Further information for Schneider Electric A9F90225 circuit breaker 2-pole 25A
Complementary
Network frequency
50/60 Hz
[Ue] rated operational voltage
220...240 V AC 50/60 Hz; 380...415 V AC 50/60 Hz; 440 V AC 50/60 Hz
Magnetic tripping limit
12 x In +/- 20 %
Breaking capacity
30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2; 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Ics] rated service breaking capacity
15 kA 50 % x Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 7.5 kA 50 % x Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2; 5 kA 50 % x Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Ui] rated insulation voltage
500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-2
Control type
Toggle
Local signalling
Trip indicator
Mounting mode
Clip-on; Removable comb busbar installed
Mounting support
35 mm DIN rail
Comb busbar and distribution block compatibility
Top or bottom: YES
Connection pitch
18 mm between phases
9 mm pitches
4
Height
85 mm
Width
36 mm
Depth
78.5 mm
Net weight
0.25 kg
Colour
White
Mechanical durability
20000 cycles
Electrical durability
10000 cycles
Connections - terminals
Single terminal (top or bottom) , for 1 cable(s) , 1…25 mm², rigid, copper; Single terminal (top or bottom) , for 1 cable(s) , 1…16 mm², flexible, copper; Single terminal (top or bottom) , for 1 cable(s) , 1…16 mm², flexible with ferrule, copper; Single terminal (top or bottom) , for 1.0 cable(s) , flexible, copper or aluminium, with ring terminal and accessory
Wire stripping length
14 mm for top or bottom connection
Tightening torque
2 N.m top or bottom
Earth-leakage protection
Separate block
Contact position indicator
Contractual warranty
Warranty (in months)
18
Environment
IP degree of protection
IP20 conforming to IEC 60529; IP40 in modular enclosure (Insulation class II) conforming to IEC 60529
Pollution degree
3 conforming to EN/IEC 60947-2
Overvoltage category
IV
Tropicalisation
2 conforming to IEC 60068-1
Relative humidity
95 % at 55 °C
Operating altitude
0...2000 m
Ambient air temperature for operation
-35…70 °C
Ambient air temperature for storage
-40…85 °C
Logistical informations
Country of origin
FR
Main
Range
Acti9
Product name
Acti9 iC60
Product or component type
Miniature circuit-breaker
Device short name
iC60L
Device application
Motor
Poles description
2P
Number of protected poles
2
[In] rated current
25 A
Network type
AC
Trip unit technology
Magnetic
Curve code
MA
Product compatibility
Vigi iC60 single terminal add-on residual current device 40/63 A; Quick Vigi iC60 single terminal add-on residual current device 40 A
Utilisation category
Category A conforming to EN/IEC 60947-2
Suitability for isolation
Yes conforming to EN/IEC 60947-2
Standards
EN/IEC 60947-2
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
7.100 cm
Package 1 Width
3.500 cm
Package 1 Length
9.200 cm
Package 1 Weight
253.000 g
Unit Type of Package 2
BB1
Number of Units in Package 2
6
Package 2 Height
8.100 cm
Package 2 Width
9.800 cm
Package 2 Length
22.300 cm
Package 2 Weight
1.580 kg
Unit Type of Package 3
S03
Number of Units in Package 3
66
Package 3 Height
30.000 cm
Package 3 Width
30.000 cm
Package 3 Length
40.000 cm
Package 3 Weight
17.650 kg
Circuit breaker Acti 9 C120N, 10kA (IEC/EN 60898-1), 10kA (IEC/EN 60947-2). 2-pole, nominal current 80A, D characteristic, operating voltage (Ue) 380-415V AC, insulation voltage (Ui) 500V AC. Protecting circuits against short-circuit currents and overload currents. Terminals IP20. Fully open contacts are indicated by the OFF marking on the switch knob, so that work on the downstream system part can be carried out with due safety. Power supply from above and below. Snap action for low-wear switching of the contacts. Technology of the trip unit - thermomagnetic. Can be combined with the FI Block Vigi for C120. Additional auxiliary modules (optional) that can be connected in series - display of switch position, fault tripping, shunt release, undervoltage release, overvoltage release. Color RAL 9003. The C120N circuit breaker meets the following standards - IEC/EN 60898-1 and IEC/EN 60947-2. This series is also VDE certified.