Further information for Schneider Electric A9F95320 circuit breaker 3-pole 20A
Complementary
Network frequency
50/60 Hz
[Ue] rated operational voltage
12...133 V AC 50/60 Hz; 220...240 V AC 50/60 Hz; 380...415 V AC 50/60 Hz; 440 V AC 50/60 Hz;
Magnetic tripping limit
12 x In +/- 20 %
Breaking capacity
70 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 25 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2; 20 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2; 20 kA Icu at
[Ics] rated service breaking capacity
35 kA 50 % x Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 25 kA 50 % x Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 12.5 kA 50 % x Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2; 10 kA 50 % x Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2; 20 kA 100 % x Icu at
Limitation class
3 conforming to EN/IEC 60898-1
[Ui] rated insulation voltage
500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-2
Control type
Toggle
Local signalling
Trip indicator
Mounting mode
Clip-on; Removable comb busbar installed
Mounting support
35 mm DIN rail
Comb busbar and distribution block compatibility
Top or bottom: YES
Connection pitch
18 mm between phases
9 mm pitches
6
Height
85 mm
Width
54 mm
Depth
78.5 mm
Net weight
0.375 kg
Colour
White
Mechanical durability
20000 cycles
Electrical durability
10000 cycles
Connections - terminals
Single terminal (top or bottom) , for 1 cable(s) , 1…25 mm², rigid, copper; Single terminal (top or bottom) , for 1 cable(s) , 1…16 mm², flexible, copper; Single terminal (top or bottom) , for 1 cable(s) , 1…16 mm², flexible with ferrule, copper; Single terminal (top or bottom) , for 1.0 cable(s) , flexible, copper or aluminium, with ring terminal and accessory
Wire stripping length
14 mm for top or bottom connection
Tightening torque
2 N.m top or bottom
Earth-leakage protection
Separate block
Contact position indicator
Contractual warranty
Warranty (in months)
18
Environment
IP degree of protection
IP20 conforming to IEC 60529; IP40 in modular enclosure (Insulation class II) conforming to IEC 60529
Pollution degree
3 conforming to EN/IEC 60947-2
Overvoltage category
IV
Tropicalisation
2 conforming to IEC 60068-1
Relative humidity
95 % at 55 °C
Operating altitude
0...2000 m
Ambient air temperature for operation
-35…70 °C
Ambient air temperature for storage
-40…85 °C
Logistical informations
Country of origin
FR
Main
Range
Acti9
Product name
Acti9 iC60
Product or component type
Miniature circuit-breaker
Device short name
iC60L
Device application
Distribution
Poles description
3P
Number of protected poles
3
[In] rated current
20 A
Network type
AC; DC
Trip unit technology
Thermal-magnetic
Curve code
K
Product compatibility
Vigi iC60 single terminal add-on residual current device 25/40/63 A; Quick Vigi iC60 single terminal add-on residual current device 25/40 A
Utilisation category
Category A conforming to EN/IEC 60947-2
Suitability for isolation
Yes conforming to EN/IEC 60947-2; Yes conforming to EN/IEC 60898-1
Standards
EN/IEC 60947-2; EN/IEC 60898-1
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
7.200 cm
Package 1 Width
5.500 cm
Package 1 Length
9.500 cm
Package 1 Weight
340.000 g
Unit Type of Package 2
BB1
Number of Units in Package 2
4
Package 2 Height
8.000 cm
Package 2 Width
9.600 cm
Package 2 Length
22.500 cm
Package 2 Weight
1.432 kg
Unit Type of Package 3
S03
Number of Units in Package 3
44
Package 3 Height
30.000 cm
Package 3 Width
30.000 cm
Package 3 Length
40.000 cm
Package 3 Weight
16.245 kg
Circuit breaker Acti 9 iC60L, 15kA (IEC/EN 60898-1), 25kA (IEC/EN 60947-2). 3-pole, nominal current 20A, K characteristic, operating voltage (Ue) 380-415V AC, insulation voltage (Ui) 500V AC. Double connection terminal for cable and pin comb bar on the top and bottom of the device. Snap action for low-wear switching of the contacts. Moving insulation cover. Operation of the top hat rail fastening element on the front of the device for tool-free installation and easy access for the user. With mechanical front-side fault indication display (VisiTrip) to indicate trips due to overload or short circuit. Safe contact display (VisiSafe) of the circuit breaker, green display ensures that there is no voltage on the output side. Terminals IP20, moving insulation cover. Single connection terminal from above or below. Easy removal of the individual device when the phase rail is installed, thanks to the fastening element accessible from the front. Can be combined with the residual current circuit breakers from the Acti 9 iID series, as well as the FI Block Vigi iC60. Additional auxiliary modules that can be connected in series (optional) - display of switch position, fault tripping, shunt release, undervoltage release, overvoltage release. Color RAL 9003. The iC60L circuit breaker meets the following standards - IEC/EN 60898-1 (up to 40A) and IEC/EN 60947-2. This series is also VDE certified!