| Complementary |
| Operating threshold | 0.7...1.1 x Un opening |
| Response time | 50 ms +/- 10 % |
| Supply holding power | 4.5 VA |
| Contractual warranty |
| Warranty (in months) | 18 |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | MasterPacT |
| Range of product | MasterPact NW; MasterPact NW DC |
| Device short name | second MX |
| Product or component type | Voltage release |
| Device application | Control |
| Voltage release type | Second opening coil; Instantaneous voltage release |
| Control type | Standard |
| [Uc] control circuit voltage | 100...130 V AC 50/60 Hz; 100...130 V DC |
| Circuit breaker mounting mode | Drawout |
| Range compatibility | Masterpact MasterPact NW; Masterpact MasterPact NW DC |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 3.5 cm |
| Package 1 Width | 6.3 cm |
| Package 1 Length | 8.1 cm |
| Package 1 Weight | 1.168 kg |
This opening coil is used for the instantaneous remote tripping of the MasterPact NT/NW circuit breaker. In conjunction with an XF closing coil and an MCH motor operator, the MasterPact can be remotely controlled. The tripping takes place instantaneously via a working current. Instantaneous voltage release 2. MX 100/130V AC/DC for MasterPact NW/NW withdrawable unit. This opening coil can only be ordered in conjunction with a configured circuit breaker.