Further information for Schneider Electric A9DXG3613 residual current circuit breaker 1P+N 13 A
Additional features
Device position in system
Outlet; group input
Earthing system
TN-S; TT; TN-C-S; TN; IT
[Ue] Operational rated voltage
230 V AC
Threshold for magnetic actuation
3 - 5 x In
Earth fault trip technology
Voltage-independent
Earth fault protection time delay
Instantaneous
Earth fault protection class
Type A
Breaking capacity
6000 A Icn at 230 V AC 50 Hz corresponds to EN/IEC 61009-2-1; 10 kA Icu at 230 V AC 50 Hz only referring to short circuit test corresponds to EN/IEC 60947-2
Rated switching-off capacity Ics
6000 A 100 % x Icn at 230 V AC; 10 kA 100 % x Icu at 230 V AC 50 Hz conforming to EN/IEC 60947-2 (only referring to short circuit test)
Rated breaking force and rated power
Idm 6000 A at 230 V AC 50 Hz corresponds to EN/IEC 61009-2-1
Limiting class
3 corresponds to EN/IEC 61009-2-1
[Ui] Rated insulation voltage
440 V AC 50 Hz
[Uimp] Rated impulse voltage withstand
4 kV
Inrush current
250 A
Control type
Toggle switch
Local signalling
ON/OFF indication; fault indication
Mounting mode
Plug-in
Mounting bracket
DIN rail
Compatibility of comb rails and distribution blocks
top or bottom: pin
Terminal pitch
9 mm between phase and neutral
9-mm pitch
2
Height
96 mm
Width
18 mm
Depth
73 mm
Product weight
125 g
Colour
White (RAL 9003)
Mechanical life
10000 cycles
Electrical lifetime
10000 cycles
Description of locking options
Padlock; Sealing possible
Connections - terminals
Tunnel terminals top or bottom 1…16 mm² solid; tunnel terminals top or bottom 1…10 mm² stranded; tunnel terminals top or bottom 1…10 mm² stranded with ferrule
Wire stripping length
12 mm for top or bottom connection
[M] tightening torque
2 Nm top or bottom
Earth fault protection
Integrated
Contact position indicator
Contractual warranty
Warranty (in months)
18
Main features
Product series
Acti9
Product name
Acti9 iCVm40
Product or component type
Residual current circuit breaker with overcurrent protection (FI/LS)
Device short name
iCVm40N
Device application
Distribution
Pole description
1P + N
Number of protected poles
1
Neutral position
Left
[In] Rated current
13 A at 30 °C
Type of network
AC
Network frequency
50 Hz
Trigger technology
Thermal-magnetic
Cam disc
B
Earth fault sensitivity
30 mA
Conformity marking
VDE; S+
Suitability for insulation
Mounting
Standards
EN/IEC 61009-1; EN/IEC 61009-2-1
Degree of protection (IP)
IP20; IP40 (modular housing)
Degree of protection (IK)
IK05
Pollution degree
2
Over voltage category
III
Electromagnetic compatibility
8/20 µs impulse resistance, 250 A corresponds to EN/IEC 61009-2-1
Drip-proof
2 corresponds to IEC 60068-1
Relative humidity
95 % at 55 °C
Operating altitude
2.000 m
Operating ambient temperature
-25…60 °C
Ambient temperature during storage
-40…80 °C
Packaging units
VPE 1 type
PCE
Number of devices per package
1
VPE 1 height
2,400 cm
VPE 1 width
11,300 cm
VPE 1 length
8,400 cm
Packaging weight (Lbs)
150,000 g
VPE 2 type
S02
VPE 2 quantity
45
VPE 2 height
15,000 cm
VPE 2 width
30,000 cm
VPE 2 length
40,000 cm
VPE 2 weight
6,854 kg
VPE 3 type
P12
VPE 3 quantity
720
VPE 3 height
45,000 cm
VPE 3 width
80,000 cm
VPE 3 length
120,000 cm
VPE 3 weight
116,160 kg
Optimaler Fehlerstromschutz für Personen und Anlagen mit unserem neuen kompakten Acti9 Typ A FI-LS 1P+N 13A von Schneider Electric. Eingesetzt wird dieser kompakte FILS 1TE (18mm) bei einer Netzfrequenz von 50Hz und einer Betriebsspannung von 230V AC. B, mit einem Kurzschlussvermögen von 6kA bei 230V AC nach EN/IEC 61009-2-1 Standard. Nennfehlerstrom 30 mA, Typ A, Löst bei AC-Fehlerströmen aus und geht nicht in die Sättigung bis 6mA DC-Fehlerströme. Einsetzbar bei einer Betriebstemperatur von -25°C bis 60°C. VisiTrip-Anzeige, die Fehlerauslösung wird von einer roten, mechanischen Anzeige an der Vorderseite angezeigt. VisiSafe-Anzeige Positive Verbindungsanzeige, Trennereigenschaften gemäß IEC/EN 60947-3. Die grüne Anzeige 'OFF' wird nur freigegeben, wenn die Kontakte vollständig geöffnet sind, so wird eine gefahrlose Wartung gewährleistet'. Die Prüftaste ist mit einem 'T' markiert. Beim drücken dieser Taste kann die Funktionalität des Schutzgerätes getestet werden. Die Acti9 FILS Serie bietet den bestmöglichen Schutz im Wohnbau, Zweckbau und Industrie.