Further information for Schneider Electric A9F07204 circuit breaker 2-pole C 4A
Complementary
Network frequency
50/60 Hz
[Ue] rated operational voltage
12...133 V AC 50/60 Hz; 220...240 V AC 50/60 Hz; 380...415 V AC 50/60 Hz; 440 V AC 50/60 Hz;
Magnetic tripping limit
8 x In +/- 20 %
Breaking capacity
70 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 70 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 70 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2; 50 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA Icu at
[Ics] rated service breaking capacity
70 kA 100 % x Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 70 kA 100 % x Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 70 kA 100 % x Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2; 50 kA 100 % x Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA 100 % x Icu at
Limitation class
3 conforming to EN/IEC 60898-1
[Ui] rated insulation voltage
500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-2
Control type
Toggle
Local signalling
Trip indicator
Mounting mode
Clip-on; Removable comb busbar installed
Mounting support
35 mm DIN rail
Connection pitch
18 mm between phases
9 mm pitches
4
Height
91 mm
Width
36 mm
Depth
78.5 mm
Net weight
0.25 kg
Colour
White
Mechanical durability
20000 cycles
Electrical durability
10000 cycles
Connections - terminals
Double terminal (top or bottom) , for 1 cable(s) , 1…25 mm², rigid, copper; Double terminal (top or bottom) , for 1 cable(s) , 1…16 mm², flexible, copper; Double terminal (top or bottom) , for 1 cable(s) , 1…16 mm², flexible with ferrule, copper; Double terminal (top or bottom) , for 1.0 cable(s) , flexible, copper or aluminium, with ring terminal and accessory
Wire stripping length
14 mm for top or bottom connection
Tightening torque
2 N.m top or bottom
Earth-leakage protection
Separate block
Contact position indicator
Contractual warranty
Warranty (in months)
18
Environment
IP degree of protection
IP20 conforming to IEC 60529; IP40 in modular enclosure (Insulation class II) conforming to IEC 60529
Pollution degree
3 conforming to EN/IEC 60947-2
Overvoltage category
IV
Tropicalisation
2 conforming to IEC 60068-1
Relative humidity
95 % at 55 °C
Ambient air temperature for operation
-35…70 °C
Ambient air temperature for storage
-40…85 °C
Main
Range
Acti9
Product name
Acti9 iC60
Product or component type
Miniature circuit-breaker
Device short name
iC60H
Device application
Distribution
Poles description
2P
Number of protected poles
2
[In] rated current
4 A
Network type
DC; AC
Trip unit technology
Thermal-magnetic
Curve code
C
Product compatibility
Vigi iC60 double terminal add-on residual current device 25/63 A
Utilisation category
Category A conforming to EN/IEC 60947-2
Suitability for isolation
Yes conforming to EN/IEC 60898-1; Yes conforming to EN/IEC 60947-2
Standards
EN/IEC 60947-2; EN/IEC 60898-1
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
3.500 cm
Package 1 Width
7.500 cm
Package 1 Length
9.000 cm
Package 1 Weight
230.600 g
Unit Type of Package 2
BB1
Number of Units in Package 2
6
Package 2 Height
8.500 cm
Package 2 Width
10.000 cm
Package 2 Length
22.000 cm
Package 2 Weight
1.440 kg
Unit Type of Package 3
S03
Number of Units in Package 3
66
Package 3 Height
30.000 cm
Package 3 Width
30.000 cm
Package 3 Length
40.000 cm
Package 3 Weight
16.306 kg
Circuit breaker Acti 9 iC60H, 10kA (IEC/EN 60898-1), 70kA (IEC/EN 60947-2). 2-pole, nominal current 4A, C characteristic, operating voltage (Ue) 380-415V AC, insulation voltage (Ui) 500V AC. Double connection terminal for cable and pin comb bar on the top and bottom of the device. Snap action for low-wear switching of the contacts. Insulation cover that moves with the device. Operation of the top hat rail fastening element on the front of the device for tool-free installation and easy access for the user. With mechanical front-side fault indication display (VisiTrip) to indicate tripping due to overload or short circuit. Safe contact display (VisiSafe) of the circuit breaker, with a green display to ensure that there is no voltage on the output side. Technology of the trip unit - thermomagnetic. Can be combined with the residual current circuit breakers of the Acti 9 iID series, as well as the FI Block Vigi iC60. Additional auxiliary modules (optional) that can be added - display of switch position, fault tripping, shunt release, undervoltage release, overvoltage release. Color RAL 9003. The iC60H circuit breaker meets the following standards - IEC/EN 60898-1 and IEC/EN 60947-2. This series is also VDE certified!