Further information for Schneider Electric A9D77432 FI/LS switch iC60N 4P
Additional features
Device position in system
Outlet
[Ue] Operational rated voltage
380 - 415 V AC 50 Hz
Threshold for magnetic actuation
5 - 10 x In
Earth fault trip technology
Voltage-independent
Earth fault protection time delay
Instantaneous
Earth fault protection class
Type A-SI (Superimmunized)
Breaking capacity
6000 A Icn at 380 - 415 V AC 50 Hz conforms to EN/IEC 61009-2-1; 6 kA Icu at 380 - 415 V AC 50 Hz conforms to EN/IEC 60947-2
Rated switching-off capacity Ics
6000 A 100 % x Ics at 380 - 415 V AC 50 Hz conforming to EN/IEC 61009-2-1; 6 kA 100 % x Icu at 380 - 415 V AC 50 Hz conforming to EN/IEC 60947-2
Rated breaking force and rated power
Idm 6000 A at 380 - 415 V AC 50 Hz corresponds to EN/IEC 61009-2-1
Limiting class
1 corresponds to EN/IEC 61009-2-1
[Ui] Rated insulation voltage
500 V AC 50 Hz
[Uimp] Rated impulse voltage withstand
4 kV
Inrush current
3000 A
Control type
Toggle switch
Local signalling
ON, OFF, fault indication
Mounting mode
Plug-in
Mounting bracket
DIN rail
Compatibility of comb rails and distribution blocks
Top or bottom: yes; bottom: dual-function terminal
Terminal pitch
9 mm between poles
9-mm pitch
8
Height
86 mm
Width
72 mm
Depth
78 mm
Product weight
423 g
Colour
White
Mechanical life
20000 cycles
Electrical lifetime
10000 cycles
Connections - terminals
Tunnel terminals top or bottom 1…35 mm² solid; tunnel terminals top or bottom 1…25 mm² fine-stranded; tunnel terminals top or bottom 1…25 mm² fine-stranded with ferrule
Wire stripping length
12 mm for top or bottom connection
[M] tightening torque
2 Nm
Earth fault protection
Integrated
Contact position indicator
Contractual warranty
Warranty (in months)
18
Main features
Product series
Acti9
Product name
Acti9 iC60 RCBO
Product or component type
Residual current circuit breaker with overcurrent protection (FI/LS)
Device short name
iC60 FI/LS
Device application
Distribution
Pole description
4P
Number of protected poles
4
[In] Rated current
32 A
Type of network
AC
Network frequency
50 Hz
Trigger technology
Thermal-magnetic
Cam disc
C
Earth fault sensitivity
30 mA
Suitability for insulation
No, complies with IEC 60947-1
Conformity marking
IMQ; NF; VDE; KEMA-KEUR
Mounting
Standards
EN/IEC 60947-2; EN/IEC 61009-2-1
Degree of protection (IP)
IP40 (distribution cabinet) corresponds to IEC 60529; IP20 corresponds to IEC 60529
Over voltage category
III corresponds to IEC 60364
Electromagnetic compatibility
8/20 µs impulse resistance, 3,000 A conforms to EN/IEC 61009-2-1
Drip-proof
2
Relative humidity
95 % at 55 °C
Operating ambient temperature
-25…60 °C
Ambient temperature during storage
-40…70 °C
Packaging units
VPE 1 type
PCE
Number of devices per package
1
VPE 1 height
7,500 cm
VPE 1 width
8,000 cm
VPE 1 length
10,000 cm
Packaging weight (Lbs)
458,600 g
VPE 2 type
BB1
VPE 2 quantity
3
VPE 2 height
9,500 cm
VPE 2 width
11,000 cm
VPE 2 length
26,500 cm
VPE 2 weight
1,448 kg
VPE 3 type
S03
VPE 3 quantity
18
VPE 3 height
30,000 cm
VPE 3 width
30,000 cm
VPE 3 length
40,000 cm
VPE 3 weight
9,262 kg
Residual current circuit breaker with overcurrent protection (FI/LS) Acti 9 iC60N, 6kA (IEC/EN 61009-1 and IEC/EN 61009-2-1), 6kA (IEC/EN 60947-2). 4-pole, nominal current 32A, C characteristic, earth fault sensitivity 30mA, earth fault protection class type A SI, operating voltage (Ue) 230V AC, insulation voltage (Ui) 500V AC. Guarantees comprehensive protection of final circuits against overcurrents and fault currents. Switching and disconnecting circuits. Snap action for low-wear switching of the contacts. Mechanically separated red display when the circuit breaker is tripped or when it is tripped by a fault current. Clear switch position display through green marking on the device's switch knob. Test button for regular function testing. The SI (superimmunized) version is designed to maintain operational continuity in systems in which high transient leakage currents can occur due to operational reasons or external influences. Technology of the trip unit - thermomagnetic. Additional auxiliary modules that can be added in series (optional) - auxiliary switch for status reporting (iOF), fault reporting switch (iSD), OF/SD switch with Ti24 interface for status reporting to a programmable logic controller (iOF/SD24). Tool-free installation on the left side of the device. Color RAL 9003. The FI/LS IC60N meets the following standards - IEC/EN 61009-1, IEC/EN 61009-2-1 and IEC/EN 60947-2. This series is also VDE certified!