| Complementary |
| Surge arrester class type | Type 2 + 3 |
| Surge arrester technology | MOV + GDT |
| [Ue] rated operational voltage | 230 V AC (+/- 10 %) at 50/60 Hz |
| Nominal discharge current | Common mode: 2.5 kA (L/PE); Common mode: 2.5 kA (N/PE); Differential mode: 2.5 kA (L/N) |
| Maximum discharge current | Common mode: 8 kA L/PE; Common mode: 8 kA N/PE; Differential mode: 8 kA L/N |
| [Uoc] open circuit voltage | 10 kV type 3 common mode N/PE; 10 kV type 3 differential mode L/N |
| [Uc] maximum continuous operating voltage | Common mode: 260 V N/PE; Common mode: 350 V L/PE; Differential mode: 350 V L/N |
| Maximum [Up] voltage protection level | Common mode 1.1 kV type 3 N/PE; Differential mode 1 kV type 2 L/N; Differential mode 1.1 kV type 3 L/N; Common mode 1.4 kV type 2 N/PE |
| [Ut] temporary overvoltage | 337 V L/N 5 s withstand; 1200 V N/PE 200 ms safe failure mode; 442 V L/PE 5 s withstand |
| Disconnector device type | Associated circuit breaker iC60L 10 A curve C - Icu 25 kA; Associated circuit breaker IC60N 10 A curve C - Icu 10 kA; Associated circuit breaker iC60H 10 A curve C - Icu 15 kA; Associated fuse gG 25 A - Icu 15 kA; Associated fuse gG 80 A - Icu 50 kA |
| Mounting mode | Clip-on (DIN rail) |
| 9 mm pitches | 4 |
| Height | 85 mm |
| Width | 36 mm |
| Depth | 69 mm |
| Net weight | 0.211 kg |
| Colour | White (RAL 9003) |
| [Ipe] Ground residual current | 0.6 mA; 0.003 mA |
| Connections - terminals | Tunnel type terminal (downside) 2.5…35 mm²; Tunnel type terminal (upside) 2.5…35 mm² |
| Tightening torque | 2.5 N.m |
| Compatibility code | IPRD8 |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IK degree of protection | IK03 conforming to IEC 62262 |
| Relative humidity | 5…95 % |
| Operating altitude | 2000 m |
| Ambient air temperature for operation | -25…60 °C |
| Ambient air temperature for storage | -40…85 °C |
| Logistical informations |
| Country of origin | CN |
| Main |
| Range of product | IPRD |
| Product name | Acti9 iPRD |
| Product or component type | Surge arrester with pluggable cartridge |
| Device short name | iPRD8 |
| Device application | Distribution |
| Standards | EN 61643-11:2012; IEC 61643-11:2011 |
| Product certifications | CE |
| Quality labels | KEMA-KEUR; NF |
| Poles description | 1P + N |
| Remote signalling | Without |
| Surge arrester type | Electrical distribution network |
| Earthing system | TN-S; TT |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 4.2 cm |
| Package 1 Width | 7.5 cm |
| Package 1 Length | 9 cm |
| Package 1 Weight | 236 g |
| Unit Type of Package 2 | BB1 |
| Number of Units in Package 2 | 6 |
| Package 2 Height | 8.5 cm |
| Package 2 Width | 10 cm |
| Package 2 Length | 28 cm |
| Package 2 Weight | 1.477 kg |
| Unit Type of Package 3 | S03 |
| Number of Units in Package 3 | 54 |
| Package 3 Height | 30 cm |
| Package 3 Width | 30 cm |
| Package 3 Length | 40 cm |
| Package 3 Weight | 13.831 kg |
The Acti 9 iPRD8 surge arrester from Schneider Electric is a plug-in protection module for electrical distribution networks. It serves as secondary protection and is installed close to sensitive consumers when these are more than 10 meters away from the primary surge protection. The device is part of the IPRD series and belongs to the Acti9 product range. It is designed for use in distribution systems and complies with standards EN 61643-11:2012 and IEC 61643-11:2011. Certifications CE, KEMA-KEUR, and NF confirm compliance with applicable safety and quality requirements.
Applications
The iPRD8 is designed for use in electrical distribution networks, particularly in buildings with sensitive electronic equipment. It protects against transient overvoltages caused by lightning strikes or network switching operations. Installation takes place close to the loads to be protected, minimizing the cable length between primary and secondary protection. This is especially important when the distance to the previous surge arrester exceeds 10 meters, to ensure the effectiveness of protection.
Functions and Equipment in Detail
The device is configured as 1P + N and provides a protection level of 1.1 kV in common-mode operation (N/PE, Type 3) and 1 kV in differential mode (L/N, Type 2). The maximum discharge current is 8 kA in common-mode (L/PE and N/PE) and in differential mode (L/N). The rated operating voltage is 230 V AC (±10 %) at 50/60 Hz. The maximum continuous voltage is 350 V in differential mode (L/N) and 350 V in common-mode (L/PE), as well as 260 V in common-mode (N/PE). The open-circuit voltage is 10 kV in Type 3 common-mode (N/PE) and 10 kV in differential mode (L/N). The temporary overvoltage (TOV) is 337 V L/N for 5 seconds (withstand) and 1200 V N/PE for 200 ms (safe failure mode).
Technology Explained Simply
The surge arrester is based on MOV + GDT technology (Metal-Oxide Varistor and Gas Discharge Tube), enabling efficient overvoltage diversion. MOV technology reacts quickly to voltage spikes, while GDT handles higher energy loads. The device is suitable for TN-S and TT earthing systems. It features tunnel terminals at the top and bottom for cross-sections from 2.5 to 35 mm². The tightening torque is 2.5 Nm. Protective conductor currents are 0.6 mA (L/PE) and 0.003 mA (N/PE). The device is plug-in mounted on DIN rail and conforms to the 9 mm pitch with a height of 85 mm, width of 36 mm, and depth of 69 mm. The color is white (RAL 9003).
Compatibility and Accessories
The iPRD8 is compatible with various disconnectors from the iC60 series, such as the iC60L 10 A Curve C (Icu 25 kA), iC60N 10 A Curve C (Icu 10 kA), and iC60H 10 A Curve C (Icu 15 kA). Fuses gG with 25 A (Icu 15 kA) and 80 A (Icu 50 kA) can also be used. Suitable accessories include the iC60L 2p C 10A LS switch, the iC60H 1p+N C 10A LS switch, the STI 1p+N 25A fuse disconnector for 10.3x38 mm, and the iC60N 1p+N C 10A LS switch.
Mounting and Installation
Mounting is done on DIN rail, with the device being plug-in. The protection rating is IK03 according to IEC 62262. The operating ambient temperature ranges from -25 °C to 60 °C, and the storage temperature ranges from -40 °C to 85 °C. Relative humidity is 5 to 95 %. The operating altitude is limited to 2,000 m.
Advantages in Operation
The iPRD8 provides reliable secondary protection for sensitive electronic equipment. The plug-in design enables flexible installation and maintenance. The combination of MOV and GDT ensures efficient overvoltage diversion. Compatibility with various disconnectors and fuses facilitates integration into existing distribution systems. Clear pole identification (1P + N) and distinct connection terminals support safe installation. The device is suitable for TN-S and TT earthing systems, enabling broad applicability in various electrical installations.