC 60947-2; 10 kA Icu at
Suitability for isolation
Yes conforming to IEC 60947-2
Standards
EN/IEC 60898-1; EN/IEC 60947-2
Product certifications
EAC
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
7.400 cm
Package 1 Width
2.700 cm
Package 1 Length
8.500 cm
Package 1 Weight
192.000 g
Unit Type of Package 2
BB1
Number of Units in Package 2
12
Package 2 Height
8.600 cm
Package 2 Width
9.300 cm
Package 2 Length
33.300 cm
Package 2 Weight
2.380 kg
Unit Type of Package 3
S03
Number of Units in Package 3
72
Package 3 Height
30.000 cm
Package 3 Width
30.000 cm
Package 3 Length
40.000 cm
Package 3 Weight
14.767 kg
Leitungsschutzschalter Acti 9 K60N, 6kA (IEC/EN 60898-1). 3-polig, Nennstrom 20A, B-Charakteristik, Betriebsspannung (Ue) 400V AC, Isolationsspannung (Ui) 500V AC. Doppelfunktionsklemme an der Geräteunterseite für getrennten Anschluss von Gabel-Phasenschiene und Leiter. Käfigklemme an der Geräteoberseite. Sprungschaltung für verschleißarmes Schalten der Kontakte. Farbton RAL 9003. Der K60N Leitungsschutzschalter erfüllt folgende Normen- IEC/EN 60898-1. Des Weiteren ist diese Baureihe VDE zertifiziert.