| Complementary |
| [Icu] rated ultimate short-circuit breaking capacity | 50 kA at 1150 V AC 50/60 Hz |
| [Ics] rated service breaking capacity | 50 kA at 1150 V AC 50/60 Hz |
| [Icw] rated short-time withstand current | 50 kA 1 s; 50 kA 3 s |
| [Icm] rated short-circuit making capacity | 105 kA 1150 V AC at 50/60 Hz |
| Sensor rating | 2000 A; 4000 A |
| [Ui] rated insulation voltage | 1250 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 12 kV |
| Maximum breaking time | 25 ms |
| Maximum closing response time | 70 ms |
| Mounting support | Backplate; Rails |
| Upside connection | Rear |
| Downside connection | Rear |
| Connection pitch | 150 mm |
| Mechanical durability | 10000 cycles without maintenance; 20000 cycles with maintenance |
| Electrical durability | 500 cycles 1150 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-2 |
| Height | 439 mm |
| Width | 556 mm |
| Depth | 395 mm |
| Net weight | 120 kg |
| Standards | EN/IEC 60947-1; EN/IEC 60947-2 |
| Product certifications | CE; CCC; EAC |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP30 conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Operating altitude | 0...2000 m without derating; 2000 m...5000 m with derating |
| Main |
| Range | MasterPacT |
| Product name | MasterPact NW |
| Circuit breaker name | MasterPact NW40H10 |
| Product or component type | Circuit breaker |
| Device application | Power distribution protection |
| Poles description | 4P |
| Neutral position | Left |
| Control unit | Without control unit |
| [In] rated current | 4000 A at 40 °C |
| Performance type | H10 50 kA 1150 V AC |
| [Ue] rated operational voltage | 1150 V AC 50/60 Hz |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Selectivity category | Category B |
| Control type | Push-button |
| Mounting mode | Drawout |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 0.1 cm |
| Package 1 Width | 0.1 cm |
| Package 1 Length | 0.2 cm |
| Package 1 Weight | 47.0 kg |
MasterPact NT and NW is the proven generation of air circuit breakers up to 6300 A, which incorporate the latest technologies. The MasterPact NT and NW consists of 3 sizes, NT from 630 to 1600A, NW from 800 to 4000A and NWb from 4000 to 6300A. It can be configured as a fixed installation or withdrawable device, or as a circuit breaker or load-break switch. The integrable protection and tripping device MicroLogic can be equipped with a wide range of functions and accessories. Air circuit breaker MasterPact NW 4000A H10 Icu is 50kA at 1150V 4-pole basic switch withdrawable device without Micrologic The Masterpact can be ordered via the online configurator.