| Complementary |
| Surge arrester class type | Type 2 |
| Surge arrester technology | MOV |
| [Ue] rated operational voltage | 400 V AC (+/- 10 %) at 50/60 Hz |
| Nominal discharge current | Common mode: 15 kA (L/PE); Common mode: 15 kA (N/PE) |
| Maximum discharge current | Common mode: 40 kA L/PE |
| [Uc] maximum continuous operating voltage | Common mode: 340 V L/PE |
| Maximum [Up] voltage protection level | Common mode 1.5 kV type 2 L/PE |
| [Ut] temporary overvoltage | 337 V L/N 5 s withstand; 442 V L/PE 5 s withstand; 1200 V N/PE 200 ms withstand; 1453 V L/PE 200 ms withstand |
| Disconnector device type | Associated circuit breaker iK60N 40 A curve C - Icu 6 kA; Associated fuse gG 63 A - Icu 25 kA |
| Signalling circuit voltage | 0.25 A/250 V AC 50/60 Hz |
| Mounting mode | Clip-on (DIN rail) |
| 9 mm pitches | 8 |
| Height | 81 mm |
| Width | 72 mm |
| Depth | 69 mm |
| Net weight | 335 g |
| Colour | White (RAL 9003) |
| [Ipe] Ground residual current | 25 mA |
| Connections - terminals | Tunnel type terminal (top or bottom) 25 mm² rigid; Tunnel type terminal (top or bottom) 16 mm² flexible; Tunnel type terminal (top or bottom) 16 mm² flexible with ferrule |
| Wire stripping length | 11 mm |
| Tightening torque | 3.5 N.m |
| Compatibility code | IPF K 40 |
| Market segment | Small commercial |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IK degree of protection | IK03 conforming to IEC 62262 |
| Relative humidity | 5…95 % |
| Operating altitude | 2000 m |
| Ambient air temperature for operation | -25…60 °C |
| Ambient air temperature for storage | -40…85 °C |
| Logistical informations |
| Country of origin | CN |
| Main |
| Range of product | IPF K |
| Product name | Acti9 iPF K |
| Product or component type | Surge arrester |
| Device short name | iPF K |
| Device application | Distribution |
| Standards | IEC 61643-11:2011 |
| Product certifications | EAC; CE |
| Poles description | 3P |
| Remote signalling | Without |
| Surge arrester type | Electrical distribution network |
| Earthing system | TN-C; IT 230 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 7.000 cm |
| Package 1 Width | 7.200 cm |
| Package 1 Length | 8.100 cm |
| Package 1 Weight | 327.000 g |
| Unit Type of Package 2 | BB1 |
| Number of Units in Package 2 | 3 |
| Package 2 Height | 8.000 cm |
| Package 2 Width | 9.500 cm |
| Package 2 Length | 27.500 cm |
| Package 2 Weight | 1.041 kg |
| Unit Type of Package 3 | S03 |
| Number of Units in Package 3 | 36 |
| Package 3 Height | 30.000 cm |
| Package 3 Width | 30.000 cm |
| Package 3 Length | 40.000 cm |
| Package 3 Weight | 13.060 kg |
Surge arrester iPF K 40. 3-pole. Imax 40kA, In 15kA, network configuration TN-C, overvoltage protection level kV: =1.5, operating voltage 400 V AC ±10%. Width 4 HP. Front-side color error indication, green not triggered, red triggered. Standard IEC 61643-11: 2011 T2.