| Complementary |
| Form factor | Flex |
| Mounting mode | Free mounting |
| Electrical connection (voltage sensing & power supply) | Removable spring terminal block |
| Cable cross section | 1 rigid cable 0.2…1.5 mm² without cable end; 1 stranded cable 0.2…2.5 mm² without cable end; 1 stranded cable 0.25…1.5 mm² with cable end |
| Wire stripping length | 11 mm |
| max power cable diameter | 17 mm |
| supply voltage | 100...277 V AC, +/- 20 %, phase to neutral; 173...480 V AC, +/- 20 %, phase to phase |
| Network frequency | 50 Hz; 60 Hz |
| Maximum power consumption | 3 VA |
| Standards | IEC 61557-12; IEC 61010-1; ETSI EN 301 489-1; IEC 61010-2-030; IEC 61326-1; ETSI EN 300 328 |
| Product certifications | UL listed; IEC; DNV Marine |
| Height | 39 mm |
| Width | 91 mm |
| Depth | 62 mm |
| Net weight | 80 g |
| Colour | White (RAL 9003) |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Quality labels | CE |
| Directives | 2014/53/EU - radio equipment directive |
| Operating altitude | 0...2000 m |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -50…85 °C |
| Overvoltage category | IV conforming to IEC 61010-1 |
| Measurement category | Category IV conforming to IEC 61010-2-030 |
| IP degree of protection | IP20 conforming to IEC 60529 |
| IK degree of protection | IK05 |
| Pollution degree | 3 |
| Relative humidity | 0…95 % at 55 °C conforming to IEC 60721-3-3 |
| Vibration resistance | 3M4 conforming to IEC 60721-3-3 |
| Electromagnetic compatibility | Industrial electromagnetic environment conforming to IEC 61326-1; Radiated EMC conforming to ETSI EN 301 489-17; Electromagnetic emission conforming to IEC 62311 |
| environmental characteristics | Indoor use |
| Logistical informations |
| Country of origin | LV |
| Main |
| Range of product | PowerLogic |
| Product name | PowerTag F160 |
| Product or component type | Energy sensor |
| Poles | 3P; 3P + N |
| Maximum current [Imax] | 160 A |
| [Ib] Basic current | 25 A |
| Starting current | 100 mA |
| Saturation current | 320 A |
| Product specific application | Energy management; Overload alarm; Power factor; Load monitoring; Circuit monitoring |
| Concentrator compatibility | EcoStruxure Panel Server Entry; EcoStruxure Panel Server Universal; EcoStruxure Panel Server Advanced; Harmony Hub; Acti9 PowerTag Link; Acti9 PowerTag Link HD |
| Range compatibility | Acti9 Acti9 C120; Acti9 Acti9 NG125; ComPacT ComPact NSXm; TeSys TeSys GV4; ComPacT ComPacT INS; Acti9 Acti9 iSW; Acti9 Acti9 iSW-NA; Acti9 Acti9 iID; PowerPact PowerPact B |
| Type of measurement | Active and reactive energy; Apparent energy; Active and reactive power; Apparent power; Current; Voltage; Power factor; Internal temperature; Frequency |
| Accuracy class | Class 1 active energy conforming to IEC 61557-12; Class 2 reactive energy conforming to IEC 61557-12; Class 2 apparent energy conforming to IEC 61557-12; Class 1 active power conforming to IEC 61557-12; Class 2 reactive power conforming to IEC 61557-12; Class 2 apparent power conforming to IEC 61557-12; Class 1 current conforming to IEC 61557-12; Class 0.5 voltage conforming to IEC 61557-12; Class 1 power factor conforming to IEC 61557-12; Class 0.5 frequency conforming to IEC 61557-12 |
| Mounting location | Top or bottom |
| Mounting support | Cables |
| Connection pitch | 27 mm |
| Product destination | Switchboard |
| Event management | Voltage loss with measured current at voltage loss |
| Transmission support medium | Radio frequency 2.4…2.4835 GHz conforming to IEEE 802.15.4 |
| Emission power | 10 mW |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 4.900 cm |
| Package 1 Width | 11.400 cm |
| Package 1 Length | 8.400 cm |
| Package 1 Weight | 135.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 24 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 3.624 kg |
The PowerTag Energy F160 3P/3P+N is a wirelessly communicating energy meter. With its flexible design, it is suitable for 3P and 3P+N measuring points with a phase distance of 25 to 27 mm and a rated current of up to 160 A. The energy meter must be connected to a concentrator or a gateway. It is specifically designed for energy management, load monitoring and availability applications. It includes accurate real-time measurements of active, reactive and apparent energy, active, reactive and apparent power, current, voltage and power factor. With 4 quadrant energy measurement. In the event of a power failure, it sends a voltage loss alarm and the value of the current per phase before being switched off. PowerTag Energy F160 complies with the IEC 61557-12 standard. It is a PMD-II/DD/K70/1. The accuracy class is Class 1. The Imax maximum current is 160A. The Ib base current is 25A. The saturation current is 320A and the actual inrush current is 100mA. The Un rated voltage is phase-neutral 100 to 277VAC +/- 20% and phase-phase 173 to 480VAC +/- 20%. The maximum consumption is less than or equal to 3VA. It can be mounted either on the top or bottom of the protective device. The product color is white (RAL9003). The weight is 100 g. The protection class is IP20 and IK05. The operating temperature is between -25°C and +70°C. The storage temperature is between -40°C and +85°C.