Further information for Schneider Electric A9F03106 Circuit Breaker 1p B 6A
Additional features
Network frequency
50/60 Hz
[Ue] Operational rated voltage
12 - 60 V AC 50/60 Hz; 100 - 133 V AC 50/60 Hz; 220 - 240 V AC 50/60 Hz; 12 - 60 V DC; 60 - 72 V DC
Magnetic trip threshold
4 x inch +/-20 %
Breaking capacity
36 kA Icu at 12 - 60 V AC 50/60 Hz complies with EN/IEC 60947-2; 20 kA Icu at 100 - 133 V AC 50/60 Hz complies with EN/IEC 60947-2; 10 kA Icu at 220 - 240 V AC 50/60 Hz complies with EN/IEC 60947-2; 15 kA Icu at 12 - 60 V DC complies with EN/IEC 60947-2; 10 kA Icu at 60 - 72 V DC complies with EN/IEC 60947-2; 6000 A Icn at 230 V AC 50/60 Hz complies with EN/IEC 60898-1
Rated switching-off capacity Ics
27 kA 75 % x Icu at 12 - 60 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA 75 % x Icu at 100 - 133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 7.5 kA 75 % x Icu at 220 - 240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA 100 % x Icu at 12 - 60 V DC conforming to EN/IEC 60947-2; 10 kA 100 % x Icu at 60 - 72 V DC conforming to EN/IEC 60947-2
Limiting class
3 corresponds to EN/IEC 60898-1
[Ui] Rated insulation voltage
500 V AC 50/60 Hz corresponds to EN/IEC 60947-2
[Uimp] Rated impulse voltage withstand
6 kV corresponds to EN/IEC 60947-2
Control type
Toggle switch
Local signalling
trip indicator
Mounting mode
Plug-on; Removable comb rail installed
Mounting bracket
35 mm DIN rail
Terminal pitch
18 mm between devices
9-mm pitch
2
Height
91 mm
Width
18 mm
Depth
78,5 mm
Product weight
0,125 kg
Colour
White
Mechanical life
20000 cycles
Electrical lifetime
10000 cycles
Connections - terminals
Double terminal (top or bottom), for 1 cable(s), 1…25 mm², solid, copper; Double terminal (top or bottom), for 1 cable(s), 1…16 mm², stranded, copper; Double terminal (top or bottom), for 1 cable(s), 1…16 mm², stranded with ferrule, copper; Double terminal (top or bottom), for 1.0 cable(s), stranded, copper or aluminium, with ring terminal and accessory
Wire stripping length
14 mm for top or bottom connection
[M] tightening torque
2 Nm top or bottom
Earth fault protection
None
Contact position indicator
Contractual warranty
Warranty (in months)
18
Main features
Product series
Acti9
Product name
Acti9 iC60
Product or component type
Miniature circuit breaker (MCB)
Device short name
iC60N
Device application
Distribution
Pole description
1P
Number of protected poles
1
[In] Rated current
6 A
Type of network
AC; DC
Trigger technology
Thermal-magnetic
Cam disc
B
Application category
Category A corresponds to EN/IEC 60947-2
Suitability for insulation
Yes complies with EN/IEC 60898-1; Yes complies with EN/IEC 60947-2
Standards
EN/IEC 60947-2; EN/IEC 60898-1
Mounting
Degree of protection (IP)
IP20 corresponds to IEC 60529; IP40 in modular enclosure (Class II insulation) corresponds to IEC 60529
Pollution degree
3 corresponds to EN/IEC 60947-2
Over voltage category
IV
Drip-proof
2 corresponds to IEC 60068-1
Relative humidity
95 % at 55 °C
Operating ambient temperature
-35…70 °C
Ambient temperature during storage
-40…85 °C
Packaging units
VPE 1 type
PCE
Number of devices per package
1
VPE 1 height
1,800 cm
VPE 1 width
7,300 cm
VPE 1 length
9,100 cm
Packaging weight (Lbs)
113,000 g
VPE 2 type
BB1
VPE 2 quantity
12
VPE 2 height
8,500 cm
VPE 2 width
9,800 cm
VPE 2 length
22,000 cm
VPE 2 weight
1,416 kg
VPE 3 type
S03
VPE 3 quantity
132
VPE 3 height
30,000 cm
VPE 3 width
30,000 cm
VPE 3 length
40,000 cm
VPE 3 weight
16,150 kg
The circuit breaker Acti9 iC60N from Schneider Electric is a 1-pole switch with a rated current of 6 A, designed for use in distribution systems. It belongs to the Acti9 series and features a thermomagnetic tripping technology that responds to both overload and short-circuit conditions. The B characteristic ensures a balanced response to load surges, with the magnetic tripping threshold set at 4 times the rated current. The device is designed for operating voltages of 220–240 V AC 50/60 Hz and complies with standards EN/IEC 60947-2 and EN/IEC 60898-1, with usage category A according to EN/IEC 60947-2. The rated insulation voltage is 500 V AC, and the rated impulse withstand voltage is 6 kV. The breaking capacity is 10 kA Icu for 220–240 V AC 50/60 Hz and 6000 A Icn at 230 V AC 50/60 Hz, achieving limitation class 3 according to EN/IEC 60898-1.
Applications
The switch is designed for use in electrical distribution systems, particularly in residential and commercial buildings as well as industrial facilities, where safe and reliable circuit protection is required. It is suitable for protecting consumers and circuits with a nominal current up to 6 A. The operating temperature range is from -35 °C to 70 °C, and the storage temperature range is from -40 °C to 85 °C, making it usable even under extreme environmental conditions. The relative humidity can reach up to 95 % at 55 °C. The protection rating IP20 is intended for use in enclosed switchgear, while IP40 is achieved in modular enclosures (insulation class II).
Functions and Equipment in Detail
The switch features double terminals at the top and bottom, suitable for solid copper cable (1–25 mm²) as well as flexible copper conductors (1–16 mm²). For flexible conductors with wire end ferrules, the permissible cross-section is 1–16 mm². A combination with flexible copper or aluminium conductors (1.0 mm²) is also possible when using ring terminals and accessories. The wire stripping length is 14 mm, and the required tightening torque is 2 Nm. The contacts are equipped with a snap-action switching mechanism, ensuring wear-resistant switching. A moving insulation cover provides additional safety during installation and maintenance.
Technology Explained Simply
The thermomagnetic tripping technology combines a thermal and a magnetic tripping element. The thermal part responds to sustained overloads, while the magnetic part protects against sudden short circuits. The B characteristic means that the switch trips after approximately 1 hour at 1.3 times the rated current, after about 10 seconds at 2 times the current, and immediately at 4 times the current. The mechanical life is 20,000 cycles, and the electrical life is 10,000 cycles. The contact position indicator (VisiSafe) shows green when the outgoing side is de-energized, and the tripping indicator (VisiTrip) mechanically signals tripping due to overload or short circuit.
Compatibility and Accessories
The switch can be mounted on a 35 mm DIN rail and can be installed tool-free via the front-accessible mounting element. The connection pitch is 18 mm, and the device is designed in 9 mm module increments (2 modules). It is compatible with RCD circuit breakers from the Acti 9 iID series as well as with the Vigi iC60 RCD module. Additional auxiliary modules such as current-operated release, under-voltage release, over-voltage release, or auxiliary switches can also be connected. Suitable accessories include filler and spacing pieces, phase bar modules, rotary drives, under-voltage releases, and terminal covers.
Mounting and Installation
Mounting is done on a 35 mm DIN rail, with the device being secured tool-free via the front-operated mounting bracket. The device can be easily removed even with an installed phase bar, as the mounting element is accessible from the front. The terminals are designed for top or bottom connections, allowing flexible installation in enclosures. The device colour corresponds to RAL 9003 (white).
Advantages in Operation
The switch offers high reliability through thermomagnetic tripping technology and snap-action switching. The front-mounted indicators (VisiSafe and VisiTrip) simplify maintenance and diagnostics. Tool-free mounting and easy removal increase efficiency during installation and maintenance. Compatibility with additional modules extends the functionality of the switch in complex distribution systems. Compliance with standards EN/IEC 60947-2 and EN/IEC 60898-1, as well as VDE certification, guarantees the safety and quality of the product.