Further information for Schneider Electric A9F04320 Circuit Breaker 3p 20A
Additional features
Network frequency
50/60 Hz
[Ue] Operational rated voltage
12 - 133 V AC 50/60 Hz; 220 - 240 V AC 50/60 Hz; 380 - 415 V AC 50/60 Hz; 440 V AC 50/60 Hz;
Magnetic trip threshold
8 x inch +/-20 %
Breaking capacity
36 kA Icu at 12 - 133 V AC 50/60 Hz complies with EN/IEC 60947-2; 20 kA Icu at 220 - 240 V AC 50/60 Hz complies with EN/IEC 60947-2; 10 kA Icu at 380 - 415 V AC 50/60 Hz complies with EN/IEC 60947-2; 6 kA Icu at 440 V AC 50/60 Hz complies with EN/IEC 60947-2; 10 kA Icu at
Rated switching-off capacity Ics
27 kA 75 % x Icu at 12 - 133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA 75 % x Icu at 220 - 240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 7.5 kA 75 % x Icu at 380 - 415 V AC 50/60 Hz conforming to EN/IEC 60947-2; 4.5 kA 75 % x Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2; 10 kA 100 % x Icu at
Limiting class
3 corresponds to EN/IEC 60898-1
[Ui] Rated insulation voltage
500 V AC 50/60 Hz corresponds to EN/IEC 60947-2
[Uimp] Rated impulse voltage withstand
6 kV corresponds to EN/IEC 60947-2
Control type
Toggle switch
Local signalling
trip indicator
Mounting mode
Plug-on; Removable comb rail installed
Mounting bracket
35 mm DIN rail
Terminal pitch
18 mm between phases
9-mm pitch
6
Height
91 mm
Width
54 mm
Depth
78,5 mm
Product weight
0,375 kg
Colour
White
Mechanical life
20000 cycles
Electrical lifetime
10000 cycles
Connections - terminals
Double terminal (top or bottom), for 1 cable(s), 1…25 mm², solid, copper; Double terminal (top or bottom), for 1 cable(s), 1…16 mm², stranded, copper; Double terminal (top or bottom), for 1 cable(s), 1…16 mm², stranded with ferrule, copper; Double terminal (top or bottom), for 1.0 cable(s), stranded, copper or aluminium, with ring terminal and accessory
Wire stripping length
14 mm for top or bottom connection
[M] tightening torque
2 Nm top or bottom
Earth fault protection
Separate block
Contact position indicator
Contractual warranty
Warranty (in months)
18
Main features
Product series
Acti9
Product name
Acti9 iC60
Product or component type
Miniature circuit breaker (MCB)
Device short name
iC60N
Device application
Distribution
Pole description
3P
Number of protected poles
3
[In] Rated current
20 A
Type of network
AC; DC
Trigger technology
Thermal-magnetic
Cam disc
C
Product compatibility
Vigi iC60 double terminal add-on residual current device 25/63 A
Application category
Category A corresponds to EN/IEC 60947-2
Suitability for insulation
Yes complies with EN/IEC 60898-1; Yes complies with EN/IEC 60947-2
Standards
EN/IEC 60947-2; EN/IEC 60898-1
Mounting
Degree of protection (IP)
IP20 corresponds to IEC 60529; IP40 in modular enclosure (Class II insulation) corresponds to IEC 60529
Pollution degree
3 corresponds to EN/IEC 60947-2
Over voltage category
IV
Drip-proof
2 corresponds to IEC 60068-1
Relative humidity
95 % at 55 °C
Operating ambient temperature
-35…70 °C
Ambient temperature during storage
-40…85 °C
Packaging units
VPE 1 type
PCE
Number of devices per package
1
VPE 1 height
7,300 cm
VPE 1 width
5,300 cm
VPE 1 length
8,700 cm
Packaging weight (Lbs)
355,000 g
VPE 2 type
BB1
VPE 2 quantity
4
VPE 2 height
8,500 cm
VPE 2 width
9,600 cm
VPE 2 length
22,000 cm
VPE 2 weight
1,472 kg
VPE 3 type
S03
VPE 3 quantity
44
VPE 3 height
30 cm
VPE 3 width
30 cm
VPE 3 length
40 cm
VPE 3 weight
16,840 kg
The circuit breaker Acti9 iC60N from Schneider Electric is a 3-pole switch with a rated current of 20 A and a C characteristic, specifically designed for distribution in electrical installations. It belongs to the Acti9 series and is intended for use in networks with AC and DC voltage. The tripping technology is based on a thermomagnetic principle, which detects both thermal overloads and magnetic short-circuit currents and reacts accordingly. The protection function complies with the standards EN/IEC 60947-2 and EN/IEC 60898-1, with usage category A defined. The operating voltage is 380–415 V AC, the rated insulation voltage is 500 V AC, and the rated impulse withstand voltage is 6 kV. The magnetic tripping threshold is set at 8 times the rated current (±20 %).
Applications
The switch is suitable for use in industrial and commercial distribution systems, particularly in installations requiring high reliability and safety. It can be used in distribution enclosures, machine controls, or lighting systems. The protection rating IP20 at the terminals and IP40 in the modular housing (insulation class II) ensures sufficient protection against contact and contamination. The operating ambient temperature ranges from -35 °C to +70 °C, and the storage temperature ranges from -40 °C to +85 °C. The relative humidity is up to 95 % at 55 °C. The overvoltage category IV and pollution degree 3 meet the requirements for industrial applications.
Functions and Equipment in Detail
The switch features a double terminal at the top and bottom, suitable for connecting cables (1–25 mm² solid, 1–16 mm² flexible, also with wire end ferrules) as well as pin-and-finger busbars. The wire stripping length is 14 mm, and the tightening torque for the terminals is 2 Nm. The spring switching ensures wear-free switching of the contacts. A moving insulation cover protects against unintended contact during mounting and dismounting. The operation of the DIN rail mounting element is performed on the front of the device, enabling tool-free mounting and easy removal.
Technology Explained Simply
The thermomagnetic tripping technology combines a thermal and a magnetic tripping mechanism. The thermal part responds to prolonged overloads, while the magnetic part trips during sudden, high short-circuit currents. The C characteristic means that the switch trips at approximately 5 times the rated current after about 10 seconds, and at 10 times the current within 0.1 seconds. The contact position indicator (VisiSafe) shows green when the contacts are open and the outgoing side is de-energized. The trip indicator (VisiTrip) mechanically signals when the switch has tripped due to overload or short circuit.
Compatibility and Accessories
The switch is compatible with residual current circuit breakers from the Acti9 iID series as well as with the Vigi iC60 residual current module. It can be extended with various auxiliary modules, including overload tripping units, undervoltage tripping units, overvoltage tripping units, auxiliary switches, remote actuators, and reclosing devices. Mounting is done on a 35-mm DIN rail, with a connection pitch of 18 mm. The device height is 91 mm, width 54 mm, and depth 78.5 mm. The color is white, corresponding to RAL 9003.
Mounting and Installation
Mounting is tool-free on a 35-mm DIN rail. The front-accessible mounting enables easy installation and removal, even with a phase busbar installed. The terminals are designed for cable connections from the top or bottom. The mechanical life is 20,000 cycles, and the electrical life is 10,000 cycles.
Operational Advantages
The switch offers high operational safety thanks to the integrated contact and trip indicators. The tool-free mounting and easy removal simplify maintenance. The combinability with additional protection and control modules extends functionality. Compliance with EN/IEC 60947-2 and EN/IEC 60898-1 standards, as well as VDE certification, guarantees adherence to European safety standards. The breaking capacity is 10 kA at 380–415 V AC, which is sufficient for many industrial applications. The limiting class 3 meets the requirements for circuit breakers used at the distribution level.