Further information for Schneider Electric A9D32610 residual current circuit breaker 1p+N 10A
Complementary
Device location in system
Outgoer
[Ue] rated operational voltage
230...240 V AC 50 Hz
Magnetic tripping limit
5...10 x In
Residual current tripping technology
Voltage independent
Earth-leakage protection time delay
Instantaneous
Earth-leakage protection class
Type A
Breaking capacity
6000 A Icn at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1
[Ics] rated service breaking capacity
6000 A 100 % x Icn at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1
Rated breaking and making capacity
Idm 6000 A at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1
Limitation class
3 conforming to EN/IEC 61009-2-1
[Ui] rated insulation voltage
400 V AC 50 Hz
[Uimp] rated impulse withstand voltage
4 kV
Control type
Toggle
Local signalling
ON, OFF, fault trip
Mounting mode
Clip-on
Mounting support
DIN rail
Comb busbar and distribution block compatibility
Top or bottom: YES
Connection pitch
9 mm between phase and neutral
9 mm pitches
4
Height
85 mm
Width
36 mm
Depth
73 mm
Net weight
125 g
Colour
White
Mechanical durability
20000 cycles
Electrical durability
20000 cycles
Locking options description
Padlocking device
Connections - terminals
Single terminal top or bottom 1…16 mm² rigid; Single terminal top or bottom 1…10 mm² flexible; Single terminal top or bottom 1…10 mm² flexible with ferrule
Wire stripping length
15 mm for top or bottom connection
Tightening torque
2 N.m top or bottom
Earth-leakage protection
Integrated
Contact position indicator
Contractual warranty
Warranty (in months)
18
Environment
Standards
EN/IEC 61009-2-1
Product certifications
VDE; KEMA; RCM
IP degree of protection
IP20 conforming to IEC 60529; IP40 (modular enclosure) conforming to IEC 60529
Pollution degree
3
Overvoltage category
III conforming to IEC 60364
Electromagnetic compatibility
8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1
Tropicalisation
2 conforming to IEC 60068-1
Relative humidity
95 % at 55 °C
Ambient air temperature for operation
-25…60 °C
Ambient air temperature for storage
-40…85 °C
Main
Range
Acti9
Product name
Acti9 iDPN Vigi
Product or component type
Residual current breaker with overcurrent protection (RCBO)
Device short name
iDPN N Vigi
Device application
Distribution
Poles description
1P + N
Number of protected poles
1
Neutral position
Left
[In] rated current
10 A
Network type
AC
Network frequency
50 Hz
Trip unit technology
Thermal-magnetic
Curve code
C
Earth-leakage sensitivity
30 mA
Suitability for isolation
Yes conforming to EN/IEC 60947-2
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
4.0 cm
Package 1 Width
8.0 cm
Package 1 Length
10.0 cm
Package 1 Weight
215 g
Unit Type of Package 2
S03
Number of Units in Package 2
54
Package 2 Height
30.0 cm
Package 2 Width
30.0 cm
Package 2 Length
40.0 cm
Package 2 Weight
12.051 kg
Unit Type of Package 3
P12
Number of Units in Package 3
432
Package 3 Height
44.4 cm
Package 3 Width
80 cm
Package 3 Length
120 cm
Package 3 Weight
108.408 kg
The residual current circuit breaker with overcurrent protection (RCCB/OCB) from the Acti9 series by Schneider Electric, type A9D32610, is an iDPN N Vigi device designed for distribution in final circuits. It protects electrical installations and persons against overcurrents as well as dangerous fault currents through integrated earth fault protection. The device is designed for use in networks with 230–240 V AC at 50 Hz and features a rated current of 10 A. The protection function is implemented using a thermomagnetic tripping mechanism, which combines both thermal and magnetic tripping mechanisms to detect overloads and short circuits. The C characteristic curve ensures a sufficiently fast response in the event of short circuits, while the earth fault sensitivity of 30 mA and protection class Type A enable reliable detection of fault currents, including pulsating currents.
Applications
This RCCB/OCB is suitable for use in electrical distribution systems in residential and commercial buildings where high safety standards for power supply to end consumers are required. It is typically mounted in distribution boards to protect individual circuits such as lighting, socket outlets, or small consumers. The integrated switching and disconnection function allows for safe disconnection and isolation of the power supply, which is important during maintenance work or in case of faults.
Functions and Equipment in Detail
The device features a clear switching position indication via a green marking on the operating handle, visually signaling the operational status. In the event of tripping, whether due to overcurrent or fault current, a mechanically separated red indicator is activated, clearly showing the tripped state. An integrated test button enables regular functional testing of the switch to ensure the reliability of the protection function. The snap-action switching ensures wear-free contact switching, increasing the device's service life.
Technology Explained Simply
The thermomagnetic tripping technology combines two principles: during overloads, a bimetal strip heats up and disconnects the contact after a certain time. During short circuits, a magnetic tripping mechanism is activated by the high current and responds immediately. The earth fault protection class Type A detects pulsating fault currents, which may occur in devices with electronic control circuits. The fault current tripping mechanism is voltage-independent, meaning tripping occurs regardless of the network voltage. The rated operational voltage is 230–240 V AC, the rated insulation voltage is 400 V AC, and the rated impulse voltage withstand is 4 kV.
Compatibility and Accessories
The device is designed for mounting on a DIN rail and can be mounted tool-free on the left side of the device. It is compatible with a 9 mm pitch, allowing easy integration into standard distribution enclosures. Various auxiliary modules can be connected, including undervoltage release (iMN), current release (iMX), auxiliary switch for status indication (iOF), and fault indication switch (iSD), to adapt the switch's functionality to specific requirements. Suitable accessories include phase bars, comb rails, remote switches, and interlocking elements, facilitating integration into existing systems.
Mounting and Installation
Mounting is done on a DIN rail, with the device being plug-in. The terminals are designed for solid cables (1…16 mm²) and flexible conductors (1…10 mm²) with or without wire end ferrules. The wire stripping length is 15 mm, and the required tightening torque is 2 Nm. The mechanical and electrical service life is 20,000 cycles each. The protection rating IP20 (within the device) and IP40 (in the modular enclosure) ensures sufficient protection against contact and contamination. The operating ambient temperature ranges from -25 °C to 60 °C, and the storage temperature ranges from -40 °C to 85 °C.
Advantages in Operation
The RCCB/OCB offers high reliability through the combination of overcurrent and residual current protection. The clear indication of switching position and tripping state simplifies diagnosis and maintenance. Tool-free mounting and compatibility with various auxiliary modules increase installation flexibility. Certification according to EN/IEC 61009-2-1 and EN/IEC 60947-2, as well as VDE certification, confirms compliance with European safety standards. The device is designed for use in overvoltage category III and pollution degree 3, enabling application in industrial and commercial environments.
Residual current circuit breaker, overcurrent protection, thermomagnetic, Type A, IP20, DIN rail