| Complementary |
| Transformer ratio | 1/1000 |
| Network frequency | 50/60 Hz; 400 Hz |
| [Icw] rated short-time withstand current | 85 kA for 0.5 s |
| Residual short-circuit withstand current | 85 kA / 0.5 s conforming to IEC 60947-2 |
| [Ui] rated insulation voltage | 1000 V |
| Overvoltage category | IV |
| [Uimp] rated impulse withstand voltage | 12 kV |
| Mounting mode | Fixed (cables); Fixed (plain backplate); Fixed (profiled sheet metal); Fixed (slotted backplate); Clip-on (DIN rail) |
| Calorific value | 3.19 MJ |
| Connections - terminals | Screw connection 0.22…2.5 mm² |
| Diameter | 80 mm inner: |
| Net weight | 0.42 kg |
| Height | 122 mm |
| Width | 150 mm |
| Depth | 44 mm |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP30; Connectors: IP20 |
| Environmental characteristic | Exposure to damp heat in service: category C2: 48 hours conforming to IEC 60068-2-56; Exposure to damp heat not in service (25...55 °C, RH 95 %) : 28 cycles conforming to IEC 60068-2-30; Salt mist: Kb/2 conforming to IEC 60068-2-52 |
| Pollution degree | Level 3 conforming to IEC 60664-1 |
| Ambient air temperature for operation | -35…70 °C |
| Ambient air temperature for storage | -55…85 °C |
| Standards | IEC 60947-2 |
| Product certifications | CE |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | VigiPacT |
| Device short name | IA80 |
| Product or component type | Earth leakage current sensor |
| Device application | Equipment monitoring and control |
| current sensor type | A type closed toroid |
| [Ie] rated operational current | 160 A |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.400 cm |
| Package 1 Width | 13.200 cm |
| Package 1 Length | 16.400 cm |
| Package 1 Weight | 317.800 g |
| Unit Type of Package 2 | S04 |
| Number of Units in Package 2 | 40 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 40.000 cm |
| Package 2 Length | 60.000 cm |
| Package 2 Weight | 13.412 kg |
This toroid is designed for Vigilohm insulation fault locators and VigiPacT type A residual current protection and monitoring relays. It allows monitoring the fed component of Vigilohm Insulation Monitor and measuring a nominal current up to 160A for VigiPacT monitoring and protection relays. The transmission ratio is 1/1000. The inner diameter of the toroid is 80 millimeters and the weight is 0.420 kg. The cables must be centered inside the toroid and the diameter of all these cables must not exceed 40 mm. The maximum cross-section per phase (R, S, T, N) is 95mm² for a copper conductor.