| Complementary |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 0.4...1 x In |
| Long-time protection delay adjustment type tr | Adjustable 9 settings |
| [tr] long-time protection delay adjustment range | 0.7…16.6 s at 7.2 x Ir; 0.7…24 s at 6 x Ir; 12.5…600 s at 1.5 x Ir |
| Thermal memory | 20 mn |
| Short-time protection pick-up adjustment type Isd | Adjustable 9 settings |
| [Isd] Short-time protection pick-up adjustment range | 1.5...10 x Ir |
| Short-time protection delay adjustment type tsd | Adjustable |
| [tsd] Short-time protection delay adjustment range | 0…0.4 s I²t=off; 0.1…0.4 s I²t=on |
| Instantaneous protection pick-up adjustment type Ii | Adjustable 9 settings |
| [Ii] instantaneous protection pick-up adjustment range | Off; 2...15 x In |
| Ground-fault protection pick-up adjustment type Ig | Adjustable 9 settings |
| [Ig] ground-fault protection pick-up adjustment range | 0.2...1 x In for 400 A < In < 1250 A; 0.3...1 x In for In = 1250 A |
| Ground-fault protection time delay adjustment type tg | Adjustable |
| [tg] ground-fault protection time delay adjustment range | 0…0.4 s I²t=off; 0.1…0.4 s I²t=on |
| Earth-leakage protection | Without |
| Zone selective interlocking ZSI | With |
| Local signalling | 3 LEDs (red) for electrical fault; 1 LED (red) for internal error |
| Display type | Digital display |
| Type of measurement | Energy meter |
| Communication of data | Measurement readout; Protection and alarm settings |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | ComPacT |
| Range of product | ComPacT NS630b...1600 new generation |
| Product or component type | Trip unit |
| Trip unit name | MicroLogic 6.0 E |
| Trip unit technology | Electronic |
| Range compatibility | ComPacT NS630b...1600 |
| Device application | Distribution |
| Number of poles | 4P; 3P |
| Protected poles description | 4t; 3t; 3t + N/2 |
| Trip unit protection functions | Selective + earth-fault protection |
| Protection type | for overload protection (long time); for short time short-circuit protection; for instantaneous short-circuit protection; for earth fault |
| Trip unit rating | 630 A at 50 °C; 800 A at 50 °C; 1000 A at 50 °C; 1250 A at 50 °C; 1600 A at 50 °C; 2000 A at 50 °C; 2500 A at 50 °C; 3200 A at 50 °C |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Circuit breaker mounting mode | Fixed |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 6.8 cm |
| Package 1 Width | 8.0 cm |
| Package 1 Length | 21.5 cm |
| Package 1 Weight | 272.0 g |
Micrologic 6.0E (energy meter) is an electronic control unit used on Compact NS630b to NS3200 fixed circuit breakers. This control unit has selective and earth fault protection (LSIG) and is intended for the protection of circuits and loads. It has adjustable long-term protection against overloads. It also offers adjustable short-term protection and instantaneous protection against short circuits. Micrologic 6.0E offers adjustable earth fault protection. Micrologic 6.0E indicates overloads with an alarm LED. It can indicate the cause of tripping via 3 additional LEDs. Micrologic 6.0E is equipped with a digital LCD display that shows the active energy with an accuracy of 2%. This control unit can be connected to a Compact NS fixed base frame.