Schneider Electric A9F94106, EAN: 3606480084515

Schneider Electric A9F94106 circuit breaker 1-pole C 6A

Installation > Modular devices / equipment installation > Circuit breaker

Schneider Electric A9F94106 circuit breaker 1-pole C 6A

Lieske Part No. 608300
Mfg Part No A9F94106
EAN-Code 3606480084515
Manufacturer Schneider Electric
Here only 62,70 EUR
74,61 EUR incl. VAT

Further information for Schneider Electric A9F94106 circuit breaker 1-pole C 6A

Complementary
Network frequency50/60 Hz
[Ue] rated operational voltage12...60 V AC 50/60 Hz; 100...133 V AC 50/60 Hz; 220...240 V AC 50/60 Hz; 12...60 V DC; 60...72 V DC
Magnetic tripping limit8 x In +/- 20 %
Breaking capacity70 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2; 50 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 25 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 25 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2; 20 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2; 15000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
[Ics] rated service breaking capacity35 kA 50 % x Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2; 25 kA 50 % x Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 12.5 kA 50 % x Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 25 kA 100 % x Icu at 12...60 V DC conforming to EN/IEC 60947-2; 20 kA 100 % x Icu at 60...72 V DC conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2
Control typeToggle
Local signallingTrip indicator
Mounting modeClip-on; Removable comb busbar installed
Mounting support35 mm DIN rail
Comb busbar and distribution block compatibilityTop or bottom: YES
Connection pitch18 mm between devices
9 mm pitches2
Height85 mm
Width18 mm
Depth78.5 mm
Net weight0.215 kg
ColourWhite
Mechanical durability20000 cycles
Electrical durability10000 cycles
Connections - terminalsSingle terminal (top or bottom) , for 1 cable(s) , 1…25 mm², rigid, copper; Single terminal (top or bottom) , for 1 cable(s) , 1…16 mm², flexible, copper; Single terminal (top or bottom) , for 1 cable(s) , 1…16 mm², flexible with ferrule, copper; Single terminal (top or bottom) , for 1.0 cable(s) , flexible, copper or aluminium, with ring terminal and accessory
Wire stripping length14 mm for top or bottom connection
Tightening torque2 N.m top or bottom
Earth-leakage protectionWithout
Contact position indicatorYes
Contractual warranty
Warranty (in months)18
Environment
IP degree of protectionIP20 conforming to IEC 60529; IP40 in modular enclosure (Insulation class II) conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Overvoltage categoryIV
Tropicalisation2 conforming to IEC 60068-1
Relative humidity95 % at 55 °C
Operating altitude0...2000 m
Ambient air temperature for operation-35…70 °C
Ambient air temperature for storage-40…85 °C
Logistical informations
Country of originFR
Main
RangeActi9
Product nameActi9 iC60
Product or component typeMiniature circuit-breaker
Device short nameiC60L
Device applicationDistribution
Poles description1P
Number of protected poles1
[In] rated current6 A
Network typeDC; AC
Trip unit technologyThermal-magnetic
Curve codeC
Product compatibilityVigi iC60 single terminal add-on residual current device 25/40/63 A; Quick Vigi iC60 single terminal add-on residual current device 25/40 A
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Suitability for isolationYes conforming to EN/IEC 60947-2; Yes conforming to EN/IEC 60898-1
StandardsEN/IEC 60947-2; EN/IEC 60898-1
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height2.000 cm
Package 1 Width7.500 cm
Package 1 Length9.500 cm
Package 1 Weight110.000 g
Unit Type of Package 2BB1
Number of Units in Package 212
Package 2 Height8.000 cm
Package 2 Width10.000 cm
Package 2 Length22.500 cm
Package 2 Weight1.378 kg
Unit Type of Package 3S03
Number of Units in Package 3132
Package 3 Height30.000 cm
Package 3 Width30.000 cm
Package 3 Length40.000 cm
Package 3 Weight15.624 kg
The circuit breaker Acti9 iC60L from Schneider Electric is a 1-pole switch with a rated current of 6 A and a C-characteristic, designed for distribution in electrical installations. It belongs to the Acti9 series and is designated as iC60L. The device is designed for use in networks with alternating and direct voltage and complies with standards EN/IEC 60947-2 and EN/IEC 60898-1, with usage category A according to EN/IEC 60947-2. The operating voltage covers multiple ranges: 12–60 V AC, 100–133 V AC, 220–240 V AC, as well as 12–60 V DC and 60–72 V DC. The rated insulation voltage is 500 V AC, and the rated impulse withstand voltage is 6 kV. The protection rating of the terminals is IP20, while in modular enclosures, a protection rating of IP40 is achieved, requiring Class II insulation.

Applications

The switch is suitable for use in distribution systems, particularly in installations requiring high reliability and safety. It can be used in residential and commercial buildings, industrial facilities, and electrical distribution enclosures. Compatibility with RCDs from the Acti 9 iID series and with the Vigi iC60 RCD module expands application possibilities. The IP20 protection rating allows use in indoor environments, while the IP40 variant in modular enclosures provides additional protection against contact and contamination.

Functions and Equipment in Detail

The switch features thermal-magnetic tripping technology, providing overload and short-circuit protection. The magnetic tripping threshold is at 8 times the rated current (±20 %). The contact position indicator (VisiSafe) shows green when the output side is de-energized, enabling a safe working environment. A front-mounted tripping indicator (VisiTrip) mechanically signals when the switch has tripped due to overload or short-circuit. The snap-action switching ensures wear-free contact operation, and the moving insulation cover increases safety during installation and maintenance.

Technology Explained Simply

The C-characteristic means the switch does not trip immediately during short-term current surges (e.g., when motors are switched on), but only when the current exceeds 8 times the rated current for a sustained period. The breaking capacity is 25 kA Icu at 220–240 V AC according to EN/IEC 60947-2 and 15000 A Icn according to EN/IEC 60898-1. The limiting class 3 according to EN/IEC 60898-1 indicates that the switch is suitable for limiting short-circuit currents. The mechanical life is 20,000 cycles, and the electrical life is 10,000 cycles.

Compatibility and Accessories

The switch is designed for mounting on a 35 mm DIN rail and can be connected at the top or bottom. The terminal connections are suitable for cable cross-sections of 1 to 25 mm² (solid copper), 1 to 16 mm² (flexible copper), and 1 to 16 mm² (flexible copper with wire end ferrule). Connections with ring terminals and accessories for copper or aluminium conductors are also possible. The wire stripping length is 14 mm, and the torque for the terminals is specified as 2 Nm. The connection pitch is 18 mm between devices, and the height of the device is 85 mm, the width is 18 mm, and the depth is 78.5 mm. The colour is white, corresponding to RAL 9003.

Installation and Mounting

Mounting is tool-free via the mounting element on the front of the device, enabling easy installation and removal, especially with installed phase bars. The terminals are IP20, and the moving insulation cover increases safety. The terminals are available at the top and bottom, allowing flexible installation in distribution enclosures. The operating temperature ranges from -35 °C to 70 °C, and the storage temperature ranges from -40 °C to 85 °C. The operating altitude is up to 2000 m above sea level, and the relative humidity may reach up to 95 % at 55 °C.

Operational Advantages

The switch offers high reliability through thermal-magnetic tripping technology and long service life. The front-mounted indicators (VisiTrip and VisiSafe) simplify maintenance and safety checks. Tool-free mounting and easy removal increase efficiency during installation and maintenance. Compatibility with additional modules such as load current release units, under-voltage release units, or auxiliary contacts extends functionality. The IP20 protection rating and Class II insulation ensure safe operation in indoor environments. Compliance with standards EN/IEC 60947-2 and EN/IEC 60898-1, as well as VDE certification, guarantee the quality and safety of the device.