Complementary
Device location in systemOutgoer
[Ue] rated operational voltage380...415 V AC 50 Hz
Magnetic tripping limit3...5 x In
Residual current tripping technologyVoltage independent
Earth-leakage protection time delayInstantaneous
Earth-leakage protection classType A
Breaking capacity6000 A Icn at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1; 6 kA Icu at 380...415 V AC 50 Hz conforming to EN/IEC 60947-2
[Ics] rated service breaking capacity6000 A 100 % x Icn at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1; 6 kA 100 % x Icu at 380...415 V AC 50 Hz conforming to EN/IEC 60947-2
Rated breaking and making capacityIdm 6000 A at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1
Limitation class1 conforming to EN/IEC 61009-2-1
[Ui] rated insulation voltage500 V AC 50 Hz
[Uimp] rated impulse withstand voltage4 kV
Surge current250 A
Control typeToggle
Local signallingON, OFF, fault trip
Mounting modeClip-on
Mounting supportDIN rail
Comb busbar and distribution block compatibilityTop or bottom: YES; Bottom: biconnect
Connection pitch9 mm between poles
9 mm pitches8
Height86 mm
Width72 mm
Depth78 mm
Net weight423 g
ColourWhite
Mechanical durability20000 cycles
Electrical durability10000 cycles
Connections - terminalsTunnel type terminal top or bottom 1…35 mm² rigid; Tunnel type terminal top or bottom 1…25 mm² flexible; Tunnel type terminal top or bottom 1…25 mm² flexible with ferrule
Wire stripping length12 mm for top or bottom connection
Tightening torque2 N.m
Earth-leakage protectionIntegrated
Contact position indicatorNo
Contractual warranty
Warranty (in months)18
Environment
StandardsEN/IEC 60947-2; EN/IEC 61009-2-1
IP degree of protectionIP40 (distribution enclosure) conforming to IEC 60529; IP20 conforming to IEC 60529
Overvoltage categoryIII conforming to IEC 60364
Electromagnetic compatibility8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1
Tropicalisation2
Relative humidity95 % at 55 °C
Ambient air temperature for operation-25…60 °C
Ambient air temperature for storage-40…70 °C
Logistical informations
Country of originPT
Main
RangeActi9
Product nameActi9 iC60 RCBO
Product or component typeResidual current breaker with overcurrent protection (RCBO)
Device short nameiC60 RCBO
Device applicationDistribution
Poles description4P
Number of protected poles4
[In] rated current32 A
Network typeAC
Network frequency50 Hz
Trip unit technologyThermal-magnetic
Curve codeB
Earth-leakage sensitivity30 mA
Suitability for isolationNo conforming to IEC 60947-1
Quality labelsIMQ; VDE; NF; KEMA-KEUR
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height8.200 cm
Package 1 Width7.200 cm
Package 1 Length10.200 cm
Package 1 Weight446.000 g
Unit Type of Package 2BB1
Number of Units in Package 23
Package 2 Height9.500 cm
Package 2 Width11.500 cm
Package 2 Length26.500 cm
Package 2 Weight1.412 kg
Unit Type of Package 3S03
Number of Units in Package 318
Package 3 Height30.000 cm
Package 3 Width30.000 cm
Package 3 Length40.000 cm
Package 3 Weight8.990 kg
Residual current circuit breaker with overcurrent protection (FI/LS) Acti 9 iC60N, 6kA (IEC/EN 61009-1 and IEC/EN 61009-2-1), 6kA (IEC/EN 60947-2). 4-pole, nominal current 32A, B characteristic, earth fault sensitivity 30mA, earth fault protection class type A, operating voltage (Ue) 230V AC, insulation voltage (Ui) 500V AC. Guarantees comprehensive protection of final circuits against overcurrents and fault currents. Switching and disconnecting of circuits. Snap action for low-wear switching of the contacts. Mechanically separated red display when the circuit breaker is tripped or when it is tripped by a fault current. Clear switch position display by green marking on the device's switch knob. Test button for regular function testing. Technology of the trip unit - thermomagnetic. Additional auxiliary modules that can be added (optional) - auxiliary switch for status reporting (iOF), error reporting switch (iSD), OF/SD switch with Ti24 interface for status reporting to a programmable logic controller (iOF/SD24). Tool-free installation on the left side of the device. Color RAL 9003. The FI/LS IC60N meets the following standards - IEC/EN 61009-1, IEC/EN 61009-2-1 and IEC/EN 60947-2. This series is also VDE certified!
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/328694
qrcode für Schneider Electric A9D87432 FI/LS switch iC60N 4P