Further information for Schneider Electric A9F94106 circuit breaker 1-pole C 6A
Complementary
Network frequency
50/60 Hz
[Ue] rated operational voltage
12...60 V AC 50/60 Hz; 100...133 V AC 50/60 Hz; 220...240 V AC 50/60 Hz; 12...60 V DC; 60...72 V DC
Magnetic tripping limit
8 x In +/- 20 %
Breaking capacity
70 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2; 50 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 25 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 25 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2; 20 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2; 15000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
[Ics] rated service breaking capacity
35 kA 50 % x Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2; 25 kA 50 % x Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 12.5 kA 50 % x Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 25 kA 100 % x Icu at 12...60 V DC conforming to EN/IEC 60947-2; 20 kA 100 % x Icu at 60...72 V DC conforming to EN/IEC 60947-2
Limitation class
3 conforming to EN/IEC 60898-1
[Ui] rated insulation voltage
500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-2
Control type
Toggle
Local signalling
Trip indicator
Mounting mode
Clip-on; Removable comb busbar installed
Mounting support
35 mm DIN rail
Comb busbar and distribution block compatibility
Top or bottom: YES
Connection pitch
18 mm between devices
9 mm pitches
2
Height
85 mm
Width
18 mm
Depth
78.5 mm
Net weight
0.215 kg
Colour
White
Mechanical durability
20000 cycles
Electrical durability
10000 cycles
Connections - terminals
Single terminal (top or bottom) , for 1 cable(s) , 1…25 mm², rigid, copper; Single terminal (top or bottom) , for 1 cable(s) , 1…16 mm², flexible, copper; Single terminal (top or bottom) , for 1 cable(s) , 1…16 mm², flexible with ferrule, copper; Single terminal (top or bottom) , for 1.0 cable(s) , flexible, copper or aluminium, with ring terminal and accessory
Wire stripping length
14 mm for top or bottom connection
Tightening torque
2 N.m top or bottom
Earth-leakage protection
Without
Contact position indicator
Contractual warranty
Warranty (in months)
18
Environment
IP degree of protection
IP20 conforming to IEC 60529; IP40 in modular enclosure (Insulation class II) conforming to IEC 60529
Pollution degree
3 conforming to EN/IEC 60947-2
Overvoltage category
IV
Tropicalisation
2 conforming to IEC 60068-1
Relative humidity
95 % at 55 °C
Operating altitude
0...2000 m
Ambient air temperature for operation
-35…70 °C
Ambient air temperature for storage
-40…85 °C
Logistical informations
Country of origin
FR
Main
Range
Acti9
Product name
Acti9 iC60
Product or component type
Miniature circuit-breaker
Device short name
iC60L
Device application
Distribution
Poles description
1P
Number of protected poles
1
[In] rated current
6 A
Network type
DC; AC
Trip unit technology
Thermal-magnetic
Curve code
C
Product compatibility
Vigi iC60 single terminal add-on residual current device 25/40/63 A; Quick Vigi iC60 single terminal add-on residual current device 25/40 A
Utilisation category
Category A conforming to EN/IEC 60947-2
Suitability for isolation
Yes conforming to EN/IEC 60947-2; Yes conforming to EN/IEC 60898-1
Standards
EN/IEC 60947-2; EN/IEC 60898-1
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
2.000 cm
Package 1 Width
7.500 cm
Package 1 Length
9.500 cm
Package 1 Weight
110.000 g
Unit Type of Package 2
BB1
Number of Units in Package 2
12
Package 2 Height
8.000 cm
Package 2 Width
10.000 cm
Package 2 Length
22.500 cm
Package 2 Weight
1.378 kg
Unit Type of Package 3
S03
Number of Units in Package 3
132
Package 3 Height
30.000 cm
Package 3 Width
30.000 cm
Package 3 Length
40.000 cm
Package 3 Weight
15.624 kg
The circuit breaker Acti9 iC60L from Schneider Electric is a 1-pole switch with a rated current of 6 A and a C-characteristic, designed for distribution in electrical installations. It belongs to the Acti9 series and is designated as iC60L. The device is designed for use in networks with alternating and direct voltage and complies with standards EN/IEC 60947-2 and EN/IEC 60898-1, with usage category A according to EN/IEC 60947-2. The operating voltage covers multiple ranges: 12–60 V AC, 100–133 V AC, 220–240 V AC, as well as 12–60 V DC and 60–72 V DC. The rated insulation voltage is 500 V AC, and the rated impulse withstand voltage is 6 kV. The protection rating of the terminals is IP20, while in modular enclosures, a protection rating of IP40 is achieved, requiring Class II insulation.
Applications
The switch is suitable for use in distribution systems, particularly in installations requiring high reliability and safety. It can be used in residential and commercial buildings, industrial facilities, and electrical distribution enclosures. Compatibility with RCDs from the Acti 9 iID series and with the Vigi iC60 RCD module expands application possibilities. The IP20 protection rating allows use in indoor environments, while the IP40 variant in modular enclosures provides additional protection against contact and contamination.
Functions and Equipment in Detail
The switch features thermal-magnetic tripping technology, providing overload and short-circuit protection. The magnetic tripping threshold is at 8 times the rated current (±20 %). The contact position indicator (VisiSafe) shows green when the output side is de-energized, enabling a safe working environment. A front-mounted tripping indicator (VisiTrip) mechanically signals when the switch has tripped due to overload or short-circuit. The snap-action switching ensures wear-free contact operation, and the moving insulation cover increases safety during installation and maintenance.
Technology Explained Simply
The C-characteristic means the switch does not trip immediately during short-term current surges (e.g., when motors are switched on), but only when the current exceeds 8 times the rated current for a sustained period. The breaking capacity is 25 kA Icu at 220–240 V AC according to EN/IEC 60947-2 and 15000 A Icn according to EN/IEC 60898-1. The limiting class 3 according to EN/IEC 60898-1 indicates that the switch is suitable for limiting short-circuit currents. The mechanical life is 20,000 cycles, and the electrical life is 10,000 cycles.
Compatibility and Accessories
The switch is designed for mounting on a 35 mm DIN rail and can be connected at the top or bottom. The terminal connections are suitable for cable cross-sections of 1 to 25 mm² (solid copper), 1 to 16 mm² (flexible copper), and 1 to 16 mm² (flexible copper with wire end ferrule). Connections with ring terminals and accessories for copper or aluminium conductors are also possible. The wire stripping length is 14 mm, and the torque for the terminals is specified as 2 Nm. The connection pitch is 18 mm between devices, and the height of the device is 85 mm, the width is 18 mm, and the depth is 78.5 mm. The colour is white, corresponding to RAL 9003.
Installation and Mounting
Mounting is tool-free via the mounting element on the front of the device, enabling easy installation and removal, especially with installed phase bars. The terminals are IP20, and the moving insulation cover increases safety. The terminals are available at the top and bottom, allowing flexible installation in distribution enclosures. The operating temperature ranges from -35 °C to 70 °C, and the storage temperature ranges from -40 °C to 85 °C. The operating altitude is up to 2000 m above sea level, and the relative humidity may reach up to 95 % at 55 °C.
Operational Advantages
The switch offers high reliability through thermal-magnetic tripping technology and long service life. The front-mounted indicators (VisiTrip and VisiSafe) simplify maintenance and safety checks. Tool-free mounting and easy removal increase efficiency during installation and maintenance. Compatibility with additional modules such as load current release units, under-voltage release units, or auxiliary contacts extends functionality. The IP20 protection rating and Class II insulation ensure safe operation in indoor environments. Compliance with standards EN/IEC 60947-2 and EN/IEC 60898-1, as well as VDE certification, guarantee the quality and safety of the device.