| Complementary |
| [Icu] rated ultimate short-circuit breaking capacity | 150 kA at 220/415 V AC 50/60 Hz; 130 kA at 440 V AC 50/60 Hz; 100 kA at 525 V AC 50/60 Hz |
| [Ics] rated service breaking capacity | 150 kA at 220/415 V AC 50/60 Hz; 130 kA at 440 V AC 50/60 Hz; 100 kA at 525 V AC 50/60 Hz |
| [Icw] rated short-time withstand current | 10 kA 0.5 s |
| [Icm] rated short-circuit making capacity | 330 kA 220/415 V AC at 50/60 Hz; 286 kA 440 V AC at 50/60 Hz; 220 kA 525 V AC at 50/60 Hz; 52 kA 690 V AC at 50/60 Hz |
| Integrated instantaneous protection (DIN in kA peak) | 5.67…6.93 kA |
| Sensor rating | 400 A; 630 A |
| [Ui] rated insulation voltage | 1000 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 12 kV |
| Power dissipation in W | 115 W |
| Maximum breaking time | 9 ms |
| Maximum closing response time | 50 ms |
| Mounting support | Backplate; Rails |
| Upside connection | Front; Rear |
| Downside connection | Front; Rear |
| Connection pitch | 70 mm |
| Mechanical durability | 12500 cycles without maintenance |
| Electrical durability | 3000 cycles 440 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-2; 2000 cycles 690 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-2 |
| Height | 322 mm |
| Width | 288 mm |
| Depth | 277 mm |
| Net weight | 30 kg |
| Standards | EN/IEC 60947-1; EN/IEC 60947-2 |
| Product certifications | CE; CCC; EAC |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP30 conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Operating altitude | 0...2000 m without derating; 2000 m...5000 m with derating |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | MasterPacT |
| Product name | MasterPact NT |
| Circuit breaker name | MasterPact NT06L1 |
| Product or component type | Circuit breaker |
| Device application | Power distribution protection |
| Poles description | 3P |
| Control unit | Without control unit |
| [In] rated current | 630 A at 40 °C |
| Performance type | L1 130 kA 440 V AC |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Selectivity category | Category A |
| Control type | Push-button |
| Mounting mode | Drawout |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 36.000 cm |
| Package 1 Width | 40.000 cm |
| Package 1 Length | 23.000 cm |
| Package 1 Weight | 16.224 kg |
| Unit Type of Package 2 | P12 |
| Number of Units in Package 2 | 16 |
| Package 2 Height | 90.000 cm |
| Package 2 Width | 80.000 cm |
| Package 2 Length | 120.000 cm |
| Package 2 Weight | 271.840 kg |
Masterpact NT06L1, 3 P, 630A, max. breaking capacity 150kA