| Additional features |
| Type of surge arrester class | Type 2 + 3 |
| Surge arrester technology | MOV |
| [Ue] Rated operational voltage | 230 V AC (± 10 %) at 50/60 Hz |
| [In] rated surge current | Common mode: 2.5 kA (L/PE); Common mode: 2.5 kA (N/PE) |
| [Imax] max. surge current | Common mode: 8 kA L/PE; Common mode: 8 kA N/PE |
| [Uoc] No-load voltage | 10 kV Type 3 common mode L/PE; 10 kV Type 3 common mode N/PE |
| [Uc] Maximum continuous voltage | Common mode: 350 V L/PE; Common mode: 350 V N/PE |
| [Up] Protection level | Common mode 1 kV Type 2 L/PE; Common mode 1 kV Type 2 N/PE; Common mode 1 kV Type 3 L/PE; Common mode 1 kV Type 3 N/PE |
| [Ut] temporary overvoltage TOV | 337 V L/N 5 s withstand; 1200 V N/PE 200 ms safe failure mode |
| Max. mains-side overcurrent protection | Associated disconnect switch iC60L 10 A curve C - Icu 25 kA; Associated disconnect switch iC60N 10 A curve C - Icu 10 kA; Associated disconnect switch iC60H 10 A curve C - Icu 15 kA; Connected fuse gG 25 A - Icu 15 kA; Connected fuse gG 80 A - Icu 50 kA |
| Mounting mode | Plug-in (DIN rail) |
| 9-mm pitch | 4 |
| Height | 85 mm |
| Width | 36 mm |
| Depth | 69 mm |
| Product weight | 0,216 kg |
| Colour | White (RAL 9003) |
| [Ipe] protective conductor current | 0,6 mA; 0,003 mA |
| Connections - terminals | Tunnel terminals (bottom) 2.5…35 mm²; tunnel terminals (top) 2.5…35 mm² |
| [M] tightening torque | 2,5 Nm |
| Compatibility code | IPRD8 |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | IPRD |
| Product category | Acti9 |
| Product name | Acti 9 iPRD |
| Product or component type | Surge arrester with plug-in module |
| Device short name | iPRD8 |
| Device application | Distribution |
| Standards | EN 61643-11:2012; IEC 61643-11:2011 |
| Product certifications | CE |
| Conformity marking | KEMA-KEUR; NF |
| Pole description | 2P |
| Remote alarm contact | None |
| Type of surge arrester | Electrical distribution network |
| Earthing system | TN-C-S |
| Mounting |
| Degree of protection (IK) | IK03 corresponds to IEC 62262 |
| Relative humidity | 5…95 % |
| Operating altitude | 2.000 m |
| Operating ambient temperature | -25…60 °C |
| Ambient temperature during storage | -40…85 °C |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 4,2 cm |
| VPE 1 width | 7,2 cm |
| VPE 1 length | 9 cm |
| Packaging weight (Lbs) | 246 g |
| VPE 2 type | BB1 |
| VPE 2 quantity | 6 |
| VPE 2 height | 9,8 cm |
| VPE 2 width | 8,5 cm |
| VPE 2 length | 28 cm |
| VPE 2 weight | 1,56 kg |
| VPE 3 type | S03 |
| VPE 3 quantity | 54 |
| VPE 3 height | 30 cm |
| VPE 3 width | 30 cm |
| VPE 3 length | 40 cm |
| VPE 3 weight | 14,553 kg |
Acti 9 iPRD8 surge arrester, plug-in protection modules. 2-pole, 8kA secondary protection, type 3. Is installed near the loads to be protected if they are more than 10 m away from the previously installed surge arrester.