Further information for Schneider Electric A9F03125 Circuit Breaker 1p B 25A
Additional features
Network frequency
50/60 Hz
[Ue] Operational rated voltage
12 - 60 V AC 50/60 Hz; 100 - 133 V AC 50/60 Hz; 220 - 240 V AC 50/60 Hz; 12 - 60 V DC; 60 - 72 V DC
Magnetic trip threshold
4 x inch +/-20 %
Breaking capacity
36 kA Icu at 12 - 60 V AC 50/60 Hz complies with EN/IEC 60947-2; 20 kA Icu at 100 - 133 V AC 50/60 Hz complies with EN/IEC 60947-2; 10 kA Icu at 220 - 240 V AC 50/60 Hz complies with EN/IEC 60947-2; 15 kA Icu at 12 - 60 V DC complies with EN/IEC 60947-2; 10 kA Icu at 60 - 72 V DC complies with EN/IEC 60947-2; 6000 A Icn at 230 V AC 50/60 Hz complies with EN/IEC 60898-1
Rated switching-off capacity Ics
27 kA 75 % x Icu at 12 - 60 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA 75 % x Icu at 100 - 133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 7.5 kA 75 % x Icu at 220 - 240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA 100 % x Icu at 12 - 60 V DC conforming to EN/IEC 60947-2; 10 kA 100 % x Icu at 60 - 72 V DC conforming to EN/IEC 60947-2
Limiting class
3 corresponds to EN/IEC 60898-1
[Ui] Rated insulation voltage
500 V AC 50/60 Hz corresponds to EN/IEC 60947-2
[Uimp] Rated impulse voltage withstand
6 kV corresponds to EN/IEC 60947-2
Control type
Toggle switch
Local signalling
trip indicator
Mounting mode
Plug-on; Removable comb rail installed
Mounting bracket
35 mm DIN rail
Terminal pitch
18 mm between devices
9-mm pitch
2
Height
91 mm
Width
18 mm
Depth
78,5 mm
Product weight
0,125 kg
Colour
White
Mechanical life
20000 cycles
Electrical lifetime
10000 cycles
Connections - terminals
Double terminal (top or bottom), for 1 cable(s), 1…25 mm², solid, copper; Double terminal (top or bottom), for 1 cable(s), 1…16 mm², stranded, copper; Double terminal (top or bottom), for 1 cable(s), 1…16 mm², stranded with ferrule, copper; Double terminal (top or bottom), for 1.0 cable(s), stranded, copper or aluminium, with ring terminal and accessory
Wire stripping length
14 mm for top or bottom connection
[M] tightening torque
2 Nm top or bottom
Earth fault protection
None
Contact position indicator
Contractual warranty
Warranty (in months)
18
Main features
Product series
Acti9
Product name
Acti9 iC60
Product or component type
Miniature circuit breaker (MCB)
Device short name
iC60N
Device application
Distribution
Pole description
1P
Number of protected poles
1
[In] Rated current
25 A
Type of network
DC; AC
Trigger technology
Thermal-magnetic
Cam disc
B
Application category
Category A corresponds to EN/IEC 60947-2
Suitability for insulation
Yes complies with EN/IEC 60898-1; Yes complies with EN/IEC 60947-2
Standards
EN/IEC 60947-2; EN/IEC 60898-1
Mounting
Degree of protection (IP)
IP20 corresponds to IEC 60529; IP40 in modular enclosure (Class II insulation) corresponds to IEC 60529
Pollution degree
3 corresponds to EN/IEC 60947-2
Over voltage category
IV
Drip-proof
2 corresponds to IEC 60068-1
Relative humidity
95 % at 55 °C
Operating ambient temperature
-35…70 °C
Ambient temperature during storage
-40…85 °C
Packaging units
VPE 1 type
PCE
Number of devices per package
1
VPE 1 height
1,700 cm
VPE 1 width
7,400 cm
VPE 1 length
9,100 cm
Packaging weight (Lbs)
121,000 g
VPE 2 type
BB1
VPE 2 quantity
12
VPE 2 height
8,500 cm
VPE 2 width
9,800 cm
VPE 2 length
22,000 cm
VPE 2 weight
1,507 kg
VPE 3 type
S03
VPE 3 quantity
132
VPE 3 height
30 cm
VPE 3 width
30 cm
VPE 3 length
40 cm
VPE 3 weight
17,064 kg
The circuit breaker A9F03125 from the Acti9 series by Schneider Electric is a 1-pole switch with a rated current of 25 A and B characteristic. It is designed for distribution and protection of electrical circuits against overload and short circuit in installations with alternating and direct voltage. The device is designed for operating voltages of 220–240 V AC 50/60 Hz and complies with standards EN/IEC 60947-2 and EN/IEC 60898-1. The tripping technology is thermomagnetic, with the magnetic tripping threshold set at 4 times the rated current. The protection rating is IP20 at the terminals and IP40 in the modular housing, enabling installation in indoor environments with limited access to moving parts. The insulation voltage is 500 V AC, and the impulse voltage withstand is 6 kV. The device is designed for an ambient temperature of -35 °C to 70 °C during operation and -40 °C to 85 °C during storage.
Applications
The switch is designed for use in electrical distribution systems, particularly in residential and commercial buildings as well as industrial installations. It is suitable for protection functions in circuits with an operating voltage of 220–240 V AC. The usage category A according to EN/IEC 60947-2 allows use in installations not intended for the protection of electrical devices. The limitation class 3 according to EN/IEC 60898-1 indicates the ability to limit short-circuit current.
Functions and Equipment in Detail
The device features double terminals at the top and bottom, suitable for connecting solid copper conductors from 1 to 25 mm² and flexible copper conductors from 1 to 16 mm². Connections can also be made with flexible conductors up to 16 mm² with wire end ferrules, or copper or aluminium conductors with ring terminals. The wire stripping length is 14 mm, and the tightening torque is 2 Nm. The contact position indicator (VisiSafe) shows green when the outgoing side is de-energized. The tripping indicator (VisiTrip) mechanically signals tripping due to overload or short circuit. Mounting is tool-free on a 35 mm DIN rail, with the mounting element operated from the front. The connection pitch is 18 mm, height 91 mm, width 18 mm, and depth 78.5 mm. The device has a mechanical life of 20,000 cycles and an electrical life of 10,000 cycles.
Technology Explained Simply
The thermomagnetic tripping technology combines a thermal and a magnetic tripping mechanism. The thermal part responds to sustained overloads, while the magnetic part protects against sudden short circuits. The B characteristic means that the switch trips after approximately 1 second at 3 times the rated current and within 0.1 seconds at 5 times the rated current. The breaking capacity is 10 kA at 220–240 V AC, ensuring the ability to interrupt short-circuit currents in typical distribution systems. The insulation cover moves with the contacts to ensure safe disconnection.
Compatibility and Accessories
The switch is compatible with RCD circuit breakers from the Acti 9 iID series and the Vigi iC60 RCD module. Additionally, auxiliary modules such as current release, undervoltage release, auxiliary contacts, and reclosing devices can be used. Suitable accessories include, for example, the undervoltage release A9A26960, auxiliary contact A9A26919, phase bar modules such as A9XAH657 and A9XPH157, as well as filler and spacing pieces such as A9A27062. Combining the switch with these modules extends functionality for specific applications.
Mounting and Installation
Mounting is done on a 35 mm DIN rail, with the device secured tool-free from the front. Removal is also tool-free, especially when using a phase bar. Connections can be made at the top and bottom, enabling flexible integration into distribution enclosures. The device colour is white (RAL 9003). Pollution degree class 3 and overvoltage category IV are suitable for use in electrical installations with increased pollution risk and near voltage sources.
Advantages in Operation
Tool-free mounting and removal simplify installation and maintenance. The visual indicators (VisiSafe and VisiTrip) allow for quick status checks. The double terminal offers flexibility in wiring. The high service life and reliability of the thermomagnetic tripping technology ensure stable operation. Compatibility with additional modules extends functionality without requiring additional switchgear cabinets.
The device is designed for use in electrical distribution systems requiring safe and reliable power supply. Compliance with standards and VDE certification guarantee adherence to safety requirements.