Further information for Schneider Electric 48291 disconnector 3p 2000A
Complementary
Control type
Push-button
Mounting mode
Drawout
Mounting support
Chassis
Operating rate
10 cyc/h maximum
[Icw] rated short-time withstand current
65 kA during 1 s conforming to IEC 60947-3; 36 kA during 3 s conforming to IEC 60947-3
Mechanical durability
10000 cycles without maintenance conforming to IEC 60947-3; 20000 cycles with maintenance conforming to IEC 60947-3
Electrical durability
AC-3: 6000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3; AC-23A: 6000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3; AC-23A: 8000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-3
Connection pitch
115 mm
Height
352 mm
Width
442 mm
Depth
297 mm
Net weight
60 kg
Contractual warranty
Warranty (in months)
18
Environment
Standards
IEC 60947-3
Product certifications
ASTA; ASEFA
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-35…85 °C
Logistical informations
Country of origin
FR
Main
Range
MasterPacT
Product name
MasterPact NW
Product or component type
Switch disconnector
Device short name
MasterPact NW20
Switch-disconnector name
MasterPact NW20HA
Device application
Protection
Poles description
3P
Network type
AC
Network frequency
50/60 Hz
[Ie] rated operational current
2000 A AC 50/60 Hz 690 V
[Ui] rated insulation voltage
1000 V AC 50/60 Hz conforming to IEC 60947-3
[Uimp] rated impulse withstand voltage
12 kV conforming to IEC 60947-3
[Icm] rated short-circuit making capacity
143 kA 220...690 V AC at 50/60 Hz
[Ue] rated operational voltage
690 V AC 50/60 Hz conforming to IEC 60947-3
Breaking capacity code
HA
Suitability for isolation
Yes conforming to IEC 60947-3
Pollution degree
4 conforming to IEC 60664-1
Contact position indicator
Visible break
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
30.5 cm
Package 1 Width
29.5 cm
Package 1 Length
37.5 cm
Package 1 Weight
48.434 kg
MasterPact NT and NW is the proven generation of air circuit breakers up to 6300 A, which incorporate the latest technologies. The MasterPact NT and NW consists of 3 sizes, NT from 630 to 1600A, NW from 800 to 4000A and NWb from 4000 to 6300A. It can be configured as a fixed installation or withdrawable device, or as a circuit breaker or load breaker. The integrable MicroLogic protection and tripping device can be equipped with a wide range of functions and accessories. MasterPact NW 2000A HA Icm air circuit breaker is 145kA at 690V 3-pole load breaker withdrawable device without Micrologic The Masterpact can be ordered via the online configurator.