Further information for Schneider Electric 31102 load isolator 3P 200A black
Complementary
Control type
Direct front rotary handle
Handle colour
Black
Mounting mode
Fixed
Mounting support
Plate; Rail
Upside connection
Front
Downside connection
Front
Maximum power
AC-23: 110 kW at 440 V AC 50/60 Hz; AC-23: 110 kW at 480 V AC 50/60 Hz (NEMA); AC-23: 132 kW at 500/525 V AC 50/60 Hz; AC-23: 160 kW at 660/690 V AC 50/60 Hz; AC-23: 55 kW at 220/240 V AC 50/60 Hz; AC-23: 55 kW at 230 V AC 50/60 Hz (NEMA); AC-23: 90 kW at 380/415 V AC 50/60 Hz
Rated duty
Uninterrupted
[Icw] rated short-time withstand current
1.8 kA during 30 s conforming to IEC 60947-3; 2.2 kA during 20 s conforming to IEC 60947-3; 4.9 kA during 3 s conforming to IEC 60947-3; 8.5 kA during 1 s conforming to IEC 60947-3
Mechanical durability
15000 cycles
Electrical durability
AC-22A: 1500 cycles 440 V AC 50/60 Hz; AC-22A: 1500 cycles 500 V AC 50/60 Hz; AC-22A: 1500 cycles 690 V AC 50/60 Hz; AC-23A: 1500 cycles 440 V AC 50/60 Hz; AC-23A: 1500 cycles 500 V AC 50/60 Hz; AC-23A: 1500 cycles 690 V AC 50/60 Hz; DC-22A: 1500 cycles 125 V DC 2 poles in series; DC-23A: 1500 cycles 125 V DC 2 poles in series
Connection pitch
35 mm
Height
136 mm
Width
140 mm
Depth
96 mm
Net weight
2 kg
Contractual warranty
Warranty (in months)
18
Environment
Standards
IEC 60947-1; IEC 60947-3
Product certifications
CCC; KEMA-KEUR
IP degree of protection
IP40 conforming to IEC 60529
IK degree of protection
IK07 conforming to EN 50102
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-50…85 °C
Logistical informations
Country of origin
PL
Main
Range
ComPact
Product or component type
Switch disconnector
Product name
ComPacT INS
Poles description
3P
Network type
DC; AC
Network frequency
50/60 Hz
[Ui] rated insulation voltage
800 V AC 50/60 Hz
[Ith] conventional free air thermal current
200 A at 60 °C
[Icm] rated short-circuit making capacity
30 kA switch-disconnector alone 690 V AC at 50/60 Hz; 330 kA with upstream protection circuit breaker 690 V AC at 50/60 Hz
[Ue] rated operational voltage
125 V DC; 690 V AC 50/60 Hz
Pollution degree
3
Suitability for isolation
Contact position indicator
Visible break
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
16.500 cm
Package 1 Width
13.500 cm
Package 1 Length
16.000 cm
Package 1 Weight
2.219 kg
Unit Type of Package 2
S04
Number of Units in Package 2
9
Package 2 Height
30.000 cm
Package 2 Width
40.000 cm
Package 2 Length
60.000 cm
Package 2 Weight
20.673 kg
Compact INS load-break switch. Load-break switch INS250, 200A/690V AC / 250V DC, black rotary drive. Rated current 200 A, number of poles 3. Complete devices with black switch lever. Disconnecting properties in accordance with VDE 0660 Part 100. Rotary drive on the front or side up to INS250.