| Complementary |
| Test function | Remote test; Local |
| Monitoring | Electronics (continuous) ; Power supply (continuous) ; Relay/sensor link (continuous) |
| Type of measurement | Earth fault current internal measurement, range: 80...100 % |
| Tamperproof of settings | Protected by sealable cover |
| Wire stripping length | Auxiliary power supply: 7 mm for top connection; Fault: 8 mm for bottom connection; Relay test and fault reset: 5 mm for bottom connection; Sensor: 5 mm for top connection; Voltage presence: 8 mm for bottom connection |
| Tightening torque | Auxiliary power supply: 0.6 N.m top; Fault: 0.6 N.m bottom; Relay test and fault reset: 0.25 N.m bottom; Sensor: 0.25 N.m top; Voltage presence: 0.6 N.m bottom |
| 9 mm pitches | 6 |
| Standards | EN/IEC 60947-2 Annex M; EN/IEC 60755; UL 1053; CAN/CSA C22.2 No. 144 |
| Width | 54 mm |
| Height | 81 mm |
| Depth | 74 mm |
| Net weight | 0.3 kg |
| IP degree of protection | IP40 on front face: conforming to EN/IEC 60529; IP30 on side parts: conforming to EN/IEC 60529; IP20 on connection terminals: conforming to EN/IEC 60529 |
| IK degree of protection | IK07 conforming to EN 50102 |
| Mechanical robustness | Fire resistance conforming to IEC 60695-2-1; IK protection 2 joules: IK07 conforming to EN 50102; Vibrations 13.2...100 Hz: 0.7 g; Vibrations 2...13.2 Hz: +/- 1 mm |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Overvoltage category | IV |
| Electrical shock protection class | Class II |
| Electromagnetic compatibility | Conducted and radiated emissions: , B, conforming to CISPR 11; Conducted radio-frequency immunity test: , 3, conforming to IEC 61000-4-6; Electrostatic discharge immunity test: , 4, conforming to IEC 61000-4-2; High-energy conducted susceptibility: , 4, conforming to IEC 61000-4-5; Low-energy conducted susceptibility: , 4, conforming to IEC 61000-4-4; Radiated susceptibility: , 3, conforming to IEC 61000-4-3 |
| Relative humidity | 95 % at 55 °C |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Ambient air temperature for operation | -35…70 °C |
| Ambient air temperature for storage | -55…85 °C |
| Main |
| Range | VigiPacT |
| Device short name | RH10M |
| Product or component type | Residual current protection relay |
| Relay application | Protection relay |
| Mounting support | DIN rail |
| Earth-leakage protection class | Type A |
| Type of setting | None |
| Residual earth-leakage sensitity adjustment type | Fixed |
| Earth-leakage sensitivity | 0.3 A |
| Earth-leakage time delay | Instantaneous |
| Current sensors compatibility | VigiPacT TOA earth leakage current sensor; VigiPacT A earth leakage current sensor; VigiPacT L earth leakage current sensor |
| [Ithe] conventional enclosed thermal current | 8 A |
| Minimum load | 10 mA at 12 V |
| [Us] rated supply voltage | 380...415 V AC 50/60 Hz 55...110 % |
| Power consumption in VA | 4 VA |
| Monitored distribution system | 1000 V - AC at 50/60 Hz (maximum) ; 1000 V - AC at 400 Hz (maximum) |
| Earthing system | TN-S; IT; TT |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Reset | Manual reset |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 8.8 cm |
| Package 1 Width | 8.1 cm |
| Package 1 Length | 9.2 cm |
| Package 1 Weight | 368.0 g |