Further information for Schneider Electric A9D87432 FI/LS switch iC60N 4P
Complementary
Device location in system
Outgoer
[Ue] rated operational voltage
380...415 V AC 50 Hz
Magnetic tripping limit
3...5 x In
Residual current tripping technology
Voltage independent
Earth-leakage protection time delay
Instantaneous
Earth-leakage protection class
Type A
Breaking capacity
6000 A Icn at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1; 6 kA Icu at 380...415 V AC 50 Hz conforming to EN/IEC 60947-2
[Ics] rated service breaking capacity
6000 A 100 % x Icn at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1; 6 kA 100 % x Icu at 380...415 V AC 50 Hz conforming to EN/IEC 60947-2
Rated breaking and making capacity
Idm 6000 A at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1
Limitation class
1 conforming to EN/IEC 61009-2-1
[Ui] rated insulation voltage
500 V AC 50 Hz
[Uimp] rated impulse withstand voltage
4 kV
Surge current
250 A
Control type
Toggle
Local signalling
ON, OFF, fault trip
Mounting mode
Clip-on
Mounting support
DIN rail
Comb busbar and distribution block compatibility
Top or bottom: YES; Bottom: biconnect
Connection pitch
9 mm between poles
9 mm pitches
8
Height
86 mm
Width
72 mm
Depth
78 mm
Net weight
423 g
Colour
White
Mechanical durability
20000 cycles
Electrical durability
10000 cycles
Connections - terminals
Tunnel type terminal top or bottom 1…35 mm² rigid; Tunnel type terminal top or bottom 1…25 mm² flexible; Tunnel type terminal top or bottom 1…25 mm² flexible with ferrule
Wire stripping length
12 mm for top or bottom connection
Tightening torque
2 N.m
Earth-leakage protection
Integrated
Contact position indicator
Contractual warranty
Warranty (in months)
18
Environment
Standards
EN/IEC 60947-2; EN/IEC 61009-2-1
IP degree of protection
IP40 (distribution enclosure) conforming to IEC 60529; IP20 conforming to IEC 60529
Overvoltage category
III conforming to IEC 60364
Electromagnetic compatibility
8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1
Tropicalisation
2
Relative humidity
95 % at 55 °C
Ambient air temperature for operation
-25…60 °C
Ambient air temperature for storage
-40…70 °C
Logistical informations
Country of origin
PT
Main
Range
Acti9
Product name
Acti9 iC60 RCBO
Product or component type
Residual current breaker with overcurrent protection (RCBO)
Device short name
iC60 RCBO
Device application
Distribution
Poles description
4P
Number of protected poles
4
[In] rated current
32 A
Network type
AC
Network frequency
50 Hz
Trip unit technology
Thermal-magnetic
Curve code
B
Earth-leakage sensitivity
30 mA
Suitability for isolation
No conforming to IEC 60947-1
Quality labels
IMQ; VDE; NF; KEMA-KEUR
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
8.200 cm
Package 1 Width
7.200 cm
Package 1 Length
10.200 cm
Package 1 Weight
446.000 g
Unit Type of Package 2
BB1
Number of Units in Package 2
3
Package 2 Height
9.500 cm
Package 2 Width
11.500 cm
Package 2 Length
26.500 cm
Package 2 Weight
1.412 kg
Unit Type of Package 3
S03
Number of Units in Package 3
18
Package 3 Height
30.000 cm
Package 3 Width
30.000 cm
Package 3 Length
40.000 cm
Package 3 Weight
8.990 kg
Residual current circuit breaker with overcurrent protection (FI/LS) Acti 9 iC60N, 6kA (IEC/EN 61009-1 and IEC/EN 61009-2-1), 6kA (IEC/EN 60947-2). 4-pole, nominal current 32A, B characteristic, earth fault sensitivity 30mA, earth fault protection class type A, operating voltage (Ue) 230V AC, insulation voltage (Ui) 500V AC. Guarantees comprehensive protection of final circuits against overcurrents and fault currents. Switching and disconnecting of circuits. Snap action for low-wear switching of the contacts. Mechanically separated red display when the circuit breaker is tripped or when it is tripped by a fault current. Clear switch position display by green marking on the device's switch knob. Test button for regular function testing. Technology of the trip unit - thermomagnetic. Additional auxiliary modules that can be added (optional) - auxiliary switch for status reporting (iOF), error reporting switch (iSD), OF/SD switch with Ti24 interface for status reporting to a programmable logic controller (iOF/SD24). Tool-free installation on the left side of the device. Color RAL 9003. The FI/LS IC60N meets the following standards - IEC/EN 61009-1, IEC/EN 61009-2-1 and IEC/EN 60947-2. This series is also VDE certified!