| Additional features |
| Type of surge arrester class | Type 1 + 2 |
| Surge arrester technology | MOV + GDT |
| [Ue] Rated operational voltage | 230/400 V AC at 50/60 Hz |
| [In] rated surge current | Differential: 25 kA (L/N); Common mode: 100 kA (N/PE) |
| [Imax] max. surge current | Differential operation: 65 kA L/N; Common mode: 130 kA N/PE |
| [Iimp] lightning impulse current | Differential mode: 25 kA L/N 12.5 A.s; Common mode: 100 kA N/PE 50 A.s |
| [Uc] Maximum continuous voltage | Differential mode: 300 V L/N; Common mode: 305 V N/PE |
| [Up] Protection level | Differential mode 1.5 kV L/N; Common mode 1.5 kV N/PE |
| [Ut] temporary overvoltage TOV | 442 V L/N 120 min withstand; 1200 V N/PE 200 ms withstand |
| [Ifi] follow current | 100 A N/PE |
| [Isccr] Short-circuit withstand capability | 50 kA |
| Max. mains-side overcurrent protection | Connected fuse gG 315 A |
| Local signalling | Operating status: indicator bit (green); Fault indication: indicator bit (red) |
| Signal circuit voltage | 1 A/250 V AC; 1 A/125 V AC; 0,5 A/48 V DC; 0,5 A/24 V DC; 0,5 A/12 V DC |
| Mounting mode | Plug-in (DIN rail) |
| 9-mm pitch | 16 |
| Height | 110,5 mm |
| Width | 144 mm |
| Depth | 86 mm |
| Product weight | 1,074 kg |
| Quantity per set | Set of 1 piece |
| Colour | White (RAL 9003) |
| Material | Thermoplastic |
| [tA] Response time | < 100 ns L/N; < 100 ns N/PE |
| Cable cross-section | 0.25…1.5 mm² solid cable for remote control; 6…35 mm² robust stranded cable for power connections; 6…25 mm² flexible cable for power connections; 16…35 mm² robust stranded cable for grounding terminal; 16…25 mm² flexible cable for grounding terminal |
| Wire stripping length | Remote control: 10 mm; power connections: 18 mm; grounding terminal: 18 mm |
| [M] tightening torque | Circuit: 4.5 Nm |
| Surge current | 25 kA |
| Possible country of use | Germany |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | IPRD1 |
| Product category | Acti9 |
| Product name | Acti9 iPRD1 |
| Product or component type | Surge arrester with plug-in module |
| Device short name | iPRD1 25r |
| Device application | Distribution |
| Standards | IEC 61643-11:2011; EN 61643-11:2012; EN 61643-11:2018/A11 |
| Product certifications | CE |
| Conformity marking | VDE |
| Pole description | 3P + N |
| Remote alarm contact | With |
| Type of surge arrester | Electrical distribution network |
| Earthing system | TT; TN-S |
| Mounting |
| Degree of protection (IP) | IP20 with inserted protection modules and built-in/wired |
| Degree of protection (IK) | IK05 |
| Relative humidity | 5…95 % |
| Operating altitude | 0 - 4000 m |
| Operating ambient temperature | -40…85 °C |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 12,800 cm |
| VPE 1 width | 17,300 cm |
| VPE 1 length | 13,400 cm |
| Packaging weight (Lbs) | 1,212 kg |
| VPE 2 type | S03 |
| VPE 2 quantity | 8 |
| VPE 2 height | 30,000 cm |
| VPE 2 width | 30,000 cm |
| VPE 2 length | 40,000 cm |
| VPE 2 weight | 10,172 kg |
| VPE 3 type | P12 |
| VPE 3 quantity | 128 |
| VPE 3 height | 75,000 cm |
| VPE 3 width | 80,000 cm |
| VPE 3 length | 120,000 cm |
| VPE 3 weight | 176,240 kg |
Acti9 iPRD1 25r modularer Kombiableiter zum Einsatz bei Blitzschutzklasse I+II. max. netzseitiger Überstromschutz 315A gG. Fernmeldekontakt. Optische Funktions - / Defektanzeige des Ableiters (grün OK/ rot Gerät defekt). Geeignet für TN-S und TT Netze. U0-Nennspannung 240 V AC (50/60Hz). Uc -höchste Dauerspannung 305V AC (N-PE) / 300V AC (L-N). In-Nennableitstossstrom 25/100 kA (L-N)/(N-PE). Imax -maximaler Ableitstossstrom 65/130 kA (L-N)/(N-PE). Iimp 25/100kA (L-N/N-PE). Up-Schutzpegel 1,5 kV (L-N/N-PE). DIN-Hutschienenmontage. Abmessung (B) 144mm x (H) 110.5mm x (T) 86mm. Gewicht 1.074kg. Schutzart IP20 integriert. Betriebstemperatur -40 bis +85 Grad Celsius. Entspricht IEC 61643-11:2011, EN 61643-11:2012+A11:2018.