Further information for Schneider Electric A9D56610 RCD 1p+N 10A
Complementary
Device location in system
Outgoer
[Ue] rated operational voltage
230...240 V AC 50 Hz
Magnetic tripping limit
3...5 x In
Residual current tripping technology
Voltage independent
Earth-leakage protection time delay
Instantaneous
Earth-leakage protection class
Type A
Breaking capacity
6000 A Icn at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1
[Ics] rated service breaking capacity
6000 A 100 % x Icn at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1
Rated breaking and making capacity
Idm 6000 A at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1
Limitation class
3 conforming to EN/IEC 61009-2-1
[Ui] rated insulation voltage
400 V AC 50 Hz
[Uimp] rated impulse withstand voltage
4 kV
Control type
Toggle
Local signalling
ON, OFF, fault trip
Mounting mode
Clip-on
Mounting support
DIN rail
Comb busbar and distribution block compatibility
Top or bottom: YES
Connection pitch
9 mm between phase and neutral
9 mm pitches
4
Height
85 mm
Width
36 mm
Depth
73 mm
Net weight
125 g
Colour
White
Mechanical durability
20000 cycles
Electrical durability
20000 cycles
Locking options description
Padlocking device
Connections - terminals
Single terminal top or bottom 1…16 mm² rigid; Single terminal top or bottom 1…10 mm² flexible; Single terminal top or bottom 1…10 mm² flexible with ferrule
Wire stripping length
15 mm for top or bottom connection
Tightening torque
2 N.m top or bottom
Earth-leakage protection
Integrated
Contact position indicator
Contractual warranty
Warranty (in months)
18
Environment
Standards
EN/IEC 61009-2-1; EN/IEC 61009-1
Product certifications
VDE; KEMA
IP degree of protection
IP20 conforming to IEC 60529; IP40 (modular enclosure) conforming to IEC 60529
Pollution degree
3
Overvoltage category
III conforming to IEC 60364
Electromagnetic compatibility
8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1
Tropicalisation
2 conforming to IEC 60068-1
Relative humidity
95 % at 55 °C
Ambient air temperature for operation
-25…60 °C
Ambient air temperature for storage
-40…85 °C
Main
Range
Acti9
Product name
Acti9 iDPN Vigi
Product or component type
Residual current breaker with overcurrent protection (RCBO)
Device short name
iDPN N Vigi
Device application
Distribution
Poles description
1P + N
Number of protected poles
1
Neutral position
Left
[In] rated current
10 A
Network type
AC
Network frequency
50 Hz
Trip unit technology
Thermal-magnetic
Curve code
B
Earth-leakage sensitivity
30 mA
Suitability for isolation
Yes conforming to EN/IEC 60947-2
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
4.000 cm
Package 1 Width
8.000 cm
Package 1 Length
10.000 cm
Package 1 Weight
218.000 g
Unit Type of Package 2
S03
Number of Units in Package 2
54
Package 2 Height
30.000 cm
Package 2 Width
30.000 cm
Package 2 Length
40.000 cm
Package 2 Weight
12.856 kg
The residual current circuit breaker with overcurrent protection (FI/LS) from the Acti9 series by Schneider Electric, type A9D56610, is a 1-pole switch with neutral conductor (1P + N) designed for use in distribution systems. It provides comprehensive protection for final circuits against overcurrents and earth fault currents and is designed for switching and disconnecting electrical circuits. The device features a thermomagnetic tripping mechanism that combines both thermal and magnetic tripping functions, with magnetic tripping occurring at 3 to 5 times the rated current (In). The rated current is 10 A, and the characteristic curve is type B, enabling typical applications in residential and small consumer systems.
Applications
This FI/LS switch is intended for use in electrical distribution systems, particularly in final circuits where protection against electric shock and overload is required. It is designed for operating voltages of 230 to 240 V AC at 50 Hz and complies with standards EN/IEC 61009-2-1 and EN/IEC 60947-2. The rated insulation voltage is 400 V AC, ensuring safe insulation even at higher voltages. The protection rating IP20 (in the device) and IP40 (in the modular housing) according to IEC 60529 makes it suitable for indoor use, with IP40 providing additional protection against contact and contamination.
Functions and Equipment in Detail
The switch includes an integrated residual current protection function with a sensitivity of 30 mA and protection class Type A, suitable for pulsating fault currents. Tripping is instantaneous, ensuring rapid response to dangerous fault currents. A mechanically separated red indicator signals tripping due to earth fault or overcurrent, while a green marking on the operating handle clearly indicates the switch position (ON/OFF). A test button allows regular functional testing of the device. The snap-action switching mechanism ensures wear-free switching of contacts and extends the device’s service life.
Technology Explained Simply
The thermomagnetic tripping technology combines a thermal tripping element for overloads (slow, continuous overload) and a magnetic tripping element for short circuits (fast, high current peaks). The B-characteristic means the switch trips at 1.3 times the rated current after approximately 1 hour, and at 5 times the current within 0.1 seconds. The breaking capacity is 6000 A (Icn) at 230–240 V AC, ensuring high safety during short-circuit events. The rated short-circuit making capacity (Idm) is also 6000 A, highlighting the device’s performance under extreme conditions. The limitation class 3 according to EN/IEC 61009-2-1 indicates the device’s ability to limit the energy of a short circuit.
Compatibility and Accessories
The device is designed for mounting on a DIN rail and can be mounted tool-free on the left side of the device. It is compatible with comb rails and distribution blocks, with connections possible at the top or bottom. The connection terminals support solid cable from 1 to 16 mm² and flexible cable from 1 to 10 mm², with wire end ferrules also being usable. The wire stripping length is 15 mm. Additionally, various auxiliary modules can be added, including undervoltage release (iMN), overvoltage release (iMSU), load current release (iMX), auxiliary switch (iOF), and fault indication switch (iSD), to extend the device’s functionality.
Mounting and Installation
Mounting is done on a DIN rail, with the device being snap-on. The mounting bracket is integrated as standard. Dimensions are 85 mm height, 36 mm width, and 73 mm depth. The device is white (RAL 9003) and has a mechanical life of 20,000 cycles and an electrical life of 20,000 cycles. The operating ambient temperature ranges from -25 °C to 60 °C, and the storage temperature ranges from -40 °C to 85 °C. The relative humidity is up to 95 % at 55 °C. The overvoltage category III according to IEC 60364 makes the device suitable for use in electrical installations not directly connected to the supply voltage.
Operational Advantages
The switch offers high reliability through the combination of residual current and overcurrent protection. Clear indication of switch position and fault tripping simplifies maintenance and diagnosis. Tool-free mounting and compatibility with various accessory modules increase installation flexibility. The high service life and wear-free switching principle ensure long-term operation with minimal maintenance. Certification by VDE and KEMA, along with compliance with standards EN/IEC 61009-2-1 and EN/IEC 60947-2, guarantee the safety and quality of the device.