| Complementary |
| Poles description | 3P + N; 1P + N; 3P |
| Type of measurement | Active energy |
| Device application | Multi-tariff; Sub billing |
| Accuracy class | Class 0.5S active energy conforming to IEC 62053-22; Class 0.5S active energy conforming to IEC 61557-12; Class C active energy conforming to EN 50470-3 |
| input type | Current transformer 1 A or 5 A |
| [In] rated current | 1 A; 5 A |
| Rated voltage | 100…277 V; 173…480 V |
| Network frequency | 50 Hz; 60 Hz |
| Technology type | Electronic |
| Display type | LCD display |
| Sampling rate | 32 samples/cycle |
| Measurement current | 1…32767000 mA |
| Maximum value measured | 99999999 MWh |
| tariff input | Tariff (4) |
| Communication port protocol | - |
| Communication port support | - |
| Local signalling | Green indicator light: power ON; Yellow flashing LED: accuracy checking |
| Number of inputs | 2 digital 0...5 V/11...40 V 24 V DC |
| Number of outputs | 0 |
| Mounting mode | Clip-on |
| Mounting support | DIN rail |
| Connections - terminals | Current circuit: screw terminals 6 mm² cable(s) ; Voltage circuit: screw terminals 2.5 mm² cable(s) |
| Overvoltage category | III |
| Market segment | Small commercial; Residential |
| Compatibility code | IEM3215 |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP40 front panel: conforming to IEC 60529; IP20 body: conforming to IEC 60529 |
| Pollution degree | 2 |
| Relative humidity | 5…95 % at 50 °C |
| Ambient air temperature for operation | -25…70 °C - IEC |
| Ambient air temperature for storage | -40…85 °C |
| Operating altitude | < 3000 m |
| Colour | White |
| 9 mm pitches | 10 |
| Width | 90 mm |
| Height | 95 mm |
| Depth | 69 mm |
| Logistical informations |
| Country of origin | CN |
| Main |
| Range | Acti9 |
| range of product | Acti9 iEM3000 |
| Product or component type | Energy meter |
| Device short name | iEM3215 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 8.500 cm |
| Package 1 Width | 9.500 cm |
| Package 1 Length | 10.500 cm |
| Package 1 Weight | 342.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 30 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 10.747 kg |
The iEM3215 energy meter from the Acti9 series by Schneider Electric is an electronic meter designed for DIN rail mounting, intended for measuring active energy in low- and medium-voltage installations. It is particularly suitable for applications in small businesses and buildings where precise sub-metering and multi-tariff measurement are required. The device features an LCD display and is designed for mounting on a 9 mm pitch DIN rail, with dimensions of 90 mm (width), 95 mm (height), and 69 mm (depth). The front plate has a protection rating of IP40, and the housing is rated IP20 according to IEC 60529, providing protection against contact, dust, and solid foreign objects.
Applications
The meter is designed for use in networks with a frequency of 50 Hz or 60 Hz and can operate at voltages between 100 and 277 V as well as between 173 and 480 V. It is suitable for measuring active and reactive power, as well as active and reactive energy, and supports various configurations: 3P + N, 1P + N, and 3P. Measurement is performed via current transformers with a rated current of 1 A or 5 A, with a measurement current range from 1 mA to 32767000 mA. The maximum measured energy amount is 99,999,999 MWh. The MID (Measuring Instruments Directive) approval enables use in sub-metering systems, particularly for billing energy consumption to individual consumers or departments.
Functions and Equipment in Detail
The meter features local signaling with a green LED indicating operation and a yellow LED flashing during accuracy tests. Two digital inputs (0–5 V / 11–40 V, 24 V DC) allow tariff control, with up to four tariffs configurable. The accuracy class for active energy is Class 0.5S according to IEC 62053-22 and IEC 61557-12, as well as Class C according to EN 50470-3. The sampling rate is 32 samples per cycle, enabling precise measurement even under fluctuating loads. Overvoltage category III ensures safe operation in industrial and commercial environments.
Technology Explained Simply
Measurement is performed electronically via current and voltage circuits, where current transformers step down the primary current to 1 A or 5 A. Voltage circuits are designed for cable cross-sections up to 2.5 mm², and current circuits up to 6 mm². The operating temperature range is -25 °C to +70 °C, with storage temperature from -40 °C to +85 °C. Relative humidity is 5 to 95 % at 50 °C. The operating altitude is limited to below 3,000 m. The device color is white.
Compatibility and Accessories
The meter is compatible with various current transformers suitable for different applications. Compatible accessories include current transformers of types TI 800/5, TI 400/5, TI 2500/5, TI 1250/5, TI 1000/5, TI 5000/5, as well as retrofit current transformers of types HA, GG, GD, HP, HG, HJ. These transformer types are designed for various installation scenarios such as cables, busbars, or Linergy systems. Combining the meter with these transformers allows flexible integration into existing electrical installations.
Mounting and Installation
Mounting is done on a DIN rail with 9 mm pitch. The screw terminals for current and voltage circuits are rated for cable cross-sections up to 6 mm² and 2.5 mm² respectively. Installation requires no special tools or additional components, as the device is simply clipped onto the rail. Pollution degree class 2 is intended for environments with low pollution, typical for indoor spaces in buildings or commercial facilities.
Operational Advantages
The meter offers high measurement accuracy and is suitable for multi-tariff systems, enabling detailed energy consumption billing. Local signaling supports maintenance and monitoring, as status and fault conditions are visually identifiable. MID approval and compliance with standards IEC 62053-22, IEC 61557-12, and EN 50470-3 ensure reliability and legal recognition of measurement values. The operating temperature range and overvoltage category III make the device suitable for industrial and commercial applications. DIN rail mounting allows quick and flexible installation in enclosures.
Certifications
The device complies with certifications EAC, CE, UL, and MID, confirming adherence to European and international safety and measurement standards. The warranty period is 18 months.