Further information for Schneider Electric A9F04110 Circuit Breaker 1p C 10A
Additional features
Network frequency
50/60 Hz
[Ue] Operational rated voltage
12 - 60 V AC 50/60 Hz; 100 - 133 V AC 50/60 Hz; 220 - 240 V AC 50/60 Hz; 12 - 60 V DC; 60 - 72 V DC
Magnetic trip threshold
8 x inch +/-20 %
Breaking capacity
36 kA Icu at 12 - 60 V AC 50/60 Hz complies with EN/IEC 60947-2; 20 kA Icu at 100 - 133 V AC 50/60 Hz complies with EN/IEC 60947-2; 10 kA Icu at 220 - 240 V AC 50/60 Hz complies with EN/IEC 60947-2; 15 kA Icu at 12 - 60 V DC complies with EN/IEC 60947-2; 10 kA Icu at 60 - 72 V DC complies with EN/IEC 60947-2; 6000 A Icn at 230 V AC 50/60 Hz complies with EN/IEC 60898-1
Rated switching-off capacity Ics
27 kA 75 % x Icu at 12 - 60 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA 75 % x Icu at 100 - 133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 7.5 kA 75 % x Icu at 220 - 240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA 100 % x Icu at 12 - 60 V DC conforming to EN/IEC 60947-2; 10 kA 100 % x Icu at 60 - 72 V DC conforming to EN/IEC 60947-2
Limiting class
3 corresponds to EN/IEC 60898-1
[Ui] Rated insulation voltage
500 V AC 50/60 Hz corresponds to EN/IEC 60947-2
[Uimp] Rated impulse voltage withstand
6 kV corresponds to EN/IEC 60947-2
Control type
Toggle switch
Local signalling
trip indicator
Mounting mode
Plug-on; Removable comb rail installed
Mounting bracket
35 mm DIN rail
Terminal pitch
18 mm between devices
9-mm pitch
2
Height
91 mm
Width
18 mm
Depth
78,5 mm
Product weight
0,125 kg
Colour
White
Mechanical life
20000 cycles
Electrical lifetime
10000 cycles
Connections - terminals
Double terminal (top or bottom), for 1 cable(s), 1…25 mm², solid, copper; Double terminal (top or bottom), for 1 cable(s), 1…16 mm², stranded, copper; Double terminal (top or bottom), for 1 cable(s), 1…16 mm², stranded with ferrule, copper; Double terminal (top or bottom), for 1.0 cable(s), stranded, copper or aluminium, with ring terminal and accessory
Wire stripping length
14 mm for top or bottom connection
[M] tightening torque
2 Nm top or bottom
Earth fault protection
None
Contact position indicator
Contractual warranty
Warranty (in months)
18
Main features
Product series
Acti9
Product name
Acti9 iC60
Product or component type
Miniature circuit breaker (MCB)
Device short name
iC60N
Device application
Distribution
Pole description
1P
Number of protected poles
1
[In] Rated current
10 A
Type of network
AC; DC
Trigger technology
Thermal-magnetic
Cam disc
C
Application category
Category A corresponds to EN/IEC 60947-2
Suitability for insulation
Yes complies with EN/IEC 60898-1; Yes complies with EN/IEC 60947-2
Standards
EN/IEC 60947-2; EN/IEC 60898-1
Mounting
Degree of protection (IP)
IP20 corresponds to IEC 60529; IP40 in modular enclosure (Class II insulation) corresponds to IEC 60529
Pollution degree
3 corresponds to EN/IEC 60947-2
Over voltage category
IV
Drip-proof
2 corresponds to IEC 60068-1
Relative humidity
95 % at 55 °C
Operating ambient temperature
-35…70 °C
Ambient temperature during storage
-40…85 °C
Packaging units
VPE 1 type
PCE
Number of devices per package
1
VPE 1 height
7,5 cm
VPE 1 width
1,8 cm
VPE 1 length
8,5 cm
Packaging weight (Lbs)
117 g
VPE 2 type
BB1
VPE 2 quantity
12
VPE 2 height
9 cm
VPE 2 width
9,5 cm
VPE 2 length
22 cm
VPE 2 weight
1,439 kg
VPE 3 type
S03
VPE 3 quantity
132
VPE 3 height
30 cm
VPE 3 width
30 cm
VPE 3 length
40 cm
VPE 3 weight
16,509 kg
The circuit breaker Acti9 iC60N from Schneider Electric is a 1-pole circuit breaker of the Acti9 series, designed for use in distribution systems. With a rated current of 10 A and a C-characteristic, it features a thermal-magnetic trip unit that responds to both overload and short-circuit conditions. The devices are designed for operating voltages of 220–240 V AC and comply with standards EN/IEC 60898-1 and EN/IEC 60947-2, with a breaking capacity of 10 kA Icu at 220–240 V AC. The insulation voltage (Ui) is 500 V AC, ensuring high safety during installation.
Applications
This switch is designed for use in electrical distribution systems, particularly in residential and commercial buildings as well as industrial facilities, where reliable protection for individual circuits is required. Compatibility with residual current circuit breakers of the Acti9 iID series and the Vigi iC60 residual current module enables flexible integration into existing switchgear. The devices are designed for operating temperatures from -35 °C to 70 °C and can also be operated at a relative humidity of up to 95 % at 55 °C.
Functions and Equipment in Detail
The switch features a double terminal block at top and bottom, suitable for rigid copper cable (1–25 mm²) and flexible copper cable (1–16 mm²). For flexible conductors with wire end ferrules, the maximum cross-section is 16 mm². The terminals are designed for a connection length of 14 mm, and the required tightening torque is 2 Nm. The snap-action switching ensures wear-free contact switching, extending the contact life. A moving insulation cover protects against accidental contact with the terminals.
Technology Explained Simply
The tripping technology is thermal-magnetic, meaning that during overload, the thermal component (heating wire) activates the trip unit, while during short-circuit, the magnetic component (electromagnet) responds immediately. The C-characteristic corresponds to a tripping threshold of 8 times the rated current (±20 %), suitable for applications with moderate inrush currents. The contact position indicator (VisiSafe) shows green when the output side is de-energized, and the trip indicator (VisiTrip) mechanically signals when the switch has tripped due to overload or short-circuit.
Compatibility and Accessories
The switch is designed for mounting on a 35 mm DIN rail and can be installed without tools, as the mounting element is operated from the front. Mounting is done on a 9 mm grid, requiring two grid positions. The device is compatible with various accessory modules, including current trip units (iMX), undervoltage trip units (iMN), overvoltage trip units (iMSU), remote switches (iTL), and auxiliary contacts (iOF/SD+OF). These modules extend the functionality of the switch, for example for remote control or additional safety functions.
Mounting and Installation
Installation is on a 35 mm DIN rail, with devices mounted at a spacing of 18 mm between units. The front side of the device allows tool-free mounting and removal, simplifying maintenance and expansion of the installation. The protection rating is IP20 at the terminals and IP40 in the modular housing, providing protection against contact and contamination. The devices are designed for ambient temperatures from -35 °C to 70 °C during operation and from -40 °C to 85 °C during storage.
Advantages in Operation
The mechanical life is 20,000 cycles, and the electrical life is 10,000 cycles, ensuring high reliability and durability. The safe contact indicator (VisiSafe) and the trip indicator (VisiTrip) facilitate maintenance and fault diagnosis. Compatibility with various modules allows application-specific adaptation of the switch. The device color is white (RAL 9003), enabling uniform visual design in distribution enclosures. The devices are VDE-certified, confirming compliance with European safety standards.
The devices are available in individual packaging, with the packaging unit containing 1 device. Dimensions are 91 mm (height), 18 mm (width), and 78.5 mm (depth), and the product weight is 0.125 kg. The operating voltage also includes DC ranges (12–60 V DC, 60–72 V DC), with breaking capacities of 15 kA and 10 kA Icu respectively. The rated impulse withstand voltage is 6 kV, ensuring high stability against transient voltage surges. Pollution degree class 3 and overvoltage category IV are suitable for use in industrial and commercial facilities. The drip-proof rating is 2, allowing limited moisture exposure.
The devices are designed for use in distribution systems, with usage category A according to EN/IEC 60947-2. Limitation class 3 corresponds to EN/IEC 60898-1, ensuring high protection performance under short-circuit conditions. The combination of thermal-magnetic trip unit, high breaking capacity, and modular expansion options makes the Acti9 iC60N a versatile and reliable circuit breaker for a wide range of applications.
The described technical features and functions are based exclusively on the information provided by the source. The devices are designed for use in electrical distribution systems, with the specified standards and technical data ensuring safety and reliability. Mounting is on a 35 mm DIN rail, with tool-free mounting and removal facilitated by the front-operated mounting element. Compatibility with various modules allows flexible adaptation to specific requirements. The device color is white (RAL 9003), enabling uniform visual design in distribution enclosures. The devices are VDE-certified, confirming compliance with European safety standards. The operating voltage also includes DC ranges (12–60 V DC, 60–72 V DC), with breaking capacities of 15 kA and 10 kA Icu respectively. The rated impulse withstand voltage is 6 kV, ensuring high stability against transient voltage surges. Pollution degree class 3 and overvoltage category IV are suitable for use in industrial and commercial facilities. The drip-proof rating is 2, allowing limited moisture exposure. The devices are designed for use in distribution systems, with usage category A according to EN/IEC 60947-2. Limitation class 3 corresponds to EN/IEC 60898-1, ensuring high protection performance under short-circuit conditions. The combination of thermal-magnetic trip unit, high breaking capacity, and modular expansion options makes the Acti9 iC60N a versatile and reliable circuit breaker for a wide range of applications.