Further information for Schneider Electric A9F03110 LS Switch 1p 10A
Additional features
Network frequency
50/60 Hz
[Ue] Operational rated voltage
12 - 60 V AC 50/60 Hz; 100 - 133 V AC 50/60 Hz; 220 - 240 V AC 50/60 Hz; 12 - 60 V DC; 60 - 72 V DC
Magnetic trip threshold
4 x inch +/-20 %
Breaking capacity
36 kA Icu at 12 - 60 V AC 50/60 Hz complies with EN/IEC 60947-2; 20 kA Icu at 100 - 133 V AC 50/60 Hz complies with EN/IEC 60947-2; 10 kA Icu at 220 - 240 V AC 50/60 Hz complies with EN/IEC 60947-2; 15 kA Icu at 12 - 60 V DC complies with EN/IEC 60947-2; 10 kA Icu at 60 - 72 V DC complies with EN/IEC 60947-2; 6000 A Icn at 230 V AC 50/60 Hz complies with EN/IEC 60898-1
Rated switching-off capacity Ics
27 kA 75 % x Icu at 12 - 60 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA 75 % x Icu at 100 - 133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 7.5 kA 75 % x Icu at 220 - 240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA 100 % x Icu at 12 - 60 V DC conforming to EN/IEC 60947-2; 10 kA 100 % x Icu at 60 - 72 V DC conforming to EN/IEC 60947-2
Limiting class
3 corresponds to EN/IEC 60898-1
[Ui] Rated insulation voltage
500 V AC 50/60 Hz corresponds to EN/IEC 60947-2
[Uimp] Rated impulse voltage withstand
6 kV corresponds to EN/IEC 60947-2
Control type
Toggle switch
Local signalling
trip indicator
Mounting mode
Plug-on; Removable comb rail installed
Mounting bracket
35 mm DIN rail
Terminal pitch
18 mm between devices
9-mm pitch
2
Height
91 mm
Width
18 mm
Depth
78,5 mm
Product weight
0,125 kg
Colour
White
Mechanical life
20000 cycles
Electrical lifetime
10000 cycles
Connections - terminals
Double terminal (top or bottom), for 1 cable(s), 1…25 mm², solid, copper; Double terminal (top or bottom), for 1 cable(s), 1…16 mm², stranded, copper; Double terminal (top or bottom), for 1 cable(s), 1…16 mm², stranded with ferrule, copper; Double terminal (top or bottom), for 1.0 cable(s), stranded, copper or aluminium, with ring terminal and accessory
Wire stripping length
14 mm for top or bottom connection
[M] tightening torque
2 Nm top or bottom
Earth fault protection
None
Contact position indicator
Contractual warranty
Warranty (in months)
18
Main features
Product series
Acti9
Product name
Acti9 iC60
Product or component type
Miniature circuit breaker (MCB)
Device short name
iC60N
Device application
Distribution
Pole description
1P
Number of protected poles
1
[In] Rated current
10 A
Type of network
AC; DC
Trigger technology
Thermal-magnetic
Cam disc
B
Application category
Category A corresponds to EN/IEC 60947-2
Suitability for insulation
Yes complies with EN/IEC 60898-1; Yes complies with EN/IEC 60947-2
Standards
EN/IEC 60947-2; EN/IEC 60898-1
Mounting
Degree of protection (IP)
IP20 corresponds to IEC 60529; IP40 in modular enclosure (Class II insulation) corresponds to IEC 60529
Pollution degree
3 corresponds to EN/IEC 60947-2
Over voltage category
IV
Drip-proof
2 corresponds to IEC 60068-1
Relative humidity
95 % at 55 °C
Operating ambient temperature
-35…70 °C
Ambient temperature during storage
-40…85 °C
Packaging units
VPE 1 type
PCE
Number of devices per package
1
VPE 1 height
7,500 cm
VPE 1 width
1,800 cm
VPE 1 length
8,700 cm
Packaging weight (Lbs)
112,000 g
VPE 2 type
BB1
VPE 2 quantity
12
VPE 2 height
8,500 cm
VPE 2 width
9,800 cm
VPE 2 length
23,000 cm
VPE 2 weight
1,466 kg
VPE 3 type
S03
VPE 3 quantity
132
VPE 3 height
30,000 cm
VPE 3 width
30,000 cm
VPE 3 length
40,000 cm
VPE 3 weight
16,800 kg
The circuit breaker Acti9 iC60N from Schneider Electric is a 1-pole switch with a rated current of 10 A and a B characteristic, specifically designed for distribution in electrical installations. It belongs to the Acti9 series and is designed for use in networks with alternating and direct voltage. The tripping technology is based on a thermal-magnetic principle, ensuring reliable disconnection in case of overloads and short circuits. The magnetic tripping threshold is at 4 times the rated current, enabling fast response to high current surges. The operating voltage covers multiple ranges: 12–60 V AC, 100–133 V AC, 220–240 V AC, as well as 12–60 V DC and 60–72 V DC, allowing flexible use in various application scenarios.
Applications
The switch is designed for use in distribution systems, particularly in residential and commercial buildings, where safe power distribution and protection functions are required. It complies with standards EN/IEC 60947-2 and EN/IEC 60898-1, making it suitable for use in electrical installations according to current safety standards. The usage category corresponds to Category A, which specifies application in switchgear with normal loading and low short-circuit risk. The insulation strength is 500 V AC, ensuring high safety for electrical isolation.
Functions and Equipment in Detail
The switch features a front-mounted contact position indicator (VisiSafe), which signals voltage-free condition on the outgoing side when green. Additionally, a trip indicator (VisiTrip) is integrated, visually indicating tripping due to overload or short circuit. Operation is performed via a toggle switch, which can be operated without tools. Mounting is done on a 35 mm DIN rail, with the mounting element accessible from the front, enabling easy installation and maintenance. The terminals are arranged as double terminals at the top and bottom, allowing flexible wiring. The terminals are designed for cable cross-sections of 1 to 25 mm² (solid, copper), 1 to 16 mm² (flexible, copper), and 1 to 16 mm² (flexible with wire end ferrule, copper). Connections for flexible copper or aluminium conductors are possible using ring terminals and accessories. The wire stripping length is 14 mm, and the required tightening torque is 2 Nm.
Technology Explained Simply
The thermal-magnetic tripping technology combines two principles: during an overload, a bimetal strip heats up and trips the switch after a certain time. In case of a short circuit, the magnetic component reacts immediately to quickly disconnect the high current surge. The snap-action switching ensures wear-free switching of contacts, increasing the service life. The moving insulation cover protects the terminals and prevents unintended contact. The limiting class 3 according to EN/IEC 60898-1 indicates that the switch allows limited energy release during short circuits, enhancing safety. The impulse voltage withstand is 6 kV, ensuring high robustness against transient voltage spikes.
Compatibility and Accessories
The switch is compatible with residual current circuit breakers from the Acti9 iID series as well as with the FI module Vigi iC60. Additionally, modular auxiliary units such as load switches (iMX), under-voltage release (iMNx), over-voltage release (iMSU), or auxiliary contacts (iOF/SD+OF, iSD+OF) can be added to meet specific switching function requirements. Mounting is on a 35 mm DIN rail, with the device featuring a connection pitch of 18 mm and a 9 mm pitch of 2. Dimensions are 91 mm height, 18 mm width, and 78.5 mm depth. The color is white (RAL 9003).
Mounting and Installation
Mounting is tool-free on a 35 mm DIN rail. The mounting element is accessible from the front, enabling easy installation and removal of the device. Terminals are arranged at the top and bottom, allowing flexible wiring. The mechanical life is 20,000 cycles, the electrical life is 10,000 cycles. The operating temperature ranges from -35 °C to +70 °C, and the storage temperature ranges from -40 °C to +85 °C. The relative humidity is up to 95 % at 55 °C. The protection rating is IP20 at the terminals and IP40 in the modular housing (insulation class II). The overvoltage category is IV, and the drip-proof rating is 2.
Advantages in Operation
The switch offers high reliability through thermal-magnetic tripping technology and snap-action switching. The front-mounted indicators (VisiSafe and VisiTrip) allow quick visual inspection of the operating status. Tool-free mounting and easy removal simplify installation and maintenance. Compatibility with various accessory modules extends functionality for specific applications. Compliance with standards EN/IEC 60947-2 and EN/IEC 60898-1, as well as VDE certification, guarantees the safety and quality of the device.