| Complementary |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 0.4...1 x In |
| Long-time protection delay adjustment type tr | Adjustable 9 settings |
| [tr] long-time protection delay adjustment range | 0.7…16.6 s at 7.2 x Ir; 0.7…24 s at 6 x Ir; 12.5…600 s at 1.5 x Ir |
| Thermal memory | 20 mn |
| Instantaneous protection pick-up adjustment type Ii | Adjustable 9 settings |
| [Ii] instantaneous protection pick-up adjustment range | 1.5...10 x Ir |
| Earth-leakage protection | Without |
| Zone selective interlocking ZSI | Without |
| Local signalling | 3 LEDs (red) for electrical fault; 1 LED (red) for internal error |
| Display type | Digital display |
| Type of measurement | Energy meter |
| Communication of data | Measurement readout; Protection and alarm settings |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | MasterPact |
| Range of product | MasterPact NW |
| Product or component type | Control unit |
| Trip unit name | MicroLogic 2.0 E |
| Trip unit technology | Electronic |
| Range compatibility | Masterpact NW08...40; Masterpact NW40b...63; Masterpact NW H10; Masterpact NW H2 corrosion protection |
| Device application | Distribution |
| Number of poles | 4P; 3P |
| Protected poles description | 4t; 3t; 3t + N/2 |
| Trip unit protection functions | Basic protection |
| Protection type | for overload protection (long time); for instantaneous short-circuit protection |
| Trip unit rating | 800 A at 50 °C; 1000 A at 50 °C; 1250 A at 50 °C; 1600 A at 50 °C; 2000 A at 50 °C; 2500 A at 50 °C; 3200 A at 50 °C; 4000 A at 50 °C; 5000 A at 50 °C; 6300 A at 50 °C |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Circuit breaker mounting mode | Drawout |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 7.000 cm |
| Package 1 Width | 15.000 cm |
| Package 1 Length | 21.500 cm |
| Package 1 Weight | 370.000 g |
| Unit Type of Package 2 | P06 |
| Number of Units in Package 2 | 32 |
| Package 2 Height | 75.000 cm |
| Package 2 Width | 60.000 cm |
| Package 2 Length | 80.000 cm |
| Package 2 Weight | 26.240 kg |
The Micrologic 2.0 E (energy measurement) is an electronic trip unit used with Masterpact NW circuit breakers. The trip unit is designed to protect circuits and loads. It has adjustable long-term protection against overload and instantaneous short-circuit protection. The Micrologic indicates an overload using an alarm LED. Other tripping causes are indicated by 3 additional LEDs. The device is equipped with a digital LCD screen that displays the actual RMS values for the current with an accuracy of 1.5%. This trip unit can be integrated into a Masterpact NW basic switch.