Further information for Schneider Electric A9F03306 circuit breaker 3p B 6A
Additional features
Network frequency
50/60 Hz
[Ue] Operational rated voltage
12 - 133 V AC 50/60 Hz; 220 - 240 V AC 50/60 Hz; 380 - 415 V AC 50/60 Hz; 440 V AC 50/60 Hz;
Magnetic trip threshold
4 x inch +/-20 %
Breaking capacity
36 kA Icu at 12 - 133 V AC 50/60 Hz complies with EN/IEC 60947-2; 20 kA Icu at 220 - 240 V AC 50/60 Hz complies with EN/IEC 60947-2; 10 kA Icu at 380 - 415 V AC 50/60 Hz complies with EN/IEC 60947-2; 6 kA Icu at 440 V AC 50/60 Hz complies with EN/IEC 60947-2; 10 kA Icu at
Rated switching-off capacity Ics
27 kA 75 % x Icu at 12 - 133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA 75 % x Icu at 220 - 240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 7.5 kA 75 % x Icu at 380 - 415 V AC 50/60 Hz conforming to EN/IEC 60947-2; 4.5 kA 75 % x Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2; 10 kA 100 % x Icu at
Limiting class
3 corresponds to EN/IEC 60898-1
[Ui] Rated insulation voltage
500 V AC 50/60 Hz corresponds to EN/IEC 60947-2
[Uimp] Rated impulse voltage withstand
6 kV corresponds to EN/IEC 60947-2
Control type
Toggle switch
Local signalling
trip indicator
Mounting mode
Plug-on; Removable comb rail installed
Mounting bracket
35 mm DIN rail
Terminal pitch
18 mm between phases
9-mm pitch
6
Height
91 mm
Width
54 mm
Depth
78,5 mm
Product weight
0,375 kg
Colour
White
Mechanical life
20000 cycles
Electrical lifetime
10000 cycles
Connections - terminals
Double terminal (top or bottom), for 1 cable(s), 1…25 mm², solid, copper; Double terminal (top or bottom), for 1 cable(s), 1…16 mm², stranded, copper; Double terminal (top or bottom), for 1 cable(s), 1…16 mm², stranded with ferrule, copper; Double terminal (top or bottom), for 1.0 cable(s), stranded, copper or aluminium, with ring terminal and accessory
Wire stripping length
14 mm for top or bottom connection
[M] tightening torque
2 Nm top or bottom
Earth fault protection
Separate block
Contact position indicator
Contractual warranty
Warranty (in months)
18
Main features
Product series
Acti9
Product name
Acti9 iC60
Product or component type
Miniature circuit breaker (MCB)
Device short name
iC60N
Device application
Distribution
Pole description
3P
Number of protected poles
3
[In] Rated current
6 A
Type of network
DC; AC
Trigger technology
Thermal-magnetic
Cam disc
B
Product compatibility
Vigi iC60 double terminal add-on residual current device 25/63 A
Application category
Category A corresponds to EN/IEC 60947-2
Suitability for insulation
Yes complies with EN/IEC 60898-1; Yes complies with EN/IEC 60947-2
Standards
EN/IEC 60947-2; EN/IEC 60898-1
Mounting
Degree of protection (IP)
IP20 corresponds to IEC 60529; IP40 in modular enclosure (Class II insulation) corresponds to IEC 60529
Pollution degree
3 corresponds to EN/IEC 60947-2
Over voltage category
IV
Drip-proof
2 corresponds to IEC 60068-1
Relative humidity
95 % at 55 °C
Operating ambient temperature
-35…70 °C
Ambient temperature during storage
-40…85 °C
Packaging units
VPE 1 type
PCE
Number of devices per package
1
VPE 1 height
5,5 cm
VPE 1 width
7,5 cm
VPE 1 length
9 cm
Packaging weight (Lbs)
341 g
VPE 2 type
BB1
VPE 2 quantity
4
VPE 2 height
8,5 cm
VPE 2 width
9,8 cm
VPE 2 length
22 cm
VPE 2 weight
1,41 kg
VPE 3 type
S03
VPE 3 quantity
44
VPE 3 height
30 cm
VPE 3 width
30 cm
VPE 3 length
40 cm
VPE 3 weight
16,008 kg
The circuit breaker Acti9 iC60N from Schneider Electric is a 3-pole switch with a rated current of 6 A and a B characteristic, specifically designed for distribution in electrical installations. It belongs to the Acti9 series and is used in the iC60 product line. The tripping technology is based on thermal-magnetic principle, ensuring reliable detection and disconnection of overloads and short circuits. The magnetic tripping threshold is at 4 times the rated current, with a tolerance of ±20 %, enabling precise response to sudden current surges. The switch is designed for operating voltages of 380–415 V AC, with a rated insulation voltage of 500 V AC. The rated impulse withstand voltage is 6 kV, ensuring high safety against transient voltage spikes.
Applications
The switch is designed for use in distribution systems, particularly in industrial and commercial installations where reliable current protection is required. It is suitable for networks with a frequency of 50/60 Hz and complies with standards EN/IEC 60947-2 and EN/IEC 60898-1. The usage category is Category A, allowing application in installations with normal load characteristics. The protection rating IP20 provides protection against finger contact and solid foreign objects, while in a modular housing, a protection rating of IP40 is achieved. Pollution degree class 3 and overvoltage category IV indicate application in environments with increased pollution risk and transient voltage surges.
Functions and Equipment in Detail
The switch features a double connection terminal at top and bottom, suitable for both rigid cables (1–25 mm² copper) and flexible cables (1–16 mm² copper, with or without wire end ferrule). The cable stripping length is 14 mm, and the required tightening torque is 2 Nm. The snap-action switching ensures wear-free contact switching, increasing service life. The moving insulation cover ensures safe access to the terminals and prevents accidental contact. The contact position indicator (VisiSafe) shows green when the outgoing side is de-energized, providing additional safety during maintenance work. The trip indicator (VisiTrip) mechanically signals on the front side when the switch has tripped due to overload or short circuit.
Technology Explained Simply
The thermal-magnetic tripping technology combines a thermal and a magnetic tripping element. The thermal part reacts to sustained overloads by deforming a bimetal strip and disconnecting the contact. The magnetic part reacts immediately to high current surges such as short circuits by actuating the tripping mechanism via an electromagnet. The B characteristic means that the switch trips at approximately 1.3 times the rated current after about 1 hour, and at 5 times the rated current within 0.1 seconds. The limiting class 3 according to EN/IEC 60898-1 indicates that the switch limits energy release during short-circuit currents up to 10 kA (at 380–415 V AC). The breaking capacity is 10 kA Icu at 380–415 V AC, ensuring high safety with high short-circuit currents.
Compatibility and Accessories
The switch is compatible with the FI module Vigi iC60N/H 3p 25A 30mA Type A (part number A9W21325) and can be combined with FI protection switches from the Acti9 iID series. Various auxiliary modules can be mounted, including under-voltage release (e.g. A9A26969), load current release (e.g. A9A26946), auxiliary switches (e.g. A9A26915), remote actuators (e.g. A9C70124), and rotary actuators (e.g. A9A27006). Mounting is done on a 35 mm DIN rail, with the mounting bracket operated from the front, enabling tool-free mounting and easy removal. The connection pitch is 18 mm between phases, and the switch occupies 6 units in the 9 mm pitch.
Mounting and Installation
Mounting is done on a 35 mm DIN rail, with the mounting element operated from the front. This enables tool-free mounting and facilitates removal of the device, especially when phase rails are installed. Dimensions are 91 mm (height), 54 mm (width), and 78.5 mm (depth). The product weight is 0.375 kg. The ambient temperature during operation ranges from -35 °C to +70 °C, and during storage from -40 °C to +85 °C. The relative humidity is up to 95 % at 55 °C. Drip-proofing is specified as class 2 according to IEC 60068-1.
Operational Advantages
The switch offers high reliability through thermal-magnetic tripping technology and snap-action switching. The mechanical service life is 20,000 cycles, and the electrical service life is 10,000 cycles. The front-side indication of switching position and tripping facilitates maintenance and diagnosis. Compatibility with various accessory modules extends functionality without impairing basic function. The color is white (RAL 9003), enabling uniform visual design in distribution enclosures. Compliance with EN/IEC 60947-2 and EN/IEC 60898-1 standards, as well as VDE certification, guarantees adherence to European safety standards.