| Complementary |
| [Icu] rated ultimate short-circuit breaking capacity | 100 kA Icu at 500 V DC L/R = 5 ms; 25 kA Icu at 900 V DC L/R = 30 ms; 35 kA Icu at 900 V DC L/R = 15 ms; 50 kA Icu at 500 V DC L/R = 30 ms; 50 kA Icu at 750 V DC L/R = 15 ms; 50 kA Icu at 750 V DC L/R = 30 ms; 85 kA Icu at 500 V DC L/R = 15 ms; 85 kA Icu at 750 V DC L/R = 5 ms; 85 kA Icu at 900 V DC L/R = 5 ms |
| [Ics] rated service breaking capacity | 100 kA at 500 V DC (L/R = 5 ms); 25 kA at 900 V DC (L/R = 30 ms); 35 kA at 900 V DC (L/R = 15 ms); 50 kA at 500 V DC (L/R = 30 ms); 50 kA at 750 V DC (L/R = 15 ms); 50 kA at 750 V DC (L/R = 30 ms); 85 kA at 500 V DC (L/R = 15 ms); 85 kA at 750 V DC (L/R = 5 ms); 85 kA at 900 V DC (L/R = 5 ms) |
| [Icw] rated short-time withstand current | 85 kA 1 s |
| [Icm] rated short-circuit making capacity | 100 kA L/R = 5 ms 500 V DC; 25 kA L/R = 30 ms 900 V DC; 35 kA L/R = 15 ms 900 V DC; 50 kA L/R = 30 ms 500 V DC; 50 kA L/R = 15 ms 750 V DC; 50 kA L/R = 30 ms 750 V DC; 85 kA L/R = 15 ms 500 V DC; 85 kA L/R = 5 ms 750 V DC; 85 kA L/R = 5 ms 900 V DC |
| Sensor rating | 1000 A |
| [Ui] rated insulation voltage | 1000 V DC |
| [Uimp] rated impulse withstand voltage | 12 kV |
| Power dissipation in W | 1000 W |
| Maximum breaking time | 30…75 ms |
| Maximum closing response time | 70 ms |
| Mounting support | Backplate; Rails |
| Upside connection | Rear |
| Downside connection | Rear |
| Connection pitch | 115 mm |
| Mechanical durability | 10000 cycles without maintenance conforming to IEC 60947-2; 20000 cycles with maintenance conforming to IEC 60947-2 |
| Electrical durability | 8500 cycles 500 V DC without maintenance conforming to IEC 60947-2; 2000 cycles 900 V DC without maintenance conforming to IEC 60947-2 |
| Height | 439 mm |
| Width | 556 mm |
| Depth | 494 mm |
| Net weight | 125…146 kg |
| Standards | IEC 60947-2 |
| Product certifications | ASTA; ASEFA |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Pollution degree | 4 conforming to IEC 60664-1 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Operating altitude | 0...2000 m without derating; 2000 m...5000 m with derating |
| Main |
| Range | MasterPacT |
| Product name | MasterPact NW DC |
| Circuit breaker name | MasterPact NW10HDC-E |
| Product or component type | Circuit breaker |
| Device application | DC voltage switching |
| Poles description | 4P |
| Control unit | Without control unit |
| [In] rated current | 1000 A at 40 °C |
| Performance type | H 85 kA 500 V DC |
| [Ue] rated operational voltage | 500/900 V DC |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Selectivity category | Category B |
| Control type | Push-button |
| Mounting mode | Drawout |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 0.1 cm |
| Package 1 Width | 0.1 cm |
| Package 1 Length | 0.2 cm |
| Package 1 Weight | 1.0 g |
MasterPact NW-DC is the proven generation of air circuit breakers up to 4000 A, which are designed for direct current networks and contain the latest technologies. The MasterPact NW-DC is available for operating currents of 1000A, 2000A and 4000A at an operating voltage of 500VDC (type N) up to max. 900VDC (type H). It can be configured as a fixed installation or withdrawable device, as a circuit breaker or load-break switch. The integrable MicroLogic 1.0 protection device can be equipped with a variety of functions and accessories. Masterpact NW10HDC-E 1000A 4P basic switch withdrawable device without Micrologic The withdrawable cassette is always included with the Masterpact NW-DC in withdrawable technology