| Complementary |
| Poles description | 3P + N; 1P + N; 3P |
| Type of measurement | Active and reactive energy; Active and reactive power; Current; Voltage |
| Metering type | Active, reactive, apparent energy (signed, four quadrant) |
| Device application | Multi-tariff; Partial meter; Sub billing |
| Accuracy class | Class 0.5S active energy conforming to IEC 62053-22; Class 0.5S active energy conforming to IEC 61557-12; Class C active energy conforming to EN 50470-3 |
| input type | Current transformer 1 A or 5 A |
| [In] rated current | 5 A; 1 A |
| Rated voltage | 100…277 V; 173…480 V |
| Network frequency | 60 Hz; 50 Hz |
| Technology type | Electronic |
| Display type | LCD display |
| Sampling rate | 32 samples/cycle |
| Measurement current | 1…32767000 mA |
| Maximum value measured | 99999999 MWh |
| tariff input | Tariff (4) |
| Communication port protocol | Modbus RTU at 9.6, 19.2 and 38.4 kbauds even/odd or none, insulation 4000 V |
| Communication port support | Screw terminal block: RS485 |
| Local signalling | Green indicator light: power ON; Yellow flashing LED: accuracy checking; alarm: overload; Yellow indicator light: communications are active on the Modbus port (Modbus) |
| Number of inputs | 1 digital 0...5 V/11...40 V 24 V DC |
| Number of outputs | 1 digital (static) |
| Output voltage | 5...40 V DC@50 mA |
| Mounting mode | Clip-on |
| Mounting support | DIN rail |
| Connections - terminals | Current circuit: screw terminals 6 mm² cable(s) ; Voltage circuit: screw terminals 2.5 mm² cable(s) |
| Overvoltage category | III |
| Market segment | Small commercial; Residential |
| Compatibility code | IEM3255 |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP40 front panel: conforming to IEC 60529; IP20 body: conforming to IEC 60529 |
| Pollution degree | 2 |
| Relative humidity | 5…95 % at 50 °C |
| Ambient air temperature for operation | -25…70 °C - IEC |
| Ambient air temperature for storage | -40…85 °C |
| Operating altitude | < 3000 m |
| Colour | White |
| 9 mm pitches | 10 |
| Width | 90 mm |
| Height | 95 mm |
| Depth | 69 mm |
| Logistical informations |
| Country of origin | CN |
| Main |
| Range | Acti9 |
| range of product | Acti9 iEM3000 |
| Product or component type | Energy meter |
| Device short name | iEM3255 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 8.800 cm |
| Package 1 Width | 9.600 cm |
| Package 1 Length | 10.600 cm |
| Package 1 Weight | 365.400 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 30 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 11.392 kg |
The iEM3255 energy meter from the Acti9 series by Schneider Electric is an electronic meter designed for DIN rail mounting, intended for measuring active and reactive energy, active and reactive power, current, and voltage in electrical networks. The device is designed for applications in small businesses and buildings and supports measurement in various configurations, including 3P + N, 1P + N, and 3P. Measurement is performed via current transformers with rated currents of 1 A or 5 A, and the meter supports a nominal voltage of 100 to 277 V or 173 to 480 V at network frequencies of 50 Hz or 60 Hz. The accuracy class for active energy corresponds to Class 0.5S according to IEC 62053-22 and IEC 61557-12, as well as Class C according to EN 50470-3, ensuring high measurement accuracy for commercial and industrial applications. Measurement is carried out in four quadrants, enabling detection of the direction of energy flow.
Applications
The meter is suitable for multi-tariff applications, sub-metering functions, and partial billing. It supports up to four tariffs, making it particularly suitable for installations with different tariff structures, such as buildings with day and night electricity tariffs. Its use in re-billing systems enables detailed billing of energy consumption to individual consumers or departments.
Functions and Equipment in Detail
The device features an LCD display for showing measured values. Local signaling includes a green LED indicating operation, a yellow flashing LED for accuracy verification, an overload alarm, and a yellow LED indicating Modbus communication activity. These visual indicators facilitate monitoring and maintenance of the device during operation.
Technology Explained Simply
The meter operates with a sampling rate of 32 samples per cycle, enabling precise capture of electrical parameters. The measurement ranges extend from 1 mA to 32767000 mA, with a maximum measured value of up to 99,999,999 MWh. Communication is via Modbus RTU over an RS485 screw terminal strip with 4000 V insulation. Baud rates include 9.6, 19.2, and 38.4 kBaud, with configurable parity checking (even/odd or none). This allows flexible integration into existing building automation or energy management systems.
Compatibility and Accessories
The meter is compatible with various current transformers listed in the accessories section, including types such as TI 250/5, TI 60/5, TI 300/5, TI 1250/5, TI 2000/5, as well as retrofit current transformers of types GJ, HJ, HM, HP, HG, GG. These transformers allow adaptation to different current levels and installation conditions. Compatibility with energy management software supports use in the context of the Internet of Things (IoT) for digital energy supply.
t
Mounting and Installation
The meter is designed for mounting on a DIN rail and has a mounting width of 10 modules (90 mm). Dimensions are 95 mm height, 90 mm width, and 69 mm depth. Connections are made via screw terminals: cables up to 6 mm² are permitted for the current circuit and up to 2.5 mm² for the voltage circuit. The protection rating is IP40 on the front panel and IP20 on the housing, providing protection against contact and dust, but not against water. The operating environment must have a relative humidity of 5 to 95 % at 50 °C and an ambient temperature of -25 to 70 °C. The operating altitude is limited to below 3000 m.
Operational Advantages
With support for Modbus RTU and integrated signaling, the meter offers high transparency and remote monitoring capability. The programmable digital inputs (0–5 V / 11–40 V, 24 V DC) and outputs (static, 5–40 V DC, 50 mA) enable integration into control and regulation systems. Certifications EAC, CE, UL, and MID ensure compliance with European and international standards, enabling use in various markets. Operational safety is supported by overvoltage category III and pollution degree 2.