Further information for Schneider Electric A9N18355 circuit breaker 4-pole 125A
Complementary
Network frequency
50/60 Hz
[Ue] rated operational voltage
380...415 V AC 50/60 Hz;
Magnetic tripping limit
3...5 x In
[Ics] rated service breaking capacity
7500 A 75 % conforming to EN/IEC 60898-1 - 400 V AC 50/60 Hz; 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz; 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz; 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz; 10 kA 100 % conforming to EN/IEC 60947-2 -
Limitation class
3 conforming to EN/IEC 60947-2
[Ui] rated insulation voltage
500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-2
Control type
Toggle
Local signalling
ON/OFF indication
Mounting mode
Clip-on
Mounting support
35 mm symmetrical DIN rail
9 mm pitches
12
Height
81 mm
Depth
73 mm
Width
108 mm
Net weight
0.82 kg
Colour
White
Mechanical durability
20000 cycles
Electrical durability
5000 cycles conforming to IEC 60947-2
Locking options description
Handle sealable with cable diameter 0.7mm in OFF or ON position
Connections - terminals
Tunnel type terminals1…50 mm² rigid; Tunnel type terminals1.5…35 mm² flexible
Wire stripping length
15 mm
Tightening torque
3.5 N.m
Earth-leakage protection
Separate block
Contact position indicator
Comb busbar and distribution block compatibility
Contractual warranty
Warranty (in months)
18
Environment
IP degree of protection
IP20 conforming to IEC 60529
Pollution degree
3 conforming to IEC 60947-2
Overvoltage category
IV
Tropicalisation
2 conforming to IEC 60068-1
Relative humidity
95 % at 55 °C
Operating altitude
2000 m
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-40…85 °C
Logistical informations
Country of origin
FR
Main
Range
Acti9
Product name
Acti9 C120
Product or component type
Miniature circuit-breaker
Device short name
C120N
Device application
Distribution
Poles description
4P
Number of protected poles
4
[In] rated current
125 A at 30 °C
Network type
AC; DC
Trip unit technology
Thermal-magnetic
Curve code
B
Breaking capacity
10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1; 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2; 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2; 10 kA Icu at
Suitability for isolation
Yes conforming to IEC 60947-2
Standards
EN/IEC 60947-2; EN/IEC 60898-1
Product certifications
EAC
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
7.500 cm
Package 1 Width
8.800 cm
Package 1 Length
10.800 cm
Package 1 Weight
777.000 g
Unit Type of Package 2
BB1
Number of Units in Package 2
3
Package 2 Height
8.500 cm
Package 2 Width
9.500 cm
Package 2 Length
33.100 cm
Package 2 Weight
2.391 kg
Unit Type of Package 3
S03
Number of Units in Package 3
18
Package 3 Height
30.000 cm
Package 3 Width
30.000 cm
Package 3 Length
40.000 cm
Package 3 Weight
14.928 kg
Circuit breaker Acti 9 K60N, 6kA (IEC/EN 60898-1). 3-pole, nominal current 10A, B characteristic, operating voltage (Ue) 400V AC, insulation voltage (Ui) 500V AC. Dual function terminal on the bottom of the device for separate connection of fork phase busbar and conductor. Cage terminal on the top of the device. Snap action for low-wear switching of the contacts. Color RAL 9003. The K60N circuit breaker meets the following standards - IEC/EN 60898-1. This series is also VDE certified.