| Complementary |
| [Icw] rated short-time withstand current | 100 kA 1 s; 100 kA 3 s |
| [Icm] rated short-circuit making capacity | 330 kA 220/415 V AC at 50/60 Hz; 330 kA 440 V AC at 50/60 Hz; 286 kA 525 V AC at 50/60 Hz; 220 kA 690 V AC at 50/60 Hz |
| Integrated instantaneous protection (DIN in kA peak) | 243…297 kA |
| Sensor rating | 3200 A; 6300 A |
| [Ui] rated insulation voltage | 1000 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 12 kV |
| Power dissipation in W | 1200 W |
| Maximum breaking time | 25 ms |
| Maximum closing response time | 80 ms |
| Mounting support | Backplate; Rails |
| Upside connection | Rear |
| Downside connection | Rear |
| Connection pitch | 230 mm |
| Mechanical durability | 10000 cycles with maintenance; 5000 cycles without maintenance |
| Electrical durability | 1500 cycles 440 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-2; 1500 cycles 690 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-2; AC-23A: 1500 cycles 440 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-3; AC-23A: 1500 cycles 690 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-3; AC-3: 6000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-3 |
| Height | 479 mm |
| Width | 786 mm |
| Depth | 395 mm |
| Net weight | 225 kg |
| Standards | EN/IEC 60947-1; EN/IEC 60947-2 |
| Product certifications | CE; CCC; EAC |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP30 conforming to IEC 60529 |
| Pollution degree | 4 conforming to IEC 60664-1 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Operating altitude | 0...2000 m without derating; 2000 m...5000 m with derating |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | MasterPacT |
| Product name | MasterPact NW |
| Circuit breaker name | MasterPact NW63H2 |
| Product or component type | Circuit breaker |
| Device application | Power distribution protection |
| Poles description | 3P |
| Control unit | Without control unit |
| [In] rated current | 6300 A at 40 °C |
| Performance type | H2 150 kA 440 V AC |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Selectivity category | Category B |
| Control type | Push-button |
| Mounting mode | Drawout |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 75.0 cm |
| Package 1 Width | 75.0 cm |
| Package 1 Length | 120.0 cm |
| Package 1 Weight | 132.286 kg |
MasterPact NT and NW is the proven generation of air circuit breakers up to 6300 A, which incorporate the latest technologies. The MasterPact NT and NW consists of 3 sizes, NT from 630 to 1600A, NW from 800 to 4000A and NWb from 4000 to 6300A. It can be configured as a fixed installation or withdrawable device, or as a circuit breaker or load breaker. The integrable MicroLogic protection and tripping device can be equipped with a wide range of functions and accessories. MasterPact NWb 6300A H2 Icu air circuit breaker is 150kA at 440VAC 3P basic switch without Micrologic withdrawable device The Masterpact can be ordered via the online configurator.