Further information for Schneider Electric A9F04750 circuit breaker 3p+N C 50A
Additional features
Network frequency
50/60 Hz
[Ue] Operational rated voltage
12 - 133 V AC 50/60 Hz; 220 - 240 V AC 50/60 Hz; 380 - 415 V AC 50/60 Hz; 440 V AC 50/60 Hz
Magnetic trip threshold
8 x inch +/-20 %
Breaking capacity
36 kA Icu at 12 - 133 V AC 50/60 Hz conforms to EN/IEC 60947-2; 20 kA Icu at 220 - 240 V AC 50/60 Hz conforms to EN/IEC 60947-2; 10 kA Icu at 380 - 415 V AC 50/60 Hz conforms to EN/IEC 60947-2; 6 kA Icu at 440 V AC 50/60 Hz conforms to EN/IEC 60947-2; 6000 A Icn at 400 V AC 50/60 Hz conforms to EN/IEC 60898-1
Rated switching-off capacity Ics
27 kA 75 % x Icu at 12 - 133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA 75 % x Icu at 220 - 240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 7,5 kA 75 % x Icu at 380 - 415 V AC 50/60 Hz conforming to EN/IEC 60947-2; 4,5 kA 75 % x Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
Limiting class
3 corresponds to EN/IEC 60898-1
[Ui] Rated insulation voltage
500 V AC 50/60 Hz corresponds to EN/IEC 60947-2
[Uimp] Rated impulse voltage withstand
6 kV corresponds to EN/IEC 60947-2
Control type
Toggle switch
Local signalling
trip indicator
Mounting mode
Plug-on; Removable comb rail installed
Mounting bracket
35 mm DIN rail
Terminal pitch
18 mm between phases; 18 mm between phase and neutral
9-mm pitch
8
Height
91 mm
Width
72 mm
Depth
78,5 mm
Product weight
0,5 kg
Colour
White
Mechanical life
20000 cycles
Electrical lifetime
10000 cycles
Wire stripping length
14 mm for top or bottom connection
[M] tightening torque
3.5 Nm top or bottom
Earth fault protection
Separate block
Contact position indicator
Contractual warranty
Warranty (in months)
18
Main features
Product series
Acti9
Product name
Acti9 iC60
Product or component type
Miniature circuit breaker (MCB)
Device short name
iC60N
Device application
Distribution
Pole description
3P + N
Number of protected poles
3
Neutral position
Left
[In] Rated current
50 A
Type of network
AC; DC
Trigger technology
Thermal-magnetic
Cam disc
C
Product compatibility
Vigi iC60 double terminal add-on residual current device 63 A
Application category
Category A corresponds to EN/IEC 60947-2
Suitability for insulation
Yes complies with EN/IEC 60898-1; Yes complies with EN/IEC 60947-2
Standards
EN/IEC 60947-2; EN/IEC 60898-1
Mounting
Degree of protection (IP)
IP20 corresponds to IEC 60529; IP40 in modular enclosure (Class II insulation) corresponds to IEC 60529
Pollution degree
3 corresponds to EN/IEC 60947-2
Over voltage category
IV
Drip-proof
2 corresponds to IEC 60068-1
Relative humidity
95 % at 55 °C
Operating ambient temperature
-35…70 °C
Ambient temperature during storage
-40…85 °C
Packaging units
VPE 1 type
PCE
Number of devices per package
1
VPE 1 height
7,500 cm
VPE 1 width
7,200 cm
VPE 1 length
9,500 cm
Packaging weight (Lbs)
528,000 g
VPE 2 type
BB1
VPE 2 quantity
3
VPE 2 height
8,500 cm
VPE 2 width
9,800 cm
VPE 2 length
22,000 cm
VPE 2 weight
1,649 kg
VPE 3 type
S03
VPE 3 quantity
33
VPE 3 height
30,000 cm
VPE 3 width
30,000 cm
VPE 3 length
40,000 cm
VPE 3 weight
18,755 kg
Circuit breaker Acti 9 iC60N, 6kA (IEC/EN 60898-1), 10kA (IEC/EN 60947-2). 3-pole+N, nominal current 50A, C characteristic, operating voltage (Ue) 380-415V AC, insulation voltage (Ui) 500V AC. Double connection terminal for cable and pin comb bar on the top and bottom of the device. Snap action for low-wear switching of the contacts. Insulation cover that moves with the device. Operation of the top hat rail fastening element on the front of the device for tool-free installation and easy access for the user. With mechanical front-side fault indication display (VisiTrip) to indicate trips due to overload or short circuit. Safe contact display (VisiSafe) of the circuit breaker, with a green display it is certain that there is no voltage on the outgoing side. Terminals IP20, moving insulation cover. Double connection terminal from above or below. Easy removal of the individual device with an installed phase rail, thanks to the fastening element accessible from the front. Technology of the trip unit - thermomagnetic. Can be combined with the residual current circuit breakers of the Acti 9 iID series, as well as the FI Block Vigi iC60. Additional auxiliary modules that can be added in series (optional) - display of switch position, fault tripping, shunt release, undervoltage release, overvoltage release. Color RAL 9003. The iC60N circuit breaker meets the following standards - IEC/EN 60898-1 and IEC/EN 60947-2. This series is also VDE certified!