Further information for Schneider Electric A9D54216 FI/LS switch iC60H 2P
Additional features
Device position in system
Outlet
[Ue] Operational rated voltage
220 - 240 V AC 50 Hz
Threshold for magnetic actuation
5 - 10 x In
Earth fault trip technology
Voltage-independent
Earth fault protection time delay
Instantaneous
Earth fault protection class
Type A
Breaking capacity
10000 A Icn at 220 - 240 V AC 50 Hz complies with EN/IEC 61009-2-1; 15 kA Icu at 220 - 240 V AC 50 Hz complies with EN/IEC 60947-2
Rated switching-off capacity Ics
7500 A 75 % x Ics at 220 - 240 V AC 50 Hz conforming to EN/IEC 61009-2-1; 7.5 kA 50 % x Icu at 220 - 240 V AC 50 Hz conforming to EN/IEC 60947-2
Rated breaking force and rated power
Idm 6000 A at 220 - 240 V AC 50 Hz complies with EN/IEC 61009-2-1
Limiting class
3 corresponds to EN/IEC 61009-2-1
[Ui] Rated insulation voltage
500 V AC 50 Hz
[Uimp] Rated impulse voltage withstand
4 kV
Inrush current
250 A
Control type
Toggle switch
Local signalling
ON, OFF, fault indication
Mounting mode
Plug-in
Mounting bracket
DIN rail
Compatibility of comb rails and distribution blocks
Top or bottom: yes; bottom: dual-function terminal
Terminal pitch
9 mm between poles
9-mm pitch
4
Height
86 mm
Width
36 mm
Depth
78 mm
Product weight
273 g
Colour
White
Mechanical life
20000 cycles
Electrical lifetime
10000 cycles
Connections - terminals
Tunnel terminals top or bottom 1…35 mm² solid; tunnel terminals top or bottom 1…25 mm² fine-stranded; tunnel terminals top or bottom 1…25 mm² fine-stranded with ferrule
Wire stripping length
12 mm for top or bottom connection
[M] tightening torque
2 Nm
Earth fault protection
Integrated
Contact position indicator
Contractual warranty
Warranty (in months)
18
Main features
Product series
Acti9
Product name
Acti9 iC60 RCBO
Product or component type
Residual current circuit breaker with overcurrent protection (FI/LS)
Device short name
iC60 FI/LS
Device application
Distribution
Pole description
2P
Number of protected poles
2
[In] Rated current
16 A
Type of network
AC
Network frequency
50 Hz
Trigger technology
Thermal-magnetic
Cam disc
C
Earth fault sensitivity
300 mA
Suitability for insulation
No, complies with IEC 60947-1
Conformity marking
VDE; NF; KEMA-KEUR; IMQ
Mounting
Standards
EN/IEC 60947-2; EN/IEC 61009-2-1
Degree of protection (IP)
IP40 (distribution cabinet) corresponds to IEC 60529; IP20 corresponds to IEC 60529
Over voltage category
III corresponds to IEC 60364
Electromagnetic compatibility
8/20 µs impulse resistance, 250 A corresponds to EN/IEC 61009-2-1
Drip-proof
2
Relative humidity
95 % at 55 °C
Operating ambient temperature
-25…60 °C
Ambient temperature during storage
-40…70 °C
Packaging units
VPE 1 type
PCE
Number of devices per package
1
VPE 1 height
8,000 cm
VPE 1 width
4,000 cm
VPE 1 length
9,800 cm
Packaging weight (Lbs)
236,000 g
VPE 2 type
BB1
VPE 2 quantity
6
VPE 2 height
10,000 cm
VPE 2 width
11,500 cm
VPE 2 length
25,000 cm
VPE 2 weight
1,482 kg
VPE 3 type
S03
VPE 3 quantity
36
VPE 3 height
30,000 cm
VPE 3 width
30,000 cm
VPE 3 length
40,000 cm
VPE 3 weight
9,458 kg
Residual current circuit breaker with overcurrent protection (FI/LS) Acti 9 iC60H, 10kA (IEC/EN 61009-1 and IEC/EN 61009-2-1), 15kA (IEC/EN 60947-2). 2-pole, nominal current 16A, C characteristic, earth fault sensitivity 300mA, earth fault protection class type A, operating voltage (Ue) 230V AC, insulation voltage (Ui) 500V AC. Guarantees comprehensive protection of final circuits against overcurrents and fault currents. Switching and disconnecting circuits. Snap action for low-wear switching of the contacts. Mechanically separated red display when the circuit breaker is tripped or when it is tripped by a fault current. Clear switch position display through green marking on the device's switch knob. Test button for regular function testing. Technology of the trip unit - thermomagnetic. Additional auxiliary modules that can be added (optional) - auxiliary switch for status reporting (iOF), fault reporting switch (iSD), OF/SD switch with Ti24 interface for status reporting to a programmable logic controller (iOF/SD24). Tool-free installation on the left side of the device. Color RAL 9003. The FI/LS IC60H meets the following standards - IEC/EN 61009-1, IEC/EN 61009-2-1 and IEC/EN 60947-2. This series is also IMQ, NF, KEMA-KEUR, VDE certified!