Further information for Schneider Electric A9F03310 Circuit Breaker 3p B 10A
Additional features
Network frequency
50/60 Hz
[Ue] Operational rated voltage
12 - 133 V AC 50/60 Hz; 220 - 240 V AC 50/60 Hz; 380 - 415 V AC 50/60 Hz; 440 V AC 50/60 Hz;
Magnetic trip threshold
4 x inch +/-20 %
Breaking capacity
36 kA Icu at 12 - 133 V AC 50/60 Hz complies with EN/IEC 60947-2; 20 kA Icu at 220 - 240 V AC 50/60 Hz complies with EN/IEC 60947-2; 10 kA Icu at 380 - 415 V AC 50/60 Hz complies with EN/IEC 60947-2; 6 kA Icu at 440 V AC 50/60 Hz complies with EN/IEC 60947-2; 10 kA Icu at
Rated switching-off capacity Ics
27 kA 75 % x Icu at 12 - 133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA 75 % x Icu at 220 - 240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 7.5 kA 75 % x Icu at 380 - 415 V AC 50/60 Hz conforming to EN/IEC 60947-2; 4.5 kA 75 % x Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2; 10 kA 100 % x Icu at
Limiting class
3 corresponds to EN/IEC 60898-1
[Ui] Rated insulation voltage
500 V AC 50/60 Hz corresponds to EN/IEC 60947-2
[Uimp] Rated impulse voltage withstand
6 kV corresponds to EN/IEC 60947-2
Control type
Toggle switch
Local signalling
trip indicator
Mounting mode
Plug-on; Removable comb rail installed
Mounting bracket
35 mm DIN rail
Terminal pitch
18 mm between phases
9-mm pitch
6
Height
91 mm
Width
54 mm
Depth
78,5 mm
Product weight
0,375 kg
Colour
White
Mechanical life
20000 cycles
Electrical lifetime
10000 cycles
Connections - terminals
Double terminal (top or bottom), for 1 cable(s), 1…25 mm², solid, copper; Double terminal (top or bottom), for 1 cable(s), 1…16 mm², stranded, copper; Double terminal (top or bottom), for 1 cable(s), 1…16 mm², stranded with ferrule, copper; Double terminal (top or bottom), for 1.0 cable(s), stranded, copper or aluminium, with ring terminal and accessory
Wire stripping length
14 mm for top or bottom connection
[M] tightening torque
2 Nm top or bottom
Earth fault protection
Separate block
Contact position indicator
Contractual warranty
Warranty (in months)
18
Main features
Product series
Acti9
Product name
Acti9 iC60
Product or component type
Miniature circuit breaker (MCB)
Device short name
iC60N
Device application
Distribution
Pole description
3P
Number of protected poles
3
[In] Rated current
10 A
Type of network
DC; AC
Trigger technology
Thermal-magnetic
Cam disc
B
Product compatibility
Vigi iC60 double terminal add-on residual current device 25/63 A
Application category
Category A corresponds to EN/IEC 60947-2
Suitability for insulation
Yes complies with EN/IEC 60898-1; Yes complies with EN/IEC 60947-2
Standards
EN/IEC 60947-2; EN/IEC 60898-1
Mounting
Degree of protection (IP)
IP20 corresponds to IEC 60529; IP40 in modular enclosure (Class II insulation) corresponds to IEC 60529
Pollution degree
3 corresponds to EN/IEC 60947-2
Over voltage category
IV
Drip-proof
2 corresponds to IEC 60068-1
Relative humidity
95 % at 55 °C
Operating ambient temperature
-35…70 °C
Ambient temperature during storage
-40…85 °C
Packaging units
VPE 1 type
PCE
Number of devices per package
1
VPE 1 height
5,5 cm
VPE 1 width
7,5 cm
VPE 1 length
9 cm
Packaging weight (Lbs)
336 g
VPE 2 type
BB1
VPE 2 quantity
4
VPE 2 height
8,6 cm
VPE 2 width
9,7 cm
VPE 2 length
21,8 cm
VPE 2 weight
1,404 kg
VPE 3 type
S03
VPE 3 quantity
44
VPE 3 height
30 cm
VPE 3 width
30 cm
VPE 3 length
40 cm
VPE 3 weight
15,799 kg
The circuit breaker Acti9 iC60N from Schneider Electric is a 3-pole switch with a rated current of 10 A and a B-characteristic, specifically designed for distribution in electrical installations. It belongs to the Acti9 series and is intended for use in networks with alternating and direct voltage. The thermomagnetic tripping technology ensures reliable response to overloads and short circuits, with the magnetic tripping threshold set at 4 times the rated current. The operating voltage covers multiple ranges: 12–133 V AC, 220–240 V AC, 380–415 V AC, and 440 V AC, each at 50/60 Hz. The rated insulation voltage is 500 V AC, enabling safe insulation even at higher voltages.
Applications
The switch is suitable for use in industrial and commercial electrical installations, particularly in distribution enclosures, where safe and reliable power distribution is required. It complies with standards EN/IEC 60947-2 and EN/IEC 60898-1, which define electrical safety and insulation requirements. The usage category is Category A according to EN/IEC 60947-2, indicating application in installations with normal loading and without special requirements for tripping delay. The protection rating IP20 at the terminals protects against contact with foreign objects larger than 12.5 mm and against splashing water, while within the modular housing, a protection rating of IP40 is achieved.
Functions and Equipment in Detail
The switch features a double connection terminal at top and bottom, suitable for solid copper cable (1–25 mm²), flexible copper cable (1–16 mm²), and flexible copper cable with wire end ferrule (1–16 mm²). Connection with ring cable (1.0 mm²) is also possible, with a tightening torque of 2 Nm. The wire stripping length is 14 mm. The snap-action switching ensures wear-free contact switching, increasing service life. The moving insulation cover ensures safe contact separation and prevents unintended contact.
Technology Explained Simply
The thermomagnetic tripping technology combines a thermal and a magnetic tripping element: the thermal part responds to sustained overloads, while the magnetic part trips quickly during sudden short circuits. The B-characteristic means the switch trips at 1.3 times the rated current after approximately 1 hour, and at 5 times the current within 0.1 seconds. The breaking capacity varies depending on the voltage range: 36 kA at 12–133 V AC, 20 kA at 220–240 V AC, 10 kA at 380–415 V AC, and 6 kA at 440 V AC. The rated impulse withstand voltage is 6 kV, ensuring robustness against transient voltage surges.
Compatibility and Accessories
The switch is compatible with various additional modules, including RCD blocks such as the Vigi iC60N/H 3p 63A 300mA Type A or 25A 30mA Type A, providing additional earth fault protection. Additionally, load current release units (iMX+OF), overvoltage release units (iMSU), undervoltage release units (iMN), and remote control units (RCA) can be mounted to extend functionality. Mounting is done on a 35 mm DIN rail, with the mounting bracket operated from the front, enabling tool-free installation and easy removal. The connection pitch is 18 mm between phases, and the switch is designed in a 9 mm pitch format with 6 modules per unit.
Mounting and Installation
Mounting is on a 35 mm DIN rail, with the mounting element operated from the front to enable tool-free installation. The terminals are designed for cables connected from top or bottom, with the double terminal allowing flexible connections. Dimensions are 91 mm (height), 54 mm (width), and 78.5 mm (depth). The color is white, corresponding to RAL 9003. The operating ambient temperature ranges from -35 °C to +70 °C, and storage temperature from -40 °C to +85 °C. Relative humidity is up to 95 % at 55 °C.
Operational Advantages
The switch features a mechanical contact position indicator (VisiSafe), which signals voltage-free condition on the outgoing side when green. The trip indicator (VisiTrip) shows whether tripping occurred due to overload or short circuit. The limiting class 3 according to EN/IEC 60898-1 ensures effective energy limitation during short circuits. The mechanical life is 20000 cycles, and the electrical life is 10000 cycles. Compatibility with various additional modules extends functionality and enables customized solutions for different applications. Mounting on the DIN rail and tool-free removal simplify installation and maintenance in operation.